Motion Sensor Adjustments 

 

 

NOTE: The three adjustment controls are connected to the components directly 

using a small stopper. Please exercise caution when adjusting, and never attempt 

to turn beyond the 270° adjustment range.  

 
The motion sensor’s settings can be adjusted as follows: 

 

Step 1 – Adjust the TIME setting to minimum 

Turn the TIME control fully anti-clockwise to set to the 10 second testing setting.   

 
Step 2 – Adjust the LUX/LIGHT setting to maximum 

Turn the LUX/LIGHT fully clockwise to set to maximum (sensor functioning in all 

lighting conditions).  

 

Step 3 – Adjust the RANGE setting 
Turn the RANGE control fully anti-clockwise. Move away from the sensor until the 

LED stops blinking. This will be the minimum detection range for the setting. To 

increase the range, turn the control clockwise until the desired distance is reached 

(2m – 10m maximum). 

 
Step 4 – Adjust the LUX/LIGHT setting 

If the LUX/LIGHT control is set to maximum (fully clockwise), the lights will turn ON 

whenever the room is occupied, even in full daylight.  

 

Alternatively, turn the LUX/LIGHT anti-clockwise until the desired LUX setting is 
achieved. 

 

Step 5 – Adjust the TIME setting  

Turn the TIME control clockwise until the desired delay is reached (10 seconds to 30 
minutes).  

 

 

Factory time out is pre set to 10 seconds. 

 

NOTE: All the time intervals are within approximately 10 seconds of the stated time 
out interval.  

 

Step 6 – Microphone (audio sensor)  

To disconnect the microphone, press the Push button once to activate the manual 

override (sensor will turn OFF). Then hold down the Push button until the LED starts 
to blink (approximately 5sec). Press the Push button once more to deactivate the 

manual override (sensor will turn back ON). The HF sensing will continue to operate 

when the microphone is disconnected.  

 

To reconnect the microphone, repeat steps above.  
 

Disabling  the  microphone  is  ideal  for  areas  where  there  are  high  ambient  sound 

levels, such as near a busy road or in a shopping center.  

  

NOTE: HF Sensor must first detect motion to switch the device on. Sensor will NOT 
switch the device on if no motion is detected.  

 

OTHER CAUTIONS: 

Disconnect power when working on electrical outlets or components. 

Do not push on the surface of the lens. 
 

Cleaning 

Carefully wipe sensor with a soft damp cloth.  

 

Recycling  

Please recycle all packaging material that came with the motion sensor.   
 

Warranty 

The  sensor  has  a  three  (3)  year  warranty  after  the  date  of  the  original  purchase. 

Please keep your original receipt, as this will be required for any claims under this 

warranty.  The warranty is a strictly carry in policy. (The sensor/s must be returned to 

Eco Heat offices for a claim to be processed). 
The warranty does not cover:  

§

 

damage from misuse,  

§

 

neglect or abuse,  

§

 

products that have been modified in any way,  

§

 

shipping and handling cost associated with the product, 

§

 

damage resulting from accidents, lightning, fire, water, power surges,  

natural disasters and/or incorrect installation 

For more information, view the Return/Refund Policy at www.ecosensor.co.za. 

Optional Remote Control 

 

 

The sensor LED will flash 3 times to 

confirm each setting applied 

 

ON=Always on. After about 

six hours turns to “AUTO” 

mode. 
OFF=Always off. After about 

six hours turns to “AUTO” 

mode. 

 

Automatic ON/OFF 

 

Test mode: Light level will not 

influence the operation in this 

mode. Use to test and setup 

detection range. 

 

Reset: Resetting of all 
functions to:  

   Time: 10sec 

   Range: Max 

   Lux: Max 

 

Microphone ON/OFF (if 

applicable) 

 

Automatic reading and 

saving of the actual light 

level 

 

Permanent tamper 

protection: Lock all settings 

to avoid tampering. Only 

On and Off buttons will be 

functional.  

 

Lux/Light settings (10 to 2000 

Lux). 
Recommendation: rooms 

with daylight 500 Lux, without 

daylight 2000 Lux. 

 

Time settings (10 secs to 30 

mins) 

 

Range settings (2m to Max) 

 

Trouble Shooting 
Malfunction 

 Possible Cause 

Remedy 

The unit will 

not switch 
“on” 

a.

 

No mains power  

b.

 

No movement is   
detected (in detection 

zone) 

c.

 

Wrong LUX/LIGHT level 

setting 

d.

 

Electrical circuitry faulty 

e.

 

Electrical Installation not 

done correctly 

f.

 

Unit may be faulty 

 

a.

 

Check mains power is on 

b.

 

Move towards the unit (in 
detection zone) or increase the 

detection range settings  

c.

 

Adjust setting on the LUX/LIGHT 

settings 

d.

 

Refer to the ‘Electrical 

Installation’ section to ensure 

correct installation 

e.

 

Have a certified electrician 

disconnect and test the unit 

f.

 

Contact Eco Heat Equipment 

Unit stays 

“on” 

permanently  

g.

 

Continuous movement in 

detection zone 

h.

 

The sensor is not 

mounted correctly for 

reliable operation 

i.

 

Wrong LUX/LIGHT level 

setting 

j.

 

Time setting control is set 

too far 

k.

 

Unit may be faulty 

g. Check detection range setting 

and reduce detection range 

sensitivity 

h. Check detection range setting 

and mounting procedure 
i. Adjust setting on the LUX/LIGHT 

settings 

j. Adjust the time setting control 

k. Contact Eco Heat Equipment 

 

Due  to  minor  improvements  in  design  or  otherwise,  the  product  you  purchase 

may  differ  from  the  one  shown  in  this  leaflet.  For  more  information  or  advice  on 

this  or  any  other  Eco  Heat  Equipment  products,  visit  www.ecosensor.co.za  or 

phone +27 (0)861 999 887. 
 
Indemnity: The Author, and supplier, shall not be held liable for any loss, injury or 

damage, of whatsoever nature, whether consequential or not, either contractual 
sustained to, or caused by, or which may arise through the use of any comments, 

suggestions,  circuitry,  services  or  equipment  offered  for  purchase.   The  User, 

indemnifies  the  author  and  supplier,  and  agrees  not  to  hold  him/her  responsible 

for  any  damages,  losses  and/or  liabilities  (including  legal  costs  on  a  scale  as 

between attorney and user) arising from, or through the use of circuit diagrams, 
equipment and services, whether such circuit diagrams, equipment and services 

were  used  with  the  consent  of  the  User  or  not.   All  risks  attached  to  the  use  of 

circuit diagrams, equipment and the connection thereof to the User’s equipment 

shall  be  deemed  to  have  passed  onto  the  User,  once  having  purchased  such 

equipment from the author or supplier.   

 

 
 