pag.7
EN
420010749000
Azur 30/40/60/80 Blu 120 P
Message
Flash-Code
waiting for air proving
❘ ❘
.
switch
pre-purge (tv1)
❘ ❘ ❘
.
pre-ignition (tvz)
❘ ❘ ❘ ❘
.
safety time (ts)
❙ ❘
.
delay 2nd stage (tv2)
❙ ❘ ❘
.
running
❘
_
low mains voltage
❘ ❙ ❙
_
Error diagnosis
Error message
Flash-Code
Possible fault
lockout
❘ ❙ ❙ ❙ ❙
within lock out safety time
safety time
no flame establishment
stray light
❘ ❘ ❙ ❙ ❙
stray light
during monitored phase,
detector may be faulty
air proving switch
❙ ❙ ❘ ❘ ❘
air proving switch
in closed position
contact welded
air proving switch
❘ ❘ ❘ ❙ ❙
air proving switch does not
time-out
close within specified time
air proving switch
❘ ❘ ❘ ❘ ❙
air proving switch opens
opened
during start or operation
loss of flame
❙ ❙ ❙ ❙ ❘
loss of flame during operation
Flash-Code for manual lock out
manual/external
❘ ❘ ❙ ❙ ❙
_
❙ ❙ ❙ ❙ ❙
lock out
Flash-Code Key
short pulse
❘
long pulse
❙
short pause
.
long pause
_
1
min. 1,5
µ
A
Microammeter full-scale 50
µ
A
SATRONIC DLG 976
IONIZATION CURRENT
The minimum current necessary to operate the control-box is 1,5 µA (DLG 976), 3µA (LME11/21). When
the measurement of the current is required it is necessary to disconnect the lead to the probe and insert in its
place a microammeter for direct current (see fig. under).
SATRONIC DLG 976 CONTROL INFORMATION SYSTEM
The SATRONIC DLG 976 control is a micro-processor control which provides information about the cur-
rent operation of the burner and the cause of any faults. The information is available by reading the “flash
code” at the red LED within the lockout reset button as detailed below. By the use of additional monitoring
equipment a short history of recorded faults is also available. There are two types of additional monitoring
devices available from Satronic Ltd. The “satropen” is a small pocket reader designed to give a visual read out
of status, flame current and supply voltage. Computer software is available to allow access to the current
information and stored data.
FAULT DISPLAY MESSAGES
On burner failure the red LED is permanently illuminated for a period of approximately 10 seconds, fol-
lowed by a brief “dark phase”, then one of the following flash codes will indicate the cause of the fault. This
indication will repeate as long as the lockout reset button is not reset.
Siemens
LME11/LME21-22
min. 3 μA
1
Connection diagram and control sequence of LME11…
RESET
M
V1
Z
AL
T
T
R / W
GP
STB
7101a24e/0609
p
EK2
K1
K2/1
K3
K2/2
H
Si
N
SB / R
W / GP
AL
M
LP
V1
Z
FS
tw
t1
t3n
TSA
t4
7
1
0
1
4
0
d
/
9
0
4
0
t10
EK2
t3
A
B
B´
C
D
CONTROL BOXES LME11