- pag.11 -
LB1312
Oilflam 700.1-800.1 PR/MD
POSITION OF IGNITION ELECTRODES
For a correct burner ignition, carefully respect the dimensions shown by the picture
5 ÷ 6 mm
3 ÷ 4 mm
Out 1(
90°
)- Out 2(
115°
)- Out 3(
118°
)- Out 4(
120°
).
- To modify factory temperature setting act as follows:
- press key “
F
”
- the led Out 1 starts to flash, if You need to modify minimum oil temperature press increase or decrease
button, after confirm the new value pressing again “
F
”
- if You need to modify an other temperature press again “
F
” untill You the relevant led flashes.
Please take care: if key “
F
” is pressed for a too long time, You enter in “configuration level” phase1, (see
“CF1” on the display); these parameters are Factory setted and they have not to be modified: if You enter
this function – You see “CF1” flashing on the display – wait 10 seconds untill the regulator automatically
goes out from “configuration level”.
BURNER MAINTENANCE