PERFORMANCE RATINGS 

 

ES50LVS 

 

Performance Data - Hot Water Capacities (BTUH) @ 70°F Entering Air Temperature 

WATER PD 

(FT-WG) 

@140°F 

ecosmart 

Air Pressure Drop: 0.04 IWC 

ES50LVS 

Entering Water Temperature 

CFM 

GPM 

110°F 

120°F 

130°F 

140°F 

150°F 

160°F 

170°F 

180°F 

300 

10,640 

13,320 

16,010 

18,700 

21,400 

24,100 

26,800 

29,500 

4.38 

10,910 

13,650 

16,400 

19,160 

21,910 

24,670 

27,430 

30,190 

4.83 

11,070 

13,850 

16,640 

19,430 

22,220 

25,020 

27,820 

30,610 

7.23 

400 

13,170 

16,510 

19,850 

23,200 

26,550 

29,910 

33,270 

36,640 

4.38 

13,640 

17,080 

20,530 

23,980 

27,440 

30,900 

34,370 

37,840 

4.83 

13,920 

17,430 

20,940 

24,460 

27,990 

31,510 

35,040 

38,570 

7.23 

500 

15,370 

19,260 

23,170 

27,090 

31,020 

34,950 

38,890 

42,840 

4.38 

16,050 

20,100 

24,170 

28,250 

32,330 

36,420 

40,520 

44,620 

4.83 

16,470 

20,630 

24,790 

28,970 

33,150 

37,340 

41,530 

45,720 

7.23 

600 

17,280 

21,660 

26,070 

30,490 

34,920 

39,360 

43,810 

48,260 

4.38 

18,190 

22,800 

27,420 

32,050 

36,700 

41,350 

46,010 

50,670 

4.83 

18,770 

23,510 

28,270 

33,040 

37,810 

42,600 

47,390 

52,180 

7.23 

700 

18,950 

23,780 

28,620 

33,480 

38,360 

43,250 

48,140 

53,040 

4.38 

20,110 

25,210 

30,330 

35,470 

40,620 

45,770 

50,940 

56,110 

4.83 

20,850 

26,130 

31,420 

36,730 

42,050 

47,380 

52,710 

58,050 

7.23 

800 

20,440 

25,650 

30,880 

36,140 

41,410 

46,690 

51,980 

57,280 

4.38 

21,840 

27,390 

32,960 

38,550 

44,150 

49,770 

55,390 

61,020 

4.83 

22,740 

28,510 

34,300 

40,100 

45,920 

51,740 

57,580 

63,420 

7.23 

900 

21,760 

27,310 

32,900 

38,500 

44,120 

49,760 

55,410 

61,070 

4.38 

23,400 

29,360 

35,340 

41,340 

47,360 

53,390 

59,430 

65,490 

4.83 

24,480 

30,690 

36,930 

43,190 

49,460 

55,750 

62,040 

68,340 

7.23 

 
 
 
 
 
 
 
 
 
 
 

Содержание ES50LVS

Страница 1: ...P N 14001A PRERAD ES50LVS ES90LVS SELECT MULTI SPEED AIR HANDLER Installation Operation and Maintenance Manual RADIANT 101 Sharer Road Woodbridge ON L4L 8Z3 Tel 905 265 1527 Fax 905 265 9739 ...

Страница 2: ... PIPING DIAGRAMS 13 Tankless Water Heater Piping 13 Boiler Piping 14 ELECTRICAL 15 Electrical Information 15 Thermostat Wiring 15 Ecosmart Wiring Diagram 16 DIP SWITCH OPTIONS 18 Switch Locations 18 Heat CFM ES50LVS 19 Heat CFM ES90LVS 19 Cool CFM ES50LVS 19 Cool CFM ES90LVS 19 Options ES50LVS and ES90LVS 20 SEQUENCE OF OPERATION 20 Multi stage Operation 20 Single stage Operation 21 Cooling Mode M...

Страница 3: ...blower control assembly 24 Thermostat call error 24 External pump does not run 24 External pump is noisy at start up 24 Water heater temperature and pressure relief valve is weeping 24 Insufficient or no heat 25 Cold water at hot faucet 25 Fan runs for cooling but not for heating 25 Heating during standby mode 25 WARRANTY 25 All technical information subject to change without notice ...

Страница 4: ... damage WARNING Improper installation may create a condition where the operation of the product could cause personal injury or property damage Only a qualified contractor installer or service agency should install this product Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual for assistance CAUTION This product must be insta...

Страница 5: ...with unmatched performance Simple independent heat cool and system parameters can easily be set by the installer to adjust for a wide variety of installations The ecosmart features a 5 speed high efficiency EC fan motor and a pump control which can operate a standard 120VAC pump or a variable speed pump from the 0 10V interface that provides LO MED HI functionality MODES OF OPERATION MULTI STAGE f...

Страница 6: ...40 4 38 4 16 050 20 100 24 170 28 250 32 330 36 420 40 520 44 620 4 83 5 16 470 20 630 24 790 28 970 33 150 37 340 41 530 45 720 7 23 600 3 17 280 21 660 26 070 30 490 34 920 39 360 43 810 48 260 4 38 4 18 190 22 800 27 420 32 050 36 700 41 350 46 010 50 670 4 83 5 18 770 23 510 28 270 33 040 37 810 42 600 47 390 52 180 7 23 700 3 18 950 23 780 28 620 33 480 38 360 43 250 48 140 53 040 4 38 4 20 1...

Страница 7: ...680 63 050 69 420 6 27 900 3 24 040 30 150 36 290 42 450 48 610 54 790 60 980 67 180 4 05 4 25 850 32 400 38 980 45 570 52 180 58 800 65 420 72 050 4 19 5 27 010 33 850 40 710 47 580 54 460 61 360 68 260 75 160 6 27 1 000 3 25 430 31 900 38 400 44 920 51 460 58 000 64 560 71 130 4 05 4 27 530 34 520 41 530 48 560 55 610 62 670 69 740 76 810 4 19 5 28 900 36 220 43 560 50 920 58 300 65 690 73 080 8...

Страница 8: ...DATA INCHES Model Overall Dimensions W x D x H Supply Opening W x D Side Return Piping Location A B C D E F G H I J K ES50LVS 14 0 21 0 29 0 11 8 17 8 18 3 14 3 1 4 2 0 2 8 2 4 ES90LVS 21 0 21 0 29 0 18 8 17 8 18 3 14 3 1 4 2 0 2 8 2 4 ...

Страница 9: ... 99A 508CFM 1 07A 482CFM 1 14A 457CFM 1 23A 433CFM 1 29A 405CFM 600CFM 1 86A 670CFM 1 92A 664CFM 2 01A 640CFM 2 08A 624CFM 2 17A 609CFM 700CFM 2 40A 760CFM 2 47A 746CFM 2 59A 730CFM 2 68A 715CFM 2 77A 704CFM 800CFM 3 19A 857CFM 3 26A 840CFM 3 37A 825CFM 3 44A 819CFM 3 53A 803CFM ES90LVS ECM blower performance amps CFM SWITCH SETTING 0 1 WC 0 2 WC 0 3 WC 0 4 WC 0 5 WC 400CFM 0 82A 662CFM 0 88A 555C...

Страница 10: ...he ecosmart and set the room thermostat to heat and set the temperature high enough to initiate a call for heat This will energize the air handler an in turn the fan and pump 6 Once the heat source is supplying hot water check supply and return pipes for a temperature difference to make sure there is flow There should be a noticeable difference in temperature between supply and return lines Use ca...

Страница 11: ...ng coil Use plastic plugs provided to close up holes on upper door Ecosmart Mounting The ecosmart can be installed in upflow downflow and left or right horizontal applications Install the ecosmart with the door in place to make sure the cabinet remains square Flip the unit for downflow applications so that the top of the unit is now the bottom No modification is required for any configuration The ...

Страница 12: ...heating loop connections are made to the domestic water connections The heating loop connections should be positioned horizontally in a vertical section of the domestic water line for both inlet and outlet Refer to the piping schematic for details Connect the heating loop to the domestic water connections as close to the water heater as possible Avoid sections of pipe in the heating loop that can ...

Страница 13: ...ump if it is a variable 0 10V type If the pump is a standard 120VAC type it will operate at a single speed only When set up in single stage mode the pump will operate as a single speed pump The ecosmart controller has a built in pump timer that exercises the pump for 1 minute every 24 hours to prevent the possibility of sticking due to sediment etc Water Heater or Boiler Setup Follow the manufactu...

Страница 14: ...13 P a g e boiler will work in a combo system Make sure any water heater being used is approved for combo applications PIPING DIAGRAMS Tankless Water Heater Piping ...

Страница 15: ...14 P a g e Boiler Piping ...

Страница 16: ...r front panel The ecosmart operates on 120VAC 60Hz single phase line voltage and should have its own dedicated breaker or fuse rated as per the MOP on the ratings label All control circuits are standard 24VAC ecosmart must be grounded via the green wire within the control box Thermostat Wiring Any standard heat cool thermostat is compatible with the ecosmart Wire thermostat to lower right tabs as ...

Страница 17: ...16 P a g e Ecosmart Wiring Diagram ...

Страница 18: ...resume once the call for DHW has ended BOILER dry contacts to initiate heat source AUX 24V 24VAC output for humidifier or other accessory Active when heating is on 0 10V 0 to 10VDC output to drive a variable speed pump if installed Variable speed pump will run at LO MED or HI speeds in the multi stage mode Note if a standard AC pump is used the pump will run at a single speed ...

Страница 19: ... switch is for Heat and Cool CFM rates and the other for system options WARNING to prevent damage use a small screwdriver to change switch position Up is ON as marked on the switch body and each switch is identified with numbers below CFM switches 1 and 2 set Heat CFM rate CFM switches 3 and 4 set Cool CFM rate OPTIONS sets various system parameters ...

Страница 20: ...90LVS MULTI STAGE CFM 0 5 WC SINGLE STAGE CFM 0 5 WC SWITCH 1 SWITCH 2 VAR PUMP STD PUMP 400 400 600 1 600 OFF OFF LO MED HI 1 HI 400 600 800 1 800 ON OFF LO MED HI 1 HI 600 800 1000 1 1000 OFF ON LO MED HI 1 HI 800 1000 1200 1 1200 ON ON LO MED HI 1 HI 1 Multi stage sequences are every 5 minutes until last speed is reached Cool CFM ES50LVS CFM 0 5 WC SWITCH 3 SWITCH 4 400 400 3 OFF OFF 400 600 3 ...

Страница 21: ...ion Thermostat calls for heat R is connected to W Heat generator is turned on Auxiliary 24VAC power is turned on Pump turns on 100 After a 15 second delay to allow for system water to heat up coil fan ramps up as follows 1 Stage 1 Lower HEAT CFM fan speed for 5 minutes If a variable speed pump is installed it runs at LO If a standard single speed AC pump is installed it runs at HI 2 Stage 2 Medium...

Страница 22: ...peed pump is installed it runs at HI If a standard single speed AC pump is installed it runs at HI Thermostat is satisfied R is disconnected from W Heat generator is turned off Auxiliary 24VAC power is turned off Pump turns off and fan speed ramps down to zero extracting any remaining heat in the coil Cooling Mode Multi and Single stage Assumes a condenser and DX coil is installed within the syste...

Страница 23: ...uns at selected HEAT CFM rate If OPTION switch 1 is ON fan runs at 300 CFM ES50LVS 400CFM ES90LVS If fan is set to OFF on thermostat fan runs at HEAT or COOL CFM settings Constant Low Fan Circulation Fan may be run at a low rate using OPTION switch 1 as follows OFF fan runs at rate set by HEAT CFM switch ES50LVS runs at 300 CFM ES90LVS runs at 400 CFM Condenser Lockout If the air out falls below 4...

Страница 24: ...pose will void equipment warranty Filter Inspect the filter monthly and replace remove and vacuum or rinse as required A clogged or inadequate filter may void product warranty Replacement filter size is 16 x 20 x 1 Coils Air conditioning and heating coils should not require cleaning if the filter maintenance schedule is adhered to If a filter is damaged or collapses from plugging dust may foul the...

Страница 25: ...er is present the pump may stick and fail to run Often closing the isolation valve on the return leg and opening the drain port so that water flows through the pump can free this If this fails to free the pump removal for cleaning or replacement is necessary The daily pump exerciser will help prevent pump sticking External pump is noisy at start up If sound has not diminished within 1 minute air m...

Страница 26: ...n heating loop remove restrictions check if valve is stuck isolation valves could be too restrictive or left partially closed after purging or a closed valve Cold water at hot faucet When the heat source is a water heater the most probable cause is reverse flow through the heating loop from a stuck check valve repair or replace valve Fan runs for cooling but not for heating The room thermostat may...

Отзывы: