pag.27

LB972  

MULTICALOR 300.1-400.1 PR/AB     

B

SETTING PARAMETERS

When the burner is ignited all displays of the regulator light up.  The set point display will blink for about 10 seconds.  The value

in the upper field of the display (red) indicates the actual value.  The value in the lower field of the display (green) indicates the set

point currently programmed. 

CHANGING THE SET POINT

To change the set point, proceed as follows: 

--

--

Press the 

PGM

PGM

button to access the user level. SP1* will appear in the lower display

--

--

  

  

Change the value of set point SP1 using the t and s keys.

.

--

--

  

  

After a 2 second delay the value set is stored automatically – To

return to normal display press 

EXIT

EXIT

**

The value of SP1 depends on the value set previously in configuration level 

C111

.

SETTING PID PARAMETERS

PID parameters are factory set to standard mean values.  The operation of the regulator can be self-adapted to suit the system by

activating the “tunE” function. The regulator will set the PID parameters automatically.  To activate the “tunE” function proceed

as follows:  

--

--

  

  

With the burner in operation, press  

PGM 

PGM 

--

--

  

  

the caption “tunE*” will blink in the display. – When “tunE” stops

blinking, the self-adaptation routine has been completed. 

--

--

  

  

Confirm the computed parameters by pressing the 

key for 2 seconds. 

**  

The “tunE” function cannot be activated in Manual mode, or when the burner is off. 

The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the derivati-

ve action time dt and the integral action time rt. 

To change parameters Pb1, dt and rt, proceeds as follows: 

--

--

  

  

Press the 

PGM

PGM

button to access the parameters level. 

--

--

  

  

To move from

one parameter to the next, press 

PGM

PGM

--

--

  

  

When 

Pb1

is displayed, the value can be increased or decreased using the s and t keys.  

--

--

Confirm the changed parameters by pressing 

PGM

PGM

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored auto-

matically. 

--

--

  

  

Press 

PGM

PGM

to access the next parameter. 

--

--

  

  

When dt is displayed, repeat the procedure described above. 

--

--

  

  

Press PGM

to access the next parameter. 

--

--

  

  

When rt is displayed, repeat the procedure above. 

--

--

  

  

To return to normal display press  

EXIT

EXIT

DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFF

The regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.

HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power.  HYS3 indicates

the upper shutoff limit, above which the regulator switches the burner off.  To set HYS1 and HYS3 proceed as follows: --

--

  

  

Press

the 

PGM

PGM

key to access the parameters level. 

--

--

  

  

To move from one parameter to the next, press 

PGM

PGM

--

--

  

  

When 

HYS1

is displayed

(burner ignition differential-stage II), increase or decrease the value using the 

and 

keys. 

--

--

  

  

Confirm the changed parameters by

pressing 

PGM

PGM

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored automatically. 

--

--

  

  

Press 

PGM

PGM

to access the

next parameter. 

--

--

  

  

When 

HYS2

is displayed (burner shutoff differential-stage II), repeat the procedure described above. 

--

--

  

  

Press

PGM

PGM

to access the next parameter. 

--

--

  

  

When 

HYS3

is displayed (upper shutoff differential) repeat the procedure described above. 

--

--

  

  

To return to normal display press 

EXIT

EXIT

MANUAL/AUTOMATIC MODE

To access “MANUAL” mode, press and hold 

EXIT

EXIT

for at least 5 seconds.  Manual mode can only be selected when the burner is

in operation.  It is deactivated automatically when the burner shuts off.  When the LED above the hand symbol is alight, the regu-

lator is in manual mode and the position of the servocontrol can be changed using the 

and 

keys. The LEDS on the front of

the regulator indicate whether the servocontrol OPEN or CLOSE command is currently active.  Pressing the 

key the servocon-

trol OPENS. Pressing the 

key the servocontrol CLOSES.  To select automatic mode press and hold 

EXIT

EXIT

for at least 5 seconds.

The LED above the hand symbol goes out and the regulator reverts to automatic. 

CLIMATIC COMPENSATION

The RWF 40 regulator can be set with the set point interlocked to the external probe.  To select this operating mode, proceed as

follows:  

--

--

  

  

Connect the required probe as in the wiring diagram.  

--

--

  

  

Change the regulator settings.  When using an external probe

the regulator must be set as follows:  

--

--

  

  

Press the 

PGM

PGM

key to access the configuration level.  When the caption 

C111

(XXXX) is

displayed, use the 

key to access the second figure (XXXX).  Use the 

key to select the type of probe (XX3X).  

--

--

  

  

Confirm the

change of  parameters by pressing 

PGM

PGM

.  If this is not done within 2 seconds, the value is stored automatically  

--

--

  

  

Press 

PGM

PGM

to

access the configuration level.  When the display reads 

C112

(XXXX), use the 

key to access the second figure (XXXX).  Press the

key to set the type of probe (XX3X).  

--

--

  

  

Confirm the changed parameters by pressing 

PGM

PGM

.  

--

--

  

  

If confirmation is not given

within 2 seconds the value will be stored automatically.  

--

--

  

  

To return to normal display press 

EXIT

EXIT

. To establish the heating curve, proceed as follows: 

--

--

  

  

Press 

PGM

PGM

to access the parameters level.  

--

--

  

  

Press 

PGM

PGM

to move from one parameter to the next.  

--

--

  

  

When the letter H is

displayed (heating curve gradient), increase or decrease the value using the 

and 

keys.  

--

--

  

  

Confirm the changed parameters by

pressing 

PGM

PGM

.  

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored automatically.  

--

--

  

  

To return to normal display press 

EXIT

EXIT

.

Содержание Multicalor 300.1 PR

Страница 1: ...LB1448 20 07 2005 Multicalor 300 1 PR MD Multicalor 400 1 PR MD Light oil Natural gas 40 300 mbar Light oil LPG 75 300 mbar MODELS A BRUCIATORI MISTI GAS GASOLIO B GAS LIGHT OIL DUAL BURNERS...

Страница 2: ...atural Gas L C V 8 570 kcal Nm3 LPG L C V 22 260 kcal Nm3 Light oil L C V 10 200 kcal kg max visc 1 5 E at 20 C OVERALL DIMENSIONS Burner output Backpressure in combustion chamber I M L E D D1 F C B A...

Страница 3: ...the air servocontrol in approximately 30 seconds time When the servocontrol is fully open a signal to the electronic control unit starts the 66 seconds pre purge cycle At the end of the prepurging tim...

Страница 4: ...ation probe which cuts in and sets the burner shutdown within the safety time In case of gas lack or a major pressure drop the minimum air pressure switch shuts down the burner Ref Description t1 Dura...

Страница 5: ...STING THE MAXIMUM CAPACITY OF THE GAS Position the selector situated on the control panel on position 1 and proceed as follows Adjusting the maximum gas flow rate see figure on solenoid valve adjustme...

Страница 6: ...p cover M ADJUSTMENT OF THE AIR PRESSURE SWITCH Unscrew screws A and B and remove cover C Set the pressure switch to the mini mum by turning regulator D to position 1 Start the burner and keep in low...

Страница 7: ...st be suitable for burner The connection of boiler s thermostats and all the safeties The motor rotation direction The correct calibration of the motor s thermal protection When all the above mentione...

Страница 8: ...button on the control box If after a successful pump priming the burner locks out after the prepurging due to a fuel pressure drop in the pump rearm the burner s lock out to restart the burner Do neve...

Страница 9: ...p 5 Selector 0 Loking of devoices for operating at intermediate outputs Operation at max output Operation at min output AUTO Automatic operation 6 Main switch I O 7 Selector 0 Light oil Gas 8 Lockout...

Страница 10: ...ses are blown out The control box is faulty THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE Check the fan and the air pressure Check the air pressure switch Control box faul...

Страница 11: ...LOSE 1st Stage Increase power OPEN 2nd Stage Two stage operation Description of display and keys on the RWF 40 microprocessor regulator The figure shows the normal display indicating the actual value...

Страница 12: ...to access the parameters level To move from one parameter to the next press PGM PGM When HYS1 is displayed burner ignition differential stage II increase or decrease the value using the and keys Conf...

Страница 13: ...1 Connection for probe QAE2 passive probe Water probe Configuration code C111 9XXX Connection for probe FT TP passive probe Degusa probe Configuration code C111 5XXX Connection for probe QBE620 P act...

Страница 14: ...faulty the regulator will not indicate the real value Situation The number 1999 blinks in the display as the actual value with SP E showing in the set point field Cause The external set point value i...

Страница 15: ...e relative opening in the electrical panel A Insert the fixing anchors and screws into the slots and secure the unit to the panel B To open the regulator squeeze the cover from the ends as shown and l...

Страница 16: ...ive probe QBE620 P QAE22 FT TP 1000 P4 P10 P16 P25 P40 Analog input 1 2 and 3 setpoint changeover shift C111 9030 5030 G000 G000 G000 G000 G000 Limit comparator controller type setpoint 1 locking C112...

Страница 17: ...A UV 19 03 1998 Q N BEM43167 3 MULTICALOR 300 1 400 1 500 1 PR PR LANDIS SQM 50 481A2 LANDIS LFL 1 622 VPS 504 UV 11 03 2005 FMP 95 96 KMV R S T NO FMV MV U V W FMP MP U V W S R T KMP R S T NO SAMA 1...

Страница 18: ...TV MV MP KA FU Z Q SWITCH OIL GAS COMMUTATORE GASOLIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS THERMOSTAT GRANDE PETIRE ALLURE HIGH LOW FLAME THERMOSTAT TERMOSTATO DI ALTA BASSA FIAMMA COMM...

Страница 19: ...2005 FMP 95 96 KMP R S T NO KMV R S T NO MP U V W MV U V W Q HLB FMV FMP S R 10 11 8 5 6 7 9 T N FMV 95 96 SAgG 1 2 3 0 SAMA 1 2 3 0 FMV 97 98 HLBT GAS 2 GASOLIO 1 COMMUTATORE ALTA BASSA FIAMMA SWITC...

Страница 20: ...LIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS TERMOSTATO DE SEGURIDAD COMMUTATORE MANUALE AUTOMATICO SWITCH MANUAL AUTOMATIC INTERRUPTEUR MANUEL AUTOMATIQUE CONMUTADOR MANUAL AUTOMATICO THERM...

Страница 21: ...1 33 LFL 1 622 VPS 504 UV 22 06 2005 FMP 95 96 KMV R S T NO FMV MV U V W FMP MP U V W S R T KMP R S T NO SAMA 1 2 3 0 HLBT FMV 97 98 SAgG 1 2 3 0 GAS 2 GASOLIO 1 T P STC 50 Hz 400V HLB STAB T P STS R...

Страница 22: ...MP KA FU Z Q SWITCH OIL GAS COMMUTATORE GASOLIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS THERMOSTAT GRANDE PETIRE ALLURE HIGH LOW FLAME THERMOSTAT TERMOSTATO DI ALTA BASSA FIAMMA COMMUTATOR...

Страница 23: ...6 Q N BEM43188 1 MULTICALOR 300 1 400 1 500 1 PR PR LANDIS SQM 50 481A2 LANDIS LFL 1 333 LFL 1 622 PREDISPOSTO UV 03 11 2005 FMP 95 96 KMV R S T NO FMV MV U V W FMP MP U V W S R T KMP R S T NO SAMA 1...

Страница 24: ...TATORE GASOLIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS THERMOSTAT GRANDE PETIRE ALLURE HIGH LOW FLAME THERMOSTAT TERMOSTATO DI ALTA BASSA FIAMMA COMMUTATORE MANUALE AUTOMATICO SWITCH MANUAL...

Страница 25: ...400 1 PR AB Multicalor 300 1 PR MD Multicalor 400 1 PR MD 7 8 36 11 14 4 6 5 3 9 10 39 26 31 29 30 27 34 32 33 52 35 28 2 37 20 13 12 25 24 22 23 19 21 17 16 15 18 1 41 50 51 44 43 47 53 38 49 42 46 4...

Страница 26: ...802 2 24 REL BASE Finder 5532 R905 R905 Finder 5534 R906 R906 25 REL Finder 5532 R711 R711 Finder 5534 R712 R712 26 UV CELL LANDIS QRA 2 A205 A205 27 IGNITION CABLE TC BFE01403 2 BFE01403 2 TL BFE0140...

Страница 27: ...right to make without any prior notice all those modifications which it deems usefull and or necessary in order to improve the quality of its products without affecting their main features CEcoflam S...

Отзывы: