E93.1001EN.C Manual CD
+
74
10.17 Setting the parameters at the control panel
The functions of the controller are embedded in de electronics by means of parameters. The values and settings
hereof can be programmed by a skilled and trained service engineer with the help of a computer (laptop), the
correct software and an interface cable. A selection of these parameters can be programmed at the control panel
of the unit itself, without the use of a computer.
The following table gives a list of these last mentioned parameters. NOTICE: Only the password for level 1 is
issued in this manual. “More advanced” parameters need to be programmed by a skilled and trained service en-
gineer with access to level 2.
When ‘Modify = no’, the parameter can only be programmed at level 2
PASSWORD:
1342
MENU
PARA-
METER
DESCRIPTION
UNITS
TEXT DISPLAY
LEVEL 1
Modify
HE
AT
ING
A
1
P5BE Step modulation (1=on 0=off)
-
S t e p m o d u l
no
2
P5AO Blocking offset flow temperature control
°C
H E s O f f 1 3
yes
3
P5AP Proportional range temperature control
°C
H E s P r b 1 3
no
4
P5AL Hysteresis CH Flow temperature control
°C
H E s c D i f 1 3
yes
5
P2IC
Integration time temperature control
s
H E s
I n t 1 3
no
6
P2MI Blocking offset System CH temperature control
°C
H E
c O f f
3
yes
7
P2MJ Proportional range System CH temperature control
°C
H E
c P r b 3
no
8
P2MK Integration time CH temperature control
s
H E
c I n t
3
no
9
P5AB Timer Contact (1=on)
-
T i m e r C o n t
yes
DHW
B
1
P4AB DHW Pump Config 0=Pump 1=TWV
-
D H i p m p / t w v
yes
2
P5CB Flow temperature DHW tank low
°C
D H i f l o w L O
yes
3
P5CK Flow temperature DHW tank hi
°C
D H i f l o w H I
yes
4
P5CL Low Flow temperature time DHW
min
D H i
L O t i m e
yes
5
P5CD Legionella temperature
°C
L e g i o
t e m p
no
6
P5CI
Legionella hyst DHW tank temperature
°C
L e g i o h y s t
no
7
P5CJ Legionella hold time (0=off)
min
L e g i o h o l d
no
8
P2KI
CH interrupt by Legionella (0=yes)(1=no)
-
L e g i o
i n t r
no
9
P2LC Regulation temperature offset DHWd
°C
D H d s c O f f 2
yes
A
P2MN Proportional range DHWd modulation
°C
D H d s c P r b 2 3
no
B
P2LD Regulation temperature hysteresis DHWd
°C
D H d s c D i f 2
yes
C
P2MO integration time DHWd modulation
s
D H d s c I n t 2 3
no
D
P2ML Sys temp blocking offset DHW tank
°C
D H d s c O f f 3
yes
E
P2MM Sys temp blocking hysteresis DHW tank
°C
D H d s c D i f 3
yes
F
P5CA Hysteresis DHW tank temperature
°C
D H i s c D i f 4
yes
G
P2KH Gradient heat demand detect DHW tank temperature
°C
D H i d e t g r a d
yes
CAS
CADE
C
1
P2MA Max number extra water heaters
-
M a x C a s c U n t
no
2
P5DA Bus address water heater
-
B u s a d r e s s
no
3
P5DC Dhw on entire cascade(0) only master(1)
-
D H i c a s / m a s
no
4
P5DE Extra Water heater output enable(1)
-
E x t r a u n i t
yes
5
P5DF Cascade detection (0=standalone 1=Leader)
-
C a s S i / M a
no
6
P5BL Power off total cascade (1)
-
P w r O f f T o C a
no
7
P5DB Number of water heaters with common flue 0=None
-
C o m F l u N u m
no
G
E
NE
RAL
D
1
P5BB Analogue input Config (0=off 1=temp)
-
A n
I n p C o n
yes
2
P5AI
Minimum Temperature 0-10V input
°C
0 - 1 0 M i n T m p
yes
3
P5BI
Altitude (in amounts of 100 ft.)
ft*100
A l t
* 1 0 0 f t
yes
4
P2LK Max cooling time
min
M a x C o o l T i m
yes
5
P5BJ Temperature display 1=on
-
T e m p O n D i s p
yes
6
P4AA DHW 0=off 1=Indirect 2=Direct
-
D H W 1 = i 2 = d
no
7
P4AD pressure 0=off 1=sensor and 2=switch
-
c o n f i g
no
8
P4BD Gas type values 0-2
-
g a s t y p e
no
9
P4BE Soft start type values 0-2
-
c o n f i g
no
A
P5BN Pump modes 0-3
-
c o n f i g
no
For extensive explanation see Ch. 11: ‘Controlling options and settings’, page 84 ff.
IMPORTANT:
Do not change the parameters P2LC, P2LD, P2ML, P2MM and P5BI; they are present in the controller
for different purposes than DHW control.
Changing these parameters may affect water heater operation negatively
.
Parameter s concise explanation see next pages
→