background image

pag.21

LB 832   

BLU 5000.1 - 6000.1 PR / MD    

B

SETTING PARAMETERS

When the burner is ignited all displays of the regulator light up.  The set point display will blink for about 10 seconds.  The value

in the upper field of the display (red) indicates the actual value.  The value in the lower field of the display (green) indicates the set

point currently programmed. 

CHANGING THE SET POINT

To change the set point, proceed as follows: 

--

--

Press the 

PGM

PGM

button to access the user level. SP1* will appear in the lower display

--

--

  

  

Change the value of set point SP1 using the t and s keys.

.

--

--

  

  

After a 2 second delay the value set is stored automatically – To

return to normal display press 

EXIT

EXIT

**

The value of SP1 depends on the value set previously in configuration level 

C111

.

SETTING PID PARAMETERS

PID parameters are factory set to standard mean values.  The operation of the regulator can be self-adapted to suit the system by

activating the “tunE” function. The regulator will set the PID parameters automatically.  To activate the “tunE” function proceed

as follows:  

--

--

  

  

With the burner in operation, press  

PGM 

PGM 

--

--

  

  

the caption “tunE*” will blink in the display. – When “tunE” stops

blinking, the self-adaptation routine has been completed. 

--

--

  

  

Confirm the computed parameters by pressing the 

key for 2 seconds. 

**  

The “tunE” function cannot be activated in Manual mode, or when the burner is off. 

The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the derivati-

ve action time dt and the integral action time rt. 

To change parameters Pb1, dt and rt, proceeds as follows: 

--

--

  

  

Press the 

PGM

PGM

button to access the parameters level. 

--

--

  

  

To move from

one parameter to the next, press 

PGM

PGM

--

--

  

  

When 

Pb1

is displayed, the value can be increased or decreased using the s and t keys.  

--

--

Confirm the changed parameters by pressing 

PGM

PGM

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored auto-

matically. 

--

--

  

  

Press 

PGM

PGM

to access the next parameter. 

--

--

  

  

When dt is displayed, repeat the procedure described above. 

--

--

  

  

Press PGM

to access the next parameter. 

--

--

  

  

When rt is displayed, repeat the procedure above. 

--

--

  

  

To return to normal display press  

EXIT

EXIT

DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFF

The regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.

HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power.  HYS3 indicates

the upper shutoff limit, above which the regulator switches the burner off.  To set HYS1 and HYS3 proceed as follows: --

--

  

  

Press

the 

PGM

PGM

key to access the parameters level. 

--

--

  

  

To move from one parameter to the next, press 

PGM

PGM

--

--

  

  

When 

HYS1

is displayed

(burner ignition differential-stage II), increase or decrease the value using the 

and 

keys. 

--

--

  

  

Confirm the changed parameters by

pressing 

PGM

PGM

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored automatically. 

--

--

  

  

Press 

PGM

PGM

to access the

next parameter. 

--

--

  

  

When 

HYS2

is displayed (burner shutoff differential-stage II), repeat the procedure described above. 

--

--

  

  

Press

PGM

PGM

to access the next parameter. 

--

--

  

  

When 

HYS3

is displayed (upper shutoff differential) repeat the procedure described above. 

--

--

  

  

To return to normal display press 

EXIT

EXIT

MANUAL/AUTOMATIC MODE

To access “MANUAL” mode, press and hold 

EXIT

EXIT

for at least 5 seconds.  Manual mode can only be selected when the burner is

in operation.  It is deactivated automatically when the burner shuts off.  When the LED above the hand symbol is alight, the regu-

lator is in manual mode and the position of the servocontrol can be changed using the 

and 

keys. The LEDS on the front of

the regulator indicate whether the servocontrol OPEN or CLOSE command is currently active.  Pressing the 

key the servocon-

trol OPENS. Pressing the 

key the servocontrol CLOSES.  To select automatic mode press and hold 

EXIT

EXIT

for at least 5 seconds.

The LED above the hand symbol goes out and the regulator reverts to automatic. 

CLIMATIC COMPENSATION

The RWF 40 regulator can be set with the set point interlocked to the external probe.  To select this operating mode, proceed as

follows:  

--

--

  

  

Connect the required probe as in the wiring diagram.  

--

--

  

  

Change the regulator settings.  When using an external probe

the regulator must be set as follows:  

--

--

  

  

Press the 

PGM

PGM

key to access the configuration level.  When the caption 

C111

(XXXX) is

displayed, use the 

key to access the second figure (XXXX).  Use the 

key to select the type of probe (XX3X).  

--

--

  

  

Confirm the

change of  parameters by pressing 

PGM

PGM

.  If this is not done within 2 seconds, the value is stored automatically  

--

--

  

  

Press 

PGM

PGM

to

access the configuration level.  When the display reads 

C112

(XXXX), use the 

key to access the second figure (XXXX).  Press the

key to set the type of probe (XX3X).  

--

--

  

  

Confirm the changed parameters by pressing 

PGM

PGM

.  

--

--

  

  

If confirmation is not given

within 2 seconds the value will be stored automatically.  

--

--

  

  

To return to normal display press 

EXIT

EXIT

. To establish the heating curve, proceed as follows: 

--

--

  

  

Press 

PGM

PGM

to access the parameters level.  

--

--

  

  

Press 

PGM

PGM

to move from one parameter to the next.  

--

--

  

  

When the letter H is

displayed (heating curve gradient), increase or decrease the value using the 

and 

keys.  

--

--

  

  

Confirm the changed parameters by

pressing 

PGM

PGM

.  

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored automatically.  

--

--

  

  

To return to normal display press 

EXIT

EXIT

.

Содержание Blu 5000.1 MD

Страница 1: ...0 1 PR MD G20 70 300 mbar LB 832 28 04 2004 G A S T E C A BRUCIATORI A GAS PROGRESSIVI E MODULANTI B MODULATING AND PROGRESSIVE GAS BURNERS C BRULEURS GAZ PROGRESSIVES ET MODULANTS D QUEMADOR DE GAS P...

Страница 2: ...300 70 300 70 300 70 300 Voltage 50 Hz V 230 400 230 400 230 400 230 400 Motor power kW 11 15 11 15 Rpm N 2800 2800 2800 2800 Fuel P c i Natural gas 35 9 Mj Nm3 8 570 kcal Nm3 WORKING FIELDS Output Ba...

Страница 3: ...al wires correspond that the burner shuts down when the boiler thermostat opens the seal of the boiler furnace which pre vents air from entering the seal on the flue boiler pipe fitting the condition...

Страница 4: ...m capacity t6 Time for enabling operation of the main gas valve on maximum capacity Duration 8 66 2 4 10 10 Rivelazione di fiamma Spia di blocco Valvola gas Serranda aria Serranda gas Trasformatore di...

Страница 5: ...ximum gas flow rate see figure on solenoid valve adjustments or adjust the gas pressure in the gover nor ADJUSTING THE MAXIMUM AIR FLOW RATE Adjusting the maximum air flow rate see figure detail 2 Loo...

Страница 6: ...Screw up cover M ADJUSTMENT OF THE AIR PRESSURE SWITCH Unscrew screws A and B and remove cover C Set the pressure switch to the minimum by turning regulator D to position 1 Start the burner and keep i...

Страница 7: ...detection failure In this case check the position of the electrode its electric connec tion and the earthing of the burner 24 min 6 A LANDIS LFL1 622 Microamperometro fondo scala 50 A IONIZATION CURRE...

Страница 8: ...SE 1st Stage Increase power OPEN 2nd Stage Two stage operation Description of display and keys on the RWF 40 microprocessor regulator The figure shows the normal display indicating the actual value an...

Страница 9: ...o access the parameters level To move from one parameter to the next press PGM PGM When HYS1 is displayed burner ignition differential stage II increase or decrease the value using the and keys Confir...

Страница 10: ...Connection for probe QAE2 passive probe Water probe Configuration code C111 9XXX Connection for probe FT TP passive probe Degusa probe Configuration code C111 5XXX Connection for probe QBE620 P activ...

Страница 11: ...aulty the regulator will not indicate the real value Situation The number 1999 blinks in the display as the actual value with SP E showing in the set point field Cause The external set point value is...

Страница 12: ...ers BEFORE TAKING ANY ACTION CHECK that there is power in the circit and the burner is connected that the gas pressure is right and the gas shut off cock is open that the control systems are properly...

Страница 13: ...e probe QBE620 P QAE22 FT TP 1000 P4 P10 P16 P25 P40 Analog input 1 2 and 3 setpoint changeover shift C111 9030 5030 G000 G000 G000 G000 G000 Limit comparator controller type setpoint 1 locking C112 0...

Страница 14: ...50 ABCD LB 832 BLU 5000 1 6000 1 PR MD 1 8 9 10 3 7 14 BLU 5000 1 6000 1 PR MD 6 5 4 35 37 11 2 36 18 16 15 13 12 38 22 21 29 28 27 24 26 32 23 25 30 31 34 39 BLU 5000 1 6000 1 MD LANDIS RWF 40 19 20...

Страница 15: ...R1020 18 MANUAL AUTOMATIC SELECTOR R1020 5 R1020 5 19 LAMP Elettrospring EL N SC4 E1510 E1510 20 FUSE SUPPORT FUSIT FH B528 E802 2 E802 2 21 RELAY BASE Finder 5532 R905 R905 22 RELAY Finder 5532 R711...

Страница 16: ...CHANGE THE CONNECTIONS OF THE MOTOR AND MOVE THE WIRE OF TERMINAL N CAMBIARE I COLLEGAMENTI DEL MOTORE E SPOSTARE IL FILO DAL MORSETTO N AL MORSETTO R DELLA MORSETTIERA 00 01 02 03 04 05 06 07 08 09 A...

Страница 17: ...TEUR VENTILATEUR RELE TERMICO MOTOR VENTILADOR LOCK OUT LAMP LAMPE DE SECURITE ESPIA DE BLOQUEO IGNITION TRANSFORMER TRANSFORMATEUR D ALLUMAGE TRANSFORMADOR MOTOR FAN MUTEUR VENTILATEUR MOTOR VENTILAD...

Страница 18: ...BEM08081 10 11 2003 400V 230V 9 HLB Q N R S T 7 6 5 8 SA P T STS S N T R PE 50 Hz 400V P T STC 14 13 12 11 10 FMV MV U V W KMV R S T NO Z FU SAL FMV 97 98 HLBT 1 2 4 3 5 SPA FMV 95 96 TV 12 LANDIS LF...

Страница 19: ...E ELECTROVALVULA GAS DE SEGURIDAD PRESSOSTATO GAS DI MINIMA CONMUTADOR MANUAL AUTOMATICO GAS PRESSURE SWITCH MIN PRESSOSTAT GAZ PRESSION MIN PRESOSTATO GAS DE MINIMA POT SPGmin HLBT YVGS ELECTROVALVUL...

Страница 20: ...right to make without any prior notice all those modifications which it deems usefull and or necessary in order to improve the quality of its products without affecting their main features CEcoflam S...

Отзывы: