ALM-BR4-4.3 Manual
10
Copyrights ECOTRONS LLC www.ecotrons.com
How to Communicate to ALM GUI
The 3-pin connector in the picture above is only used for flashing the S19 file. And that is
RS232 bus.
The ModBUS or RS485 communication must be through the regular port “A” and “B”
showed in second picture above.
These two are different communication interfaces. The correct process is:
1) Flash the S19 file via the 3-pin connector on the board using EcoFlash software.
2) Connect the ALM-GUI-
RS485 software tool to Port “A” and “B”, via RS485-USB
converter.
We have not combined the 2 communication interfaces in one software because the
flashing process requires the bootloader to be activated, which is not compatible with
RS485 / ModBUS.