9
P-P
150 (50
– 200)
Third Menu {20} (Setting Alarm set point)
Above sets: Alarm is on, Buzzer is on, display flashes, Fan is off (no pulse), and Primary is on
P-A
200 (50
– 230)
Fourth Menu {10 + TBD delay} (Setting Stack off point)
Below sets: All outputs are off, On leaves system running.
P-S
100 (On, 50
– 220)
Fifth Menu {N/A} (Setting Delay time)
Delay between high speed fan pulses when water at or above set point in minutes
P-d
15
(1
– 30)
Sixth Menu {N/A} (Setting Pulse time)
On time of high speed fan pulses when water at or above set point in seconds
P-o
15
(1
– 60)
In program mode up and down arrows will adjust the Setting value within the range given in 5 deg steps (except for delay
and pulse menus). Enter proceeds to the next menu. To exit the user enters through all six menus. The program is saved
after the last menu is exited. This allows the user to abort programming by cycling power before program completion.
However programming must be completed to save the program. No key presses for several seconds during programming
will abort the program and the controller will revert to the normal Fan setting mode and use the previously saved
parameters and ignore any new settings.