Ecoer Smart IOT Gateway Скачать руководство пользователя страница 5

5/5 

02.2018 

IOT Gateway 

Manufacturer reserves the right to change at any time for specifications or designs without notice and incurring obligations. 

No 

1.Error definition

 

G1: The continuous offline time of gateway is more than 15 minutes. 
G2: The continuous offline time of gateway is more than 4 hours.

 

 

2.Possible causes

 

  Outdoor unit(ODU) is power off. 

  Cable between gateway and ODU main control board is loose or open. 

  Damaged gateway. 

ODU power supply is turned on? 

Turn on the power supply. 

Connection cable is loose or  
open? 

Reconnect the cable. 

Yes 

Replace a new gateway. 

Yes 

No 

G1/G2: The continuous offline time of gateway is too long. 

G3: Local link is disconnected. 

1.Error definition

 

G3: Local link is disconnected.

 

 

2.Possible causes 

 

  Damaged gateway. 

  Damaged ODU main control board. 

Normal 

No 

Replace the gateway and the problem is 
disappeared. 

Replace the ODU main control board  

Yes 

 Note: The gateway error code is displayed on the Ecoer Smart Service App. 

Error code 

Description 

G1 

The continuous offline time of gateway is more than 15 minutes.  

G2 

The continuous offline time of gateway is more than 4 hours.  

G3  

Local link is disconnected. 

 Error Code Lists for Gateway 