Error Message No Communication

Error Message No Sensor

Error Message Wireless Sensor Lost

When the thermostat powers up, it will display the nC message 
indicating it has not established communication with the Wiring Hub.  
After about 10 seconds the thermostat will establish communication 
with the Wiring Hub and the nC message disappears.

The nC message will appear anytime communication with the Wiring 
Hub is lost or never established.  Check the wiring between the 
thermostat and Wiring Hub and that the wires are secured in the 
correct  terminals on the thermostat and Wiring Hub.

The thermostat displays the nS message indicating it has not detected 
an upstairs temperature sensor. Check the wiring between the sensor 
and Wiring Hub and that the wires are secured in the correct terminals 
on the Sensor and Wiring Hub.  If a wireless temperature sensor is 
used, be sure the batteries are installed and the wireless sensor is set 
to the correct number. 

The thermostat displays the Err 01 or Err 02 message indicating it has 
lost communication with  an upstairs, wireless temperature sensor.   
Check the batteries in the sensor and be sure they are set to the 
correct sensor#.  If the error message persists, turn the power off to the 
Wiring Hub.  When power is restored, the Wiring Hub automatically 
detects which sensors are being used and clears the error messages.

When an nS error is detected, the thermostat fully opens the Upstairs 
and Downstairs dampers and turns airflow control off as long as the nS 
error persists.  It still maintains control of heating and cooling calls.

When an Err 01 error is 
detected, the thermostat 
alternately displays

When an Err 02 error is 
detected, the thermostat 
alternately displays

Inside

Tu

Day

Upstairs

Auto

Downstairs

Airflow %

COOL

Schedule

AUTO

FAN

MENU

MODE

Cool

Set To

SYSTEM

AM

Inside

Inside

Tu

Tu

Day

Day

Upstairs

Upstairs

Auto

Auto

Downstairs

Downstairs

Airflow %

Airflow %

COOL

COOL

Schedule

Schedule

AUTO

AUTO

FAN

FAN

MENU

MENU

MODE

MODE

Cool

Cool

Set To

Set To

SYSTEM

SYSTEM

AM

WIRING INSTRUCTIONS

Wiring Thermostat to Wiring Hub

Warning!

Use 5-conductor(1 spare), 18 or 20 gage, thermostat cable.

Turn the power to the HVAC equipment off before wiring.

C365

Terminal

5V

GND

SA
SB

Wire Color

Red

White

Blue

Yellow

Wiiring Hub

Terminal

5V

GND

SA
SB

Function

24VAC Power

Common

Signal A
Signal B

+5V

GND

SB

WIRING HUB

SA

Thermostat Model C365C32 or C365C32WF

WIRING DIAGRAM

C365C32

R

EQUIPMENT

C W/B O Y G

US-SNR US-SNR

OD-SNR OD-SNR GND +5V

LIVING SLEEPING
DAMPER DAMPER

SA SB

Wiring Hub Model WH11 or WH32

2

Check for the following error messages:

Содержание Comfort365 C365C32

Страница 1: ...airflow upstairs Operates on 24VAC from the HVAC equipment to the Wiring Hub R and C terminals Hold Schedule or Vacant mode Morning Daytime Evening and Night Weekdays and weekend 5 2 Up down keys adjust the setpoint temperature Temperature setting is held for 4 hours when adjusted in Schedule mode Up down keys adjust the upstairs downstairs airflow Airflow setting is held for 4 hours when adjusted...

Страница 2: ...quired to define the upstairs or downstairs zones the second damper may be plugged into the connector marked OUT on the first damper LEDS on the damper actuator indicate when the damper is fully open green or fully closed red INSTALL UPSTAIRS DOWNSTAIRS DAMPERS Ensure that damper installation does not cause obstruction to the damper blade 2 5V GND SA WIRING HUB SB C365C32 Green LED Red LED Refer t...

Страница 3: ...ge persists turn the power off to the Wiring Hub When power is restored the Wiring Hub automatically detects which sensors are being used and clears the error messages When an nS error is detected the thermostat fully opens the Upstairs and Downstairs dampers and turns airflow control off as long as the nS error persists It still maintains control of heating and cooling calls When an Err 01 error ...

Страница 4: ... Calibrate Downstairs Sensor C A L 5 NA 05 Fan Operation FAn GA Up or EL Down GA Only displayed if GE selected 04 Heating Stages HtG 0 1 or 2 1 Only displayed if HP selected 14 15 16 17 18 19 21 20 22 23 Night Level LCD Backlight Airflow Control On or Off Up Stage Time Maximum Upstairs Airflow in Heating Maximum Downstairs Airflow in Heating Maximum Upstairs Airflow in Cooling Maximum Downstairs A...

Страница 5: ...ge the minimum off time minutes before restarting the compressor Touch NEXT or ENTER Option Option Touch the UP DOWN keys to change the minimum run time minutes before turning a system off Touch NEXT or ENTER Option Touch the UP DOWN keys to change the minimum off time minutes before restarting a gas furnace or electric strip heater Touch NEXT or ENTER 07 Compressor Minimum Off Time Factory Defaul...

Страница 6: ...ENTER Inside2 Option Touch the keys to set the time in minutes to update the upstairs and downstairs airflow Touch or UP DOWN NEXT ENTER Option This is the frequency in minutes that the damper position is updated 15 Calibrate Upstairs Temperature Sensor Factory Default None o Range 5 16 Airflow Update Time Factory Default 2 Minutes Range 1 to 20 Minutes Option Night Touch the key to turn the low l...

Страница 7: ...estore factory settings touch then touch the key NEXT ENTER BACK ENTER UP Option Maximum allowable temperature difference between the upstairs and downstairs temperatures When the temperature difference is equal to or greater than the allowed differential the airflow is adjusted When 2 or more Comfort365 sytems with wireless sensors are installed within 300 feet of one another the installations ha...

Страница 8: ... is too great and causes noise or annoyance Increase the airflow using the key until it is acceptable This is the maximum allowable downstairs airflow in heating Record the airflow value DOWN UP Maximum Allowable Downstairs Airflow in Heating 05 06 Testing Cooling Airflow Limits In Option 5 the system is Off Touch to go to Option 6 to activate cooling Verify the equipment is operating To determine...