- 21 -
Parameter Name
Parameter Name
Parameter Name
Parameter Name
Cell
Cell
Cell
Cell
number
number
number
number
Factory sets
Factory sets
Factory sets
Factory sets
Max
Max
Max
Max
Min
Min
Min
Min
Enter the defrost of the
longest cumulative time
d1
d1
d1
d1
4 hours
12 hours
1 hour
Compressor
enter the
defrost of the
cumulative time firstly
d2
d2
d2
d2
40minutes
99 minutes
20 minutes
defrost of the longest
time
d3
d3
d3
d3
8 minutes
15 minutes
2 minutes
Enter the condition of
the
outdoor coil
temperature
d4
d4
d4
d4
-3℃
0℃
-15℃
Exit the condition of
the
outdoor coil
temperature
d5
d5
d5
d5
15℃
20℃
0℃
4
Function description
1). temp. control target
temp control target is air-conditioner return water temp.
2). function choice
Function choice be decision from Table 3 set 〖b1〗,when 〖b1〗parameter show is”1”then
the machine is heat pump, but when 〖b1〗parameter show is”0”,the machine is cooling only.
3). running model choice
System running models can choice as that:cooling,
heating, if 〖b1〗set is “0”,then the machine is only cooling type,mean that the
running model is cooling just. If 〖b1〗set is “1”, then the model change can be choice when