ECOFOREST ecogeo basic Скачать руководство пользователя страница 25

User manual ecoGEO 

 

54 

 

EN

 

Specification ecoGEO B/C 5-22 

Units 

ecoGEO 

B/C1 

ecoGEO 

B/C2 

ecoGEO 

B/C3 

ecoGEO 

B/C4 

Application 

Place of installation 

Indoors 

Type of brine system

1

 

Geothermal / Aerothermic / Hybrid 

Heating 

 

 

 

 

 

 

 

 

HTR - High temperature recovery system 

 

 

 

 

 

 

 

 

Integrated active cooling 

-- 

 

 

 

 

 

Passive outdoor cooling control 

-- 

 

 

-- 

 

 

Performance 

Compressor range of modulation 

25 to 100 

Heating power

2

, B0W35 

kW 

5,8 to 25 

COP

2

, B0W35 

4,9 

Active cooling power

2

, B35W7 

kW 

-- 

6 to 22 

EER

2

, B35W7 

-- 

Maximum unassisted DHW temperature 

°C 

58 

Maximum assisted DHW temperature

5

 

°C 

70 

Noise emission level

6

 

db 

35 to 46 

Energy label / 

η

s with average temperature control 

-- 

A+++ / 187% 

Operation 
limits 

Heating outlet temperatura range 

°C 

10 to 60 (Max setpoint 60°C) 

Cooling outlet temperatura range 

°C 

4 to 35 (Min setpoint 7°C) 

Brine inlet temperature in heating mode range 

°C 

-25 to +35 

Brine outlet temperature in cooling mode range 

°C 

10 to 60 

Cooling circuit pressure min / max 

bar 

2 / 45 

Production / Pre-load circuit pressure 

bar 

0,5 to 3 / 1,5 

Brine / Pre-load circuit pressure 

bar 

0,5 to 3 / 0,7 

Maximum DHW storage tank pressure 

bar 

8 (Only for ecoGEO C) 

Working fluids 

Refrigerant R410A load 

kg 

1,70 

2,00 

Compressor oil type / load 

kg 

POE / 1,18 

Control 
electrical data 

1/N/PE 230 V / 50-60 Hz

8

 

 

 

Maximum recommended external protection

9

 

C16A 

Transformer primary circuit fuse 

0,5 

Transformer secondary circuit fuse 

2,5 

Electrical data: 
Single phase 

1/N/PE 230 V / 50-60 Hz

8

 

 

 

Maximum recommended external protection

9

 

C50A 

Maximum consumption

2

, B0W35 

kW/A 

5,6/28,2 

Maximum consumption

2

, B0W55 

kW/A 

7,8/39,2 

Starting current min/max 

7

 

6,1/15,7 

Correction of cosine φ

 

0,96-1 

Electrical data: 
Three phase 

3/PE 400 V / 50-60 Hz

8

 

 

 

Maximum recommended external protection

9

 

C20A 

Maximum consumption

2

, B0W35 

kW/A 

5,6/8 

Maximum consumption

2

, B0W55 

kW/A 

7,8/11,2 

Starting current min/max 

7

 

2/5,2 

Correction of cosine φ

 

0,96-1 

Dimensions 
and weight 

Height x width x depth 

mm 

ecoGEO B: 1060x600x710 
ecoGEO C: 1804x600x710 

Empty weight (without assembly) 

Kg 

B: 185 
C: 247 

B: 193 
C: 255 

B: 185 
C: 247 

B: 193 
C: 255 

1.

 

Replacing or combining the geothermal collector with one or more ecoGEO AU12 aerothermal units. Refer to the ecoGEO AU12 aerothermal 
units manual for more detailed information. 

2.

 

In compliance with EN 14511, this includes the consumption of the circulation pumps and the compressor driver. 

3.

 

Considering brine and production flows of 2500 l/h. 

4.

 

Considering a heat ramp of 20°C to 50°C in absence of consumption. 

5.

 

Considering support provided by the emergency electrical resistor or the HTR system. Maximum DHW temperature with the HTR system can 
be limited by the compressor discharge temperature. 

6.

 

In compliance with EN 12102, this includes the acoustic insulation kit of the compressor. 

7.

 

Starting current depends on working condition of the hydraulic circuits. 

8.

 

The admissible voltage range for proper operation of the heat pump is ±10%. 

9.

 

Maximum consumption can vary significantly according to working conditions, or if the compressor's range of operation is restricted. Refer 
to the technical service manual for more detailed information. 

 

 

 

Содержание ecogeo basic

Страница 1: ...USER MANUAL EN 05 2018 SERVICE CONTACT MODEL ecoGEO Basic ecoGEO Compact ecoGEO HP...

Страница 2: ...0 3 7 List of user menus 42 3 8 Parameter adjustment 43 3 9 ON OFF Menu 43 3 10 CALENDAR Menu 44 3 11 HEATING Menu 44 3 12 COOLING Menu 45 3 13 DHW LEGIONELLA PROT Menu 46 3 14 POOL Menu 47 3 15 INFOR...

Страница 3: ...jury resulting from improper use or incorrect installation of the equipment The heat pump must be installed by a licensed installer in accordance with applicable local regulations and in accordance wi...

Страница 4: ...rted up The controller monitors a large number of parameters and will produce a warning if any problem arises It is simply necessary to ensure that the installation is checked regularly by an authoris...

Страница 5: ...s points of consumption DHW heating etc The transfer of energy from one circuit to another takes place through heat exchangers where the higher temperature fluid transfers heat to the fluid at a lower...

Страница 6: ...DHW Auxiliary integrated hot water equipment Another installation option is a 4 kW ecoGEO 1 9 or 6 kW ecoGEO 3 12 and ecoGEO 5 22 electrical resistor in the production circuit This resistor can be use...

Страница 7: ...l geothermal brine systems Control of all nothing or modulating external support units Joint management of several parallel heat pumps up to 3 in ecoGEO B C and as many as 6 in ecoGEO HP Simultaneous...

Страница 8: ...user menus and to adjust the parameters Figure 3 1 Control panel The general functions of each of the buttons and operation is indicated below The ALARMS menu can be accessed directly from anywhere i...

Страница 9: ...nsumption bar is also shown for the compressor and modulating circulator pumps Aerothermal fan activated only for ecoGEO B C versions Brine pump activated Compressor in start up phase Compressor activ...

Страница 10: ...he differential of start up temperatures DHW mode The heat pump sends hot water to increase the temperature of the storage tank so it reaches the DHW setpoint temperature as soon as possible This mode...

Страница 11: ...peration program determines which operation modes can be activated WINTER program The heat pump does not allow activation of the PASSIVE COLD and ACTIVE COLD operating modes SUMMER program The heat pu...

Страница 12: ...functions EMERGENCY status from control panel The heat pump is in emergency status activated manually from the front panel of the controller The compressor cannot be started up but the services can b...

Страница 13: ...w desired information Figure 3 3 Browsing through the list of user menus XXXXXX XXXXXX XXXXXX Mon 4 5 7 5 4 5 User menu 8 On Off Schedule Heating User menu 8 On Off Schedule Heating User menu 3 8 Sche...

Страница 14: ...s or next screen or to return to the list of user menus Figure 3 4 Adjusting comfort parameters 3 9 ON OFF Menu On Off Shows the direction of the unit Used to switch the heat pump on off or to activat...

Страница 15: ...is can be used to program up to 3 periods a year when the heat pump stays on or off 3 11 HEATING Menu Heating This enables the HEATING mode and adjusts the heating cut off temperature The HEATING mode...

Страница 16: ...t off temperature Only PASSIVE COOLING can be activated for outside temperatures between passive and active cut off temperatures ACTIVE COOLING activation is only allowed for outside temperatures over...

Страница 17: ...active alarms that prevent compressor start up In SUPPORT mode the auxiliary system is activated after the compressor when the latter cannot reach the target DHW storage tank temperature DHW Recircula...

Страница 18: ...n menu from the main screen Brine Production This shows the inlet and return temperatures temperature difference current pressure and the percentage of circulator pump regulation in the brine and prod...

Страница 19: ...compressor and condenser operation Compressor 2 This displays the registry of compressor hours of operation number of start ups and start up hour ratios It also shows the current temperature of the c...

Страница 20: ...EMERGENCY mode when a critical alarm goes off more than 5 times a day In these cases the heat pump can be unblocked from this screen once the problem has been solved Log alarms The heat pump stores t...

Страница 21: ...emperature again Indoor room temperature low in HEATING mode high in COOLING mode Incorrect operation program Select the appropriate program HEATING COOLING mode deactivated Activate the HEATING COOLI...

Страница 22: ...and the main screen shows If the problem is solved these alarms disappear and the heat pump starts to operate automatically The button flashes red to indicate that the error has been solved The butto...

Страница 23: ...ded external protection9 A C25A Maximum consumption2 B0W35 kW A 2 7 11 8 Maximum consumption2 B0W55 kW A 3 8 16 5 Starting current min max 7 A 2 8 5 8 Correction of cosine 0 96 1 Electrical data Three...

Страница 24: ...rnal protection9 A C32A Maximum consumption2 B0W35 kW A 4 2 18 6 Maximum consumption2 B0W55 kW A 5 21 7 Starting current min max 7 A 2 8 Correction of cosine 0 96 1 Electrical data Three phase 3 PE 40...

Страница 25: ...xternal protection9 A C50A Maximum consumption2 B0W35 kW A 5 6 28 2 Maximum consumption2 B0W55 kW A 7 8 39 2 Starting current min max 7 A 6 1 15 7 Correction of cosine 0 96 1 Electrical data Three pha...

Страница 26: ...king fluids Refrigerant R410A amout kg 4 0 4 2 Compressor oil type amout kg POE 3 3 Antifreeze fluid recommended for the source4 Propylene glycol Brine nominal flow B0W351 T 3 C l h 2405 to 9830 Produ...

Страница 27: ...ids Refrigerant type amout kg R410A 4 7 R410A 5 5 Compressor oil type amout kg POE 3 6 Antifreeze fluid recommended for the source4 Propylene glycol Brine nominal flow B0W351 T 3 C l h 3230 to 13195 P...

Страница 28: ...fluids Refrigerant type amout kg R410A 8 5 R410A 9 1 Compressor oil type amout kg POE 6 7 Antifreeze fluid recommended for the source4 Propylene glycol Brine nominal flow B0W351 T 3 C l h 4765 to 193...

Страница 29: ...document that supports the date of purchase duly stamped and signed from the establishment that made the sale Disclaimer of warranty The warranty does not include product non conformities derived from...

Страница 30: ......

Страница 31: ...cela 139 36316 Vincios Gondomar Pontevedra Spain Tel 34 986 262 184 34 986 417 700 Fax 34 986 262 186 e mail Info ecoforest es http www ecoforest es The manufacturer reserves the right to make any nec...

Отзывы: