Ecodan PUHZ-HW140VHA-BS Скачать руководство пользователя страница 6

If these options can not rectify the problems then please contact your local installer so a qualified engineer
can fix the problem. Any work carried out by the homeowner will cause the warranty to be void. 

Troubleshooting

Fault  

Water does not heat up well  

Water or vapour is emitted from
the Ecodan unit  

Cold water at hot taps    

Hot water provided but no heating 

Heating provided but no hot water 

Heating does not work at 
specific times 

Heating and hot water are 
active at different times during 
the weekend

Room becomes too hot when
heating is operated 

Possible Cause

Ecodan may not be working 
to its highest capacity. 

Filter may be dirty and needs 
to be cleaned. 

During the heating mode, water
may form and drop from the heat
exchanger on the outdoor unit. 

During the defrosting mode, water
on the heat exchanger or the
outdoor unit evaporates and water
vapour may be emitted.

System may be switched off. 

Hot water used may have exceeded
capacity of cylinder. 

Temperatures set are too low. 

Time clock has been programmed
incorrectly.

Time clock has been programmed
incorrectly. 

Time clock has been programmed
incorrectly. 

The programmable room
thermostat has 5/2 split function 
to create different settings for 
the weekend. 

Programmable room thermostat 
set too high. 

Heating is not needed during
summer months and should be
switched off. 

Solution

Make sure that there is plenty 
of space around the outdoor unit
so air can flow in and out. 

Cleaning of this filter should be
carried out by your installer. 

No solution necessary, this will 
not effect the performance of 
the Ecodan.

No solution necessary, pay
attention in icy conditions. 

Switch on unit and continue
operation as usual.

Tank will automatically fill up as
water is used but will take time to
heat up. This is dependent upon
the size of the cylinder. 

Temperature parameters are too
low and need to be set by your
installer. 

Refer to pages 9, 10 and 11 for
time clock instructions and set
desired times for each function. 

Refer to pages 9, 10 and 11 for
time clock instructions and set
desired times for each function. 

Refer to pages 9, 10 and 11 
for time clock instructions 
and set desired times. 

Refer to pages 7 and 8 
for programmable room
thermostat settings. 

Refer to pages 7 and 8 and 
lower temperatures. 

Refer to pages 9, 10 and 11 
for time clock instructions to 
stop heating mode. 

6

Homeowner Kingspan Manual 2012 (planned)_Homeowner Standalone Manual-04-11  29/02/2012  11:49  Page 11

Содержание PUHZ-HW140VHA-BS

Страница 1: ...Ecodan Aerocyl Plus me Air Source Heat Pump and Stainless Steel Cylinder Ecodan Air Source Heat Pump Model Number PUHZ W50VHA 2 BS PUHZ W85VHA 2 BS PUHZ HW140VHA 2 BS YHA BS PUHZ HW140VHA BS 2 YHA 2 BS MARCH 2012 HOMEOWNER KINGSPAN ...

Страница 2: ...2 ...

Страница 3: ... demands thus producing cheaper energy bills Compared to regular electricity bills it will look higher than usual but the homeowner should be aware that this bill incorporates heating that is usually achieved though gas or oil Please note that heat pumps provide lower flow temperatures to radiators than a conventional gas boiler Rather than the radiators turning on off locally as with a gas boiler...

Страница 4: ...r PAR W21MAA Not necessary to adjust the installation engineer uses this to commission the system Room Controllers Located within a room placement on a wall will be dependent on installer 2 channel time clock Used to control on off periods for heating and hot water Instructions on pages 9 10 and 11 Room Thermostat Used to control the room temperature Instructions on pages 7 and 8 Aerocyl Plus me S...

Страница 5: ...or user instructions Time clock pattern setup Each channel on the time clock should be programmed to meet the demands of the home occupier in the most efficient way Hot water will take priority over heating For example If a homeowner wakes up in the morning and wants a shower at 7am and the property takes an hour to raise to the required room temperature then both channels should be set to 5am as ...

Страница 6: ...orrectly Time clock has been programmed incorrectly The programmable room thermostat has 5 2 split function to create different settings for the weekend Programmable room thermostat set too high Heating is not needed during summer months and should be switched off Solution Make sure that there is plenty of space around the outdoor unit so air can flow in and out Cleaning of this filter should be c...

Страница 7: ... thermostat can also be set up by your installer to provide one set of times and temperatures that are repeated each day of the week This is referred to as 24 hour operation The thermostat can also be set by you to provide two different programming blocks which can then be assigned to any day of the week this is referred to as A B programme operation All thermostats can be set to provide up to 2 4...

Страница 8: ...8 ...

Страница 9: ...n and off at times that suit you Your programme has had the date and time set up during manufacture and will automatically change between Greenwich Mean Time and British Summer Time You can programme up to 3 ON OFF times per day for the heating and hot water and the two systems can be operated independently 9 ...

Страница 10: ...10 ...

Страница 11: ...11 ...

Страница 12: ... trademarks of Mitsubishi Electric Europe B V The company reserves the right to make any variation in technical specification to the equipment described or to withdraw or replace products without prior notification or public announcement Mitsubishi Electric is constantly developing and improving its products All descriptions illustrations drawings and specifications in this publication present onl...

Отзывы: