Min Cycle Off Time

  

Enables you to configure the 

compressor off time between cycles. This is adjustable 
from 240 - 900 Seconds.

 

   

Min Outdoor Temp

  

Allows you to set the minimum 

outside air temperature at which the compressor will 
be disabled. This performs two functions: You can set 
it to prevent the compressor from going on when 
the outdoor temperature is too low, thus resulting in 
damage to the compressor. You can also set this value to 
determine when you want the auxiliary heat (if installed) 
to engage to help meet the set temperature. The 
temperature range is adjustable from 0°F (-17.8°C) - 65°F 
(18.3°C) or can be completely disabled. You will need an 
internet connection for this feature to operate properly.

   

Allow Heat Pump/Auxiliary Heat to Run Simultaneously 

 

If you select Yes and there is a source of auxiliary 
heat, it will turn on in addition to the heat pump. The 
heat pump will be energized for the first 30 minutes. 
If, after 30 minutes, the set point has not been met, 
the auxiliary heat will be energized to assist the heat 
pump in meeting the load.
If you select no, the heat pump will be energized for up 
to 2 hours. If after 2 hours the set point has not been 
met, the Thermostat will shutdown the heat pump and 
energize the auxiliary heat to meet the set point.  This 
option should also be used for installation where the 
heat pump evaporator coil is downstream from the 
source of auxiliary heat.

Furnace (Auxiliary Heat)

Allows you to enable and configure up to a 3-stage 
conventional heat source.  If you have selected Heat 
pump as your primary source, this feature will allow you 
to configure the auxiliary heat connected to the system. 

   

Furnace Type

  Allows you to configure the type of fur-

nace connected. This allows the Smart Thermostat to 
optimize its algorithms based on the type of fuel and 
typical characteristics of the chosen system. Choose 
the option that best represents the type of heating 
system installed.

21  Configuring The Smart Thermostat 

   

Heat Stages

  Allows you to configure up to 3 stages of 

heat. If you require a third stage, you must configure 
an accessory relay to control that stage.

   

Heat Fan Control

  This option allows you to determine 

if the system fan is controlled by the system during 
heat cycles, or if the Thermostat is required to control 
the fan. Normally the HVAC system controls the fan 
during heat cycles.

Air Conditioner

Allows you to enable and configure up to 2 stages of air 
conditioning. If you require a second stage, you must 
configure an accessory relay to control that stage.

  

Staging Method of Operation

The ecobee Smart Thermostat uses a unique method 
for staging for multi-stage heating or cooling. It uses 
a combination of intelligent algorithms and past 
performance to determine when to activate the stages.  
When there is a call for heat or cool, the system computes 
how long it would take for the system to reach the desired 
set point in stage 1, stage 2 or stage 3 accordingly. It will 
determine the highest stage at which a minimum of 10 
minutes of run time is required. It will then automatically 
start the system at that stage (ie if it calculates that it will 
take 15 minutes at stage 2 but only 7 minutes at stage 3, 
the system will immediately turn on stage 2 to meet the 
set point).  If the calculation indicates to start at stage 1, 
and it takes more than 10 minutes to reach the set point, 
it will automatically engage stage 2. If stage 2 runs for 
more than 10 minute without reaching the set point it will 
activate stage 3. A minimum run time of 10 minutes is used 
to ensure that proper circulation throughout the system 
and that minimum cycle times are maintained. For heat 
pumps with auxiliary heat, the operation of the auxiliary 
heat will depend on the configuration of the 

Allow Heat 

Pump/Auxiliary Heat to Run Simultaneously.

Accessory relays

Accessory relays are generic relays that can be configured 
to control the following;

   

Heat Stage 3

  Select this option when the Thermostat 

is required to control a 3-stage conventional heating 
system. Connect the third stage (or W3) contact to this 
accessory relay.

 

Configuring The Smart Thermostat  22

Содержание SMART

Страница 1: ... 2011 ecobee 477 Richmond Street West Suite 210 Toronto Ontario M5V 3E7 Canada toll free 1 877 932 6233 www ecobee com IM STAT 203 R1 SMART Thermostat Installation Manual ...

Страница 2: ... the Smart Thermostat to the Equipment Interface 16_ Connecting Power 17 Equipment Interface Status LED 18 CONTENTS Navigating the Smart Thermostat 19 Configuring the Installer Settings 20 Configuring the Installer Settings 20_ Installation Wizard 20_ Equipment 20 Thresholds 24 Test Equipment 27 Sensors 27 Setting up the Remote Sensor Inputs 27 View Wiring Diagram 28 Contractor Info 28 Reset Insta...

Страница 3: ...ensure the installation process is simple and efficient This step by step Installation Manual will walk you through all aspects of the installation To ensure an on going service relationship with your customers please register all of your ecobee Smart Thermostats in your Contractor Portal The ecobee Team Technical support Our technical support team is available to answer your questions at 1 877 9 ...

Страница 4: ...overy ventilators and energy recovery ventilators ecobee 1 2 3 Getting Started Equipment Description Gas Oil Electric heating up to three stages Yes Heat pump with auxiliary heat up to four stages Yes Geothermal Heat Pump Yes Duel fuel systems Yes Standard electric cooling up to two stages Yes Boilers Yes Central humidifier Yes Central dehumidifier Yes Heat Recovery Ventilator HRV Yes Energy Recov...

Страница 5: ...wer AC Transformer 24 VAC 3VA Minimum not included Battery CR2032 3V lithium coin cell included Power Adaptor EB PS 01 120V 50 60Hz to 12V DC 1A not included 5 Getting Started Wiring Specifications Refer to this table to determine maximum wire lengths allowed Smart Thermostat to Equipment Interface 18 AWG 20 AWG 22 AWG 1250ft 380m 790ft 240m 500ft 150m Equipment Interface to heating air equipment ...

Страница 6: ... and use it as a template to mark the location of the mounting holes as shown below 7 Installing The Smart Thermostat Insert a screwdriver into one of the two slots and twist gently 4 Move the back of the enclosure out of the way and make the holes where indicated in step 3 The mounting holes can accommodate a 6 pan head screw 5 Use drywall plugs or other screw anchors not included to ensure the E...

Страница 7: ...H R C ACC1 ACC1r ACC2 ACC2r ACC3 ACC3r Equipment Interface Y1 G W2 R W1 Y2 Furnace Humidifier C 24V Air Conditioner NOTE Indicates jumper Non Powered Accessories will require a jumper from RH RC to ACC1 ACC2 ACC3 for a 24V feed factory installed jumper Diagram indicates 24V humidifier terminal If your furnace control board does not have this you must use a 110V 24V step down transformer Two Stage ...

Страница 8: ...C2 ACC2r ACC3 ACC3r Equipment Interface Y1 G W2 R W1 Y2 Furnace NOTE Indicates jumper Non Powered Accessories will require a jumper from RH RC to ACC1 ACC2 ACC3 for a 24V feed factory installed jumper Diagram indicates 24V humidifier terminal If your furnace control board does not have this you must use a 110V 24V step down transformer Two Stage Heat Cool Two Stage Auxiliary Heat Duel Fuel With On...

Страница 9: ...m indicates 24V humidifier terminal If your furnace control board does not have this you must use a 110V 24V step down transformer Two Stage Furnace Carrier 58MVB With Two Stage Heat Pump Duel Fuel Aux Heat Stage 2 Dehumidifier Comp2 Humidifier C 24V Humidastat Y2 O R W2 C Heat Pump Y1 R Dhum Com Remove factory installed jumper Y W O B G W2 AUX R H R C ACC1 ACC1r ACC2 ACC2r ACC3 ACC3r Equipment In...

Страница 10: ...uipment Interface D D GND 12V Equipment Interface Thermostat D D GND 12V Installing The Smart Thermostat 16 Installing the Smart Thermostat The ideal location for the Smart Thermostat is approximately five feet 1 5m above floor level in the main living area Do not install the Smart Thermostat Close to sources of heat such as incandescent lights or heating cooling registers In direct sunlight On ex...

Страница 11: ...ectly only the Power LED should be on The LEDs operate as follows Power This LED monitors the power supply of the Equipment Interface LED ON Power is connected to the Equipment Interface and is within the appropriate voltage range LED OFF Power is disconnected or has dropped below 9V System This LED monitors the operation of the Equipment Interface LED ON There is a fault with the Equipment Interf...

Страница 12: ...Interface To prevent accidental modifications to these settings you can enable a 4 digit installer code This code is pre programmed to 3262 and can be enabled in the Thresholds option menu Installation Wizard The Installation Wizard takes you step by step through a series of choices regarding the HVAC equipment intended to be connected to the Equipment Interface Simply answer the questions accordi...

Страница 13: ...Thermostat Heat Stages Allows you to configure up to 3 stages of heat If you require a third stage you must configure an accessory relay to control that stage Heat Fan Control This option allows you to determine if the system fan is controlled by the system during heat cycles or if the Thermostat is required to control the fan Normally the HVAC system controls the fan during heat cycles Air Condit...

Страница 14: ... reduce short cycling of the equipment NEW Dehumidify in Heat Mode Allows you to control the dehumidification even when the system is in heat mode 23 Configuring The Smart Thermostat NEW Dehumidifier Active Allow you to configure if the active stat of this relay is open or closed Ventilator Activated when the user engages Ventilator Max from the Details screen The system fan will also turn on when...

Страница 15: ...on is enabled the thermostat will cycle down from the higher stages so that as it approaches set point it will only be running in stage 1 The HVAC equipment will start in stage 1 As the stage 1 temperature delta is exceeded the second stage will engage Once the equipment has brought the current temperature back to within the 25 Configuring The Smart Thermostat temperature delta stage 2 will diseng...

Страница 16: ...rmostat 28 Test Equipment This section allows you to manually turn on and off the various equipment connected to the Equipment Interface in order to test the wiring and connections If an optional Remote Sensor module is installed this section will display the actual value in ohms or volts being read by the module for each individual sensor Warning Compressor protection and minimum run time feature...

Страница 17: ...eminder on or off and to select the reminder interval in hours or calendar months This reminder also displays the date of the last filter change Humidity Filter The Humidity Filter reminder generates an alert for cleaning or changing the humidity filter Select this item to turn the reminder on or off and to select the reminder interval in hours or calendar months This reminder also displays the da...

Страница 18: ...ect No if you do not want any of the alerts to be display on the touch screen interface Alerts will continue to be displayed on the web portal and sent via email Enable Heating and Cooling Alerts Select No if you do not want the Thermostat to generate the System Failed to Heat or Cool alerts If disabled these alerts will not be shown on the Thermostat or web portal and no emails will be sent 31 Co...

Страница 19: ...arrangements Upon receipt of the defective Product ecobee will ship an equivalent replacement product to Customer provided the returned Product is found by ecobee to be defective and Customer is otherwise eligible to receive a replacement product 31 Warranty This warranty does not cover removal or reinstallation costs and shall not apply if the damages were found to be caused by something other th...

Страница 20: ...33 Notes Notes 34 ...

Отзывы: