background image

 

 EcoSolar   Energy Conscious Design Limited 

 

10

be confirmed and the valve replaced if there is any doubt over its operation and correct function. 
The function of this valve shall be regularly checked and be appropriately maintained. The tempering 
valve must be suitable for the high temperatures experienced in solar systems 

 

damage to system components.

 Some components installed in conventional hot water 

systems are not compatible with the high temperatures experienced in solar hot water systems. Of 
particular concern are; 

 

mains pressure hot water cylinders which, unless manufactured specifically for use in high 

temperature systems, have a recommended temperature limit. In many cases this will be between 
70

O

C to 80

O

C. The specification of the installed cylinder should be checked and a temperature 

limitation device installed to limit the temperature within the cylinder to within acceptable limits. The 
solar controller has this function and should be programmed to suit.   

 

Pipework. All hot water pipework upstream of the tempering valve should be completed in 

copper. Please be aware that many other alternatives have unacceptable temperature limitations and 
are not suitable for the high temperatures associated with solar hot water systems.  

 
Frost Protection 

Many areas of New Zealand are prone to collectors freezing and subsequent damage, including areas 
which are not renowned for heavy frosts or pipes freezing. By their very nature solar collectors are 
good at absorbing heat, they are also good at absorbing coolth. The collector temperature is raised 
mainly by thermal radiation from the sun, in the same way its temperature is lowered at night by the 
cold night sky. A night sky can, especially on a cold clear night, freeze the water within the solar 
collector even if the ambient temperatures are above 0

O

C.  

 
The water in the collector generally freezes within the pipe risers, the smaller copper tubes that run 
the length of the collector, see Figure 2 below. Once the water in the collector freezes, it generally 
results in the riser splitting and a subsequent leak once the ice has thawed. This split in the pipework 
can generally be repaired by removing the absorber from the collector and brazing.  

 

Antifreeze 

A reliable system of frost protection, indirect systems circulate water with predetermined 
concentrations of a suitable Propylene Glycol antifreeze through the collectors and through a heat 
exchanger to transfer heat to the hot water cylinder.  
 
Being a chemical, the handling and use of Propylene Glycol should be strictly in accordance with the 
manufacturer’s recommendations. The Propylene Glycol should also contain:  

 

a dye to help identify leaks and system failure. If a customer observes dye in the hot water 

from the cylinder they should suspect a leak in the solar system and immediately contact their local 
EcoSolar solar installer for guidance.  

 

a corrosion inhibitor to prevent corrosion in systems containing dissimilar metals.  

 
The PH of the Propylene Glycol mixture should be periodically tested and the mixture replaced as 
necessary usually every year. The discharge of Propylene Glycol should be contained and not left to 
enter the environment or rainwater tanks. If Propylene Glycol does enter a rainwater tank used for 
drinking water, it will have an adverse effect upon the taste of the water and it may be necessary to 

Содержание ESR21-R3

Страница 1: ...Solar Hot Water System Installation Guide...

Страница 2: ...ot Water Heating Installation Guide Energy Conscious Design Limited EcoSolar 15B Saturn Place Albany Auckland Postal PO Box 81049 Whenuapai Auckland New Zealand Phone 09 442 0996 Fax 09 442 0997 E inf...

Страница 3: ...systems 14 Pumped systems 14 Thermosyphon systems 15 System types 16 Mains pressure system 16 Low pressure system 17 Connection to an existing hot water cylinder with no solar system connections 17 C...

Страница 4: ...e glycol 42 System design and over heating 42 Heat dumping 42 Drainback 44 Reliability 47 Existing hot water cylinder heating Source 47 Legionella 49 Safety 50 Periodic Maintenance 50 Glazing maintena...

Страница 5: ...taller should discuss the requirements with the end user to ensure an appropriate system is installed The EcoSolar check sheets should be completed guidance sought and complied with where required and...

Страница 6: ...this is key to the performance of the system and delivering acceptable energy savings System operation and control there are several levels of system operation and control the selection of these is de...

Страница 7: ...EcoSolar Energy Conscious Design Limited 3 Figure 1 Thermosyphon system Figure 2 Indirect pumped drainback system...

Страница 8: ...ould require a larger system with a 300 litre hot water cylinder and multiple collectors The sizing of solar water heating systems for conventional housing is fairly well known however sizing of comme...

Страница 9: ...ntrol and one in the upper half of the cylinder for boosting the water temperature The use of the electric elements the boiler or other heat source should be minimised and ideally should only be switc...

Страница 10: ...emperatures and turn the electric elements or boiler on if required Wetback Combined solar and wetback heated installations are becoming increasingly common The solar system heats the cylinder in the...

Страница 11: ...lowing boosting systems 1 an instantaneous gas water heater as shown in Figure 5 below If the water being heated by the solar system is up to temperature the bypass valve in the hot water supply diver...

Страница 12: ...EcoSolar Energy Conscious Design Limited 8 Figure 6 EcoSolar drainback solar preheat system c w boiler heated booster cylinder...

Страница 13: ...ystem failure or excessive heat being supplied by the solar collector the hot water cylinder could explode causing serious injury death and or damage There have been many such cases and the results ca...

Страница 14: ...mal radiation from the sun in the same way its temperature is lowered at night by the cold night sky A night sky can especially on a cold clear night freeze the water within the solar collector even i...

Страница 15: ...The EcoSolar solar controllers have functions to start the pump and allow warm water to enter the collector when low temperatures are recorded by its sensor in the collector thereby reducing the risk...

Страница 16: ...ers are installed Figure 7 Mechanical frost valves Frost valves rely upon the warm water in the cylinder heating the collectors this therefore results in cooling of the hot water cylinder and thus inc...

Страница 17: ...nders being installed The low and medium pressure cylinders often offer a reduction in water usage which is becoming increasingly important Mains pressure There are now more and more options available...

Страница 18: ...ng hot water cylinder are only suitable for smaller households Retrofit systems will be covered in more detail in a future article Horizontal versus vertical cylinders Vertical cylinders are invariabl...

Страница 19: ...warm water rising from the solar collector into the hot water cylinder Thermosyphon systems can either have the cylinder close coupled to the collectors or have a remote mounted cylinder The systems...

Страница 20: ...If the system installed is a drainback system there will be an overflow from the system If the hot water cylinder is valve vented the existing relief valves should be checked for correct operation and...

Страница 21: ...ion of a four way inlet which allows the cold water supply and warm water returns from the collector to be installed in to the existing cold water connection Alternatively spare lower connections can...

Страница 22: ...the retrofitting of a solar system on to an existing hot water cylinder as shown in Figure 8 and 8 A direct system as highlighted previously is where the water passing through the collectors is drawn...

Страница 23: ...cious Design Limited 19 Figure 8 above shows an open loop solar hot water installation retrofitted on to a cylinder with only bottom entry fittings no bottom dispersion plate This installation uses th...

Страница 24: ...EcoSolar Energy Conscious Design Limited 20 Figure 9 Mains pressure open loop solar hot water installation using side entry connections and retrofit 4 way connection...

Страница 25: ...and corrosion inhibitor however these system are becoming less favourable as the deficiencies of Propylene glycol are becoming understood An indirect Glycol based system is shown in Figure 10 below T...

Страница 26: ...EcoSolar Energy Conscious Design Limited 22 Figure10 Closed loop glycol based system with single pump and heat exchanger in the DHW cylinder...

Страница 27: ...be the most flexible and reliable system and are becoming more commonly installed in NZ As well as the conventional drainback system as shown in Figure 11 below options are available to retrofit a dra...

Страница 28: ...EcoSolar Energy Conscious Design Limited 24 Figure 11 Closed loop drainback system with single pump and heat exchanger in the DHW cylinder...

Страница 29: ...EcoSolar Energy Conscious Design Limited 25 Figure 12 Retrofit indirect drainback system with twin pumps...

Страница 30: ...h increases mixing within the cylinder which reduces the efficiency of the system See Figure below Remote Mounted Cylinder These systems have the collectors on the roof and the cylinder located above...

Страница 31: ...pports shall also be installed immediately either side of pumps valves and changes in direction All hot water pipework is to be insulated using Armstrong Armaflex or similar Pipework shall be flushed...

Страница 32: ...f Care shall be taken to ensure the integrity of the roof is not compromised These shall be in compliance with G12 AS2 Relief Valve The relief valve or relief path shall be sized for the total power o...

Страница 33: ...herefore the vegetation may have to be pruned to prevent shadows Inclination The ideal inclination of the solar collector is at an angle equal to the latitude of the site Deviations greater than 20O w...

Страница 34: ...as shown by a compass X for locations in NZ are shown below Latitude Cape Reinga 17 34 Kaitia 17 5 35 Whangerei 18 36 Auckland 18 5 37 Hamilton 19 38 Taupo 19 5 39 Palmerston North 20 40 Wellington a...

Страница 35: ...esign is required in high extreme wind zone areas such as above a height of 8m above ground level Corrugated Iron sheet roofing Attach collector to roof inclination There are several methods of instal...

Страница 36: ...EcoSolar Energy Conscious Design Limited 32 Figure 14 Fixing method to corrugated iron and long run pan or deep trough roofing...

Страница 37: ...the channel marked out on the roof The collector is then unbolted from the angle brackets The channels are laid horizontally across the roof in the required location The straps are bolted on the chann...

Страница 38: ...EcoSolar Energy Conscious Design Limited 34 Figure 15 Fixing method to tiled roofing...

Страница 39: ...or inclination from roof pitch The concept for increasing the collector pitch off of a pitched roof is shown below The pitch required shall be stated when ordering the fixing kits from EcoSolar Figure...

Страница 40: ...lation requires specific design for the design of the collector mounting frame however the concept is similar to that shown in Figure 16 above Figure 17 presents a potential system Please contact us f...

Страница 41: ...ure is below its maximum temperature The system will often have a backup heating system such as an electric immersion heater To maximise savings these backup heating systems should be left off during...

Страница 42: ...monitor an EcoSolar solar radiation sensor This controller can control up to 3 solar systems allowing the solar collectors to heat up to 3 hot water cylinders swimming or spa pools Multiple arrays of...

Страница 43: ...again resulting in considerable energy usage This controller automates this function by automatically turning the backup heating off once the water is up to temperature There are also more sophistica...

Страница 44: ...m and top of the cylinder respectively Temperature sensor installation Temperature sensors should be installed such that they monitor the water temperature and are not influenced too greatly by their...

Страница 45: ...ers generally have a maximum design temperature that should not be exceeded Many of the hot water cylinders sold in New Zealand are lined steel cylinders these generally have a lower maximum design te...

Страница 46: ...ve collector area will provide too much heat in to the system and lead to overheating unless correctly managed Many installations will experience intermittent hot water draw off such as baches or comm...

Страница 47: ...generation EcoSolar controller is able to automatically control a solar system to prioritise heat to several heating demands and then dump excess heat so to avoid system overheating Figure 22 Closed l...

Страница 48: ...that could be exposed to low or high temperatures should be fully free draining Whilst the pump is turned off there is no water in the collectors there is then no risk of freezing in cold weather and...

Страница 49: ...aximum of about two thirds full of water Provided the system is installed properly the system should operate as follows When there is a heat demand and there is heat to gain from the collector the pum...

Страница 50: ...demand for the client at a cost similar to those for conventional systems and without the maintenance issues associated with propylene glycol The heatstore cylinder is a low pressure copper cylinder w...

Страница 51: ...se involved in that particular installation but it will have a significant impact upon how the industry is perceived and whether such systems are seen as an appropriate solution to the rising cost of...

Страница 52: ...g on the least amount of time and provide the greatest savings Figure 26 One Shot Backup heating controller allows manual control of the backup heating The heating is manually turned on and will be au...

Страница 53: ...me time each week this way the management will hopefully become habitual If the cylinder has two immersion heaters the lower one should be initiated to maximise the amount of water heated Please note...

Страница 54: ...nnually Check solar panels for shading Measure and test Propylene Glycol antifreeze acidity level and colour closed loop glycol systems Check solar system pressure closed loop glycol systems Check wat...

Страница 55: ...elatively easy task aluminium extrusions clip on to secure the glazing in place with a U shaped EPDM seal Lever off and unclip the four outer perimeter extrusions using an approximately 75mm wide leve...

Страница 56: ...lector antifreeze function within the Men Menu shall be programmed and initiated where only water is circulated through the solar collector Where antifreeze is within an indirect circuit no electronic...

Страница 57: ...he front plate Recheck all terminations for correct location and good practice termination Plug in and switch the controller on The controller will go through its checking process and then display the...

Страница 58: ...the down arrow the temperature will blink now press the left and right arrows to change the temperature now press the up arrow to select the temperature The max temperature is always greater than max...

Страница 59: ...nks now use the left and right hand arrows to change the temperature and press the up arrow to select the required temperature 9 Now press the right hand arrow max 2 is displayed on the screen This te...

Страница 60: ...C for most cases change if required using the down arrow then right hand arrows then select using up arrow Now press the right hand arrow this temperature is also to protect the pump it is the tempera...

Страница 61: ...ress the boost switch the green neon on the One Shot will turn on 4 The over ride button should only be used if there is significant water consumption 5 If all the water has not been heated to 60 OC f...

Страница 62: ...he cylinder T3 over a short period of time they will determine the temperature below which additional hot water is required this temperature will vary from household to household and depend upon hot w...

Страница 63: ...wn 5 If the water temperature is below the predetermined set point press the boost switch the green neon on the One Shot will turn on 6 The over ride button should only be used if there is significant...

Страница 64: ...instead installed facing East and West The controller has an internal daily timer which is able to control 3 outputs this function is often used to automate the backup heating The controller will dete...

Страница 65: ...cylinder is being heated regularly to greater than 60O C there is a risk of Legionella establishing itself in the hot water cylinder In order to minimize this risk the water should be heated to 60O C...

Отзывы: