background image

further alarms fitted on each upstairs landing. This includes basements but excludes crawl spaces and unfinished 

attics. See Figure 2 for examples. 

NOTE: For maximum protection an alarm should be fitted in every room (except kitchen, bathroom and garage).  

DO NOT FIT AN ALARM IN THE KITCHEN OR BATHROOM, as cooking fumes or steam may trigger the alarm. 

DO NOT FIT ALARM IN GARAGE, as exhaust fumes are likely to set it off. 

POSITIONING THE SMOKE ALARM 

Ceiling Mounting

 

As hot smoke rises and spreads out, it is advisable to mount 

the alarm on a ceiling in a central position. Avoid areas 

where there is no air circulation. e.g.corners of rooms and 

keep away from items which may prevent the free flow of 

air. Place the unit at least 300 mm from and light fitting or 

decorative object which might obstruct smoke entering the 

alarm. Keep at least 300 mm away from walls. See Figure 

3i. 

Wall Mounting

 

Do not mount tight into the corners. Put the top edge of your smoke alarm between 150 and 300mm below the ceiling. 

Keep at least 300mm from room corners. See Figure 3i 

On a Sloping Ceiling

 

In areas with sloping or peaked ceilings install your Smoke Alarm 900mm from the highest point measured horizontally 

because “dead air” at the apex may prevent smoke from reaching the unit. See Figure 3ii. 

Figure 3i - Positioning the smoke / heat detector Figure 3ii

Areas to be avoided include the following :-

•   

Situations where the temperature may fall below 0°or rise above 40°

•   

Humid areas such as bathrooms, kitchens, shower rooms where the relative humidity may exceed 90%

•   

Near a decorative object, door, light fitting, window molding etc., that may prevent smoke from entering the alarm.

•   

Fume filled environments such as garages. Exhaust gases may cause false alarms. 

•   

Adjacent to or directly above hot components such as radiators or wall vents that can affect the direction of air  

    currents. 

•   

In very dusty or dirty environments such as workshops. 

•   

Locate unit at least 1.5m and route wiring at least 1m away for fluorescent light fittings as electrical “noise” and/or  

    flickering may affect the unit. Do not wire into the same circuit as fluorescent lights or dimmers.

•   

Do not locate in insect infested areas. Insects and contamination on the alarm sensor can increase its response   

    time.

INSTALLING THE SMOKE ALARM

WARNING – This smoke alarm is mains powered and requires wiring by a qualified electrician in accordance 

with the current IEE Regulations for Electrical Installations (BS7671). 

The circuit used to power the smoke alarm must be a dedicated permanent supply that cannot be switched off 

accidentally by the normal user. Before installing ensure the electrical supply is isolated. 

WARNING : To prevent injury, this smoke alarm must be securely attached to the ceiling/wall in accordance 

with the installation  instructions.

IMPORTANT 

 A correct AC Quick Connector Plug should have a Brown, Blue, White wire on it as the configuration on 

Figure A above. If the AC Quick Connector Plug does not have the correct colour order, please STOP USING IT and 

contact your retailer store immediately to replace with a new AC Quick Connector.

The Smoke Alarm will function correctly either as a stand-alone alarm or inter-connected. All interconnected 

Smoke Alarms must be supplied from a single power circuit. 

A common neutral must be used for the interconnect to function. Do not connect the Inter-connect wire to Live 

or Neutral. 

•   

Disconnect the AC main power from the circuit that is

    going to be used. 

•   

Having established the mounting location install a junction

    box suitable for locating the termination point. Ensure that 

    there is no other electrical wiring or pipe work in the area

    adjacent to the mounting surface. 

•   

Unlock the detector unit from the base by push back the

    snap lock with a screw driver and turn the alarm unit anti- 

    clockwise to release it. See Figure 5 and Figure 6

•   

Fix mounting plate in position.

•   

Strip the Live / Neutral and Inter-connect (if used) wires.

•   

Connect the wires correctly. If the smoke alarms are to be  

    interconnected, connect the white wire. For Alarm that are used as single station, DO NOT CONNECT THE WHITE     

    WIRE TO ANYTHING. Ensure the screws are fully tightened. See Figure 6.

•   

The alarm must be wired in accordance with National wiring codes. 

LIVE

 - connect to house wires coloured    

    Brown, Red or marked with L. 

NEUTRAL

 - connect to house wires coloured Blue, Black or marked with N.     

    

INTERCONNECT

 - connect to the third wire. If you are not interconnecting to other units, do not connect this wire.

•   

Insert a 9V battery firmly into battery compartment on the rear of the alarm. NOTE POLARITY OF CONNECTIONS. 

•   

Ensure the metal tab is fully depressed when the battery has been fitted. NOTE – For the safety of the end user, the   

    smoke alarm cannot be fitted without its battery.

•   

Before assembly to base plate test the correct operation of the smoke alarm (operating from the battery only) by  

    depressing the test button on the front of the alarm. The unit should emit a loud pulsating alarm.

•   

Assemble alarm unit onto the mounting plate by turning the alarm unit counter-clockwise. See Figure 4

•   

Restore the AC supply by pluging the AC QUICK CONNECTOR into the back of the alarm (see Figure 4). Make sure       

    that the locks on the connector snap into place.

•   

Test the correct operation of the smoke alarm by depressing the test button on the front of the detector. The unit  

    should emit a loud pulsating alarm. 

•   

Should use 2.1mm wire for connection.

OPERATING YOUR SMOKE ALARM

Once the smoke alarm has been installed a small GREEN indicator light (LED) should be visible through the alarm 

grill indicating that AC supply is healthy. A RED indicator light (LED) should also flash approximately once a minute to 

indicate the battery is healthy and the unit is operating properly.  

If smoke is detected, the unit will emit a load pulsating alarm and a RED indicator light (LED) will be flashing quickly at 

the same time until the air is clear.

TESTING YOUR SMOKE ALARM

It is recommended that you test your smoke alarm once a week to ensure the detector is working correctly. 

Push and hold the test button for approximately 3 seconds. A loud pulsating alarm should sound and a RED indicator 

light (LED) will flash at the same time. 

NOTE – for multiple interconnected smoke alarms, only the RED indicator light (LED) of the originating unit will flash 

rapidly. All other units in the interconnect system will sound an alarm but their RED indicator light (LED) will NOT flash. 

Test each alarm checking that the alarm is triggered on all other alarms installed.

HUSH OR SILENCE FEATURE

This Smoke Alarm has a built-in Hush or Silence feature incorporated into the 

Test button.  If cooking or other non-hazardous sources cause the unwanted 

alarm, it can be temporarily silenced by depressing the test button and holding 

for approximately 3 seconds.  The alarm will enter a dormant period for 10 

minutes.  The red LED will flash every 10 seconds to indicate the sensitivity is 

reduced.  At the end of the hush period the alarm will reset to normal sensitivity. 

NOTE – If the smoke density increase during this period (i.e. from a fire) the unit 

will go into alarm mode.

LOW BATTERY WARNING

If the smoke alarm emits a short ‘beep’ once a minute the battery is at the end 

of its life and should be replaced immediately. This low voltage warning will be 

given for at least 30 days. In this case, the other interconnected units in the 

system which are not in low battery condition will chirps for a few seconds once 

an hour as long as the detector with the “dead” battery beeps. If the red indicator 

light (LED) does not flash every minute then replace the battery.

MAINTAINING YOUR SMOKE ALARM

Clean your smoke alarm at least once every six months to prevent dust build up. This can be done using a vacuum 

cleaner with the brush attachment. Clean gently around the front grilled section and sides. The apparatus shall not be 

exposed to dripping or splashing and no objects filled with liquids, such as vases, shall be placed on the apparatus.

 

220~240V   
AC OPERATED   
INTERCONNECTABLE 
PHOTOELECTRIC SMOKE 
ALARM 

 

MODEL: SGD1236
(With 9V Battery Back-up)  

Main Features :

 

 This instruction leaflet contains important information on 

the correct installation and operation of your smoke alarm. 

Read  this  leaflet  fully  before  attempting  installation  and 

retain for future reference. 

SPECIFICATION 

Power Source 

   

: 220-240Vac~ 50-60Hz with 9V 

battery back-up (battery included) 

Battery Back-up

Battery Back-up Life : In the event of a break in the mains supply   

the battery will give detector operation for 

1 month minimum

Operation Current   

: <40mA operation (In Alarm) 

Sensitivity to smoke

: 0.08-0.18db/m 

Operation Temperature  : 0

o

C - 40

o

C

Ambient Humidity 

: 10%-90% 

Alarm Sound Level 

: 85 Decibels at 3 metres   

Interconnect facility 

: 20 smoke detector over 150 

metres maximum  

Approved to 

: BS EN14604:2005

 

PRODUCT DESCRIPTION 

 

 

LOCATING THE SMOKE ALARM 

If  your  dwelling  is  multi-storey,  for  minimum  protection  one  alarm 

should be fitted at the bottom of the staircase with further alarms fitted 

on each upstairs landing. This includes basements but excludes crawl 

spaces and unfinished attics. See Figure 2 for examples. 

 

NOTE: For maximum protection an alarm should be fitted in every 

room (except kitchen, bathroom and garage).   

 

DO  NOT  FIT  AN  ALARM  IN  THE  KITCHEN  OR  BATHROOM,  as 

cooking fumes or steam may trigger the alarm. 

DO NOT FIT ALARM IN GARAGE, as exhaust fumes are likely to set 

it off. 

 

POSITIONING THE SMOKE ALARM 

Ceiling Mounting   

As hot smoke rises and spread out, it is advisable to mount on a 

ceiling  in  a  central  position.  Avoid  areas  where  there  is no air 

circulation.  E.g.  Corners  of  rooms  and  keep  away  from  items 

which may prevent the free flow of air. Place the unit at least 300 

mm from and light fitting or decorative object which might obstruct 

smoke entering the alarm. Keep at least 300 mm away from walls. 

See Figure 3i. 

 

Wall Mounting 

Do  not  mount  tight  into  the  corners.  Put  the  top  edge  of  your 

smoke alarm between 150 and 300mm below the ceiling. Keep at 

least 300mm from room corners. See Figure 3i 

 

On a Sloping Ceiling 

In areas with sloping or peaked ceilings install your Smoke Alarm 

900mm  from  the  highest  point  measured  horizontally  because 

“dead air” at the apex may prevent smoke from reaching the unit. 

See Figure 3ii. 

 

 

Areas to be avoided include the following :- 

 

Situations  where  the  temperature  may  fall  below  0

℃ 

or 

 

rise above 40

   

 

Humid areas such as bathrooms, kitchens, shower rooms 

 

where the relative humidity may exceed 90% 

 

Near a decorative object, door, light fitting, window molding 

etc., that may prevent smoke from entering the alarm. 

 

Fume filled environments such as garages. Exhaust gases 

may cause false alarms. 

 

Adjacent  to  or  directly  above  hot  components  such  as 

radiators  or  wall  vents  that  can  affect  the  direction  of  air 

currents. 

 

In very dusty or dirty environments such as workshops. 

 

Locate unit at least 1.5m and route wiring at least 1m away 

for  fluorescent  light  fittings  as  electrical  “noise”  and/or 

flickering may affect the unit. Do not wire into the same circuit 

as fluorescent lights or dimmers. 

 

Do not locate in insect infested areas. Insects and contamination on 

the alarm sensor can increase its response time. 

 

INSTALLING THE SMOKE ALARM

 

WARNING  –  This  smoke  alarm  is  mains  powered  and  requires 

wiring  by  a  qualified  electrician  in  accordance  with  the  current 

IEE Regulations for Electrical Installations (BS7671). 

 

The  circuit  used  to  power  the  smoke  alarm  must  be  a  dedicated 

permanent  supply  that  cannot  be switched  off accidentally by the 

normal user. Before installing ensure the electrical supply is isolated. 

 

WARNING :  To prevent injury,  this  smoke alarm must be securely 

attached  to  the  ceiling/wall  in  accordance  with  the  installation 

instructions. 

 

Figure A 

 

! Important ! A correct AC Quick Connector Plug should have a 

Brown, Blue, White wire on it as the configura�on on Figure A 

above. If the 

AC Quick Connector Plug does not have the correct 

color order, please STOP USING IT and contact your retailer 

store immediately to replace for a new AC Quick Connector.

 

 

The Smoke Alarm will function correctly either as a stand-alone 

alarm or inter-connected. 

All  interconnected  Smoke  Alarms  must  be  supplied  from  a 

single power circuit. 

A common neutral must be used for the interconnect to function. 

 

Do not connect the Inter-connect wire to Live or Neutral. 

 

Disconnect the  AC main  power from  the  circuit that is  going  to  be 

used. 

 

Having  established  the  mounting  location  install  a  junction box 

suitable  for locating  the  termination point. Ensure  that there is no 

other  electrical  wiring  or  pipe  work  in  the  area adjacent  to the 

mounting surface. 

 

Unlock the detector unit from the base by push back the snap lock 

with a screw driver and turn the alarm unit anti-clockwise to release 

it. See Figure 5 and Figure 6 

 

Fix mounting plate in position. 

 

Strip the Live / Neutral and Inter-connect (if used) wires. 

 

Connect  the  wires  correctly.  If  the  smoke  alarms  are  to  be 

interconnected, connect the white wire. For Alarm that are used as

single station, DO NOT CONNECT THE WHITE WIRE TO ANYTHING.

Ensure the screws are fully tightened.  See Figure 6. 

 

The alarm must be wired in accordance with National wiring codes. 

LIVE -  connect  to  house  wires  coloured  Brown,  Red  or marked 

with L. 

 

LIVING

ROOM

BATHROOM

KITCHEN

BEDROOM

BEDROOM

BEDROOM

BEDROOM

HALL

LANDING

HALL

BATHROOM

BEDROOM

LIVING

ROOM

KITCHEN

BASEMENT

MAXIMUM PROTECTION
MINIMUM PROTECTION

KEY

FIGURE 1 - SINGLE STOREY DWELLING

FIGURE 2 - 2/3  STOREY DWELLING

eclipse

2797-CPR-638573

KM 638574

BS 

EN14604:2005

NEUTRAL - 

connect to house wires coloured Blue, Black or marked with N.

Figure 3i - Positioning the smoke / heat detector Figure 3ii

CEILING

30 cm

BEST IN CENTRE OF ROOM

15 cm Min.

Do not mount lower 

than 30 cm

DEAD AIR SPACE,

Do not mount

within this area

WALL

900 mm

(3 ft)

CLASS II

APPARATUS

• Photoelectric Sensor For Slow 
    Smoldering Fires
• Power / Alarm Test Button 
• HUSH FEATURE
• Battery Back-Up  
• Low Battery Warning 
• INTERCONNECTABLE (UP TO 20 HEAT 
    AND/OR SMOKE ALARMS)
• Kitemark Approved –  BS EN14604: 
    2005
• Supplied with Fixing Kit
• Loud 85dB Alarm Signal
• Fault signal 

: 9V DC Carbon Zinc Battery (Peak 

Power 1604E Golden Power 1604D, 

Gold Peak 1604P), 

Alkaline Battery (Gold Peak 1604A, 

Energizer 522, Duracell MN1604) or 

Lithium Battery (EVE CR9V/P) 

All the Smoke Alarms should be interconnected to ensure the 

early warning will be heard, particularly by somebody sleeping. A 

properly designed early warning fire system ensures the alarm is 

given before the escape routes become blocked with smoke.   

If your dwelling is on a single storey, for minimum protection you 

should fit an alarm in a corridor or hallway between the sleeping 

and living areas (incl. Kitchens). Place it as near to the living 

areas as possible and ensure the audible alarm can be heard 

when the bedrooms are occupied. See Figure 1 for examples. 

SGD1236 is a multiple station photoelectric smoke alarm and can 

be connected to other alarms of the same make and type. This 

interconnect feature allow up to 20 units to be connected together 

over 150 metres maximum, using the single white wire, and thus 

allowing all alarms to sound when any one is activated.
Note: This smoke alarm cannot be connected to any other 

device such as a fire alarm panel. 

INTERCONNECT - connect to the third wire. If you are 

not interconnecting to other units, do not connect this wire.

 

Insert a 9V battery firmly into battery compartment on 

the  rear  of  the  alarm.  NOTE  POLARITY  OF 

CONNECTIONS.  Ensure the metal  tab is fully depressed 

when the battery has been 

fitted. 

NOTE –  For the safety of the 

end user, the smoke alarm 

cannot  be fitted without  its 

battery. 

 

Before  assembly  to  base 

plate  test  the  correct 

operation  of  the  smoke 

alarm  (operating  from  the 

battery  only)  by  depressing 

the test button on the front of 

the alarm. The unit  should emit  a loud pulsating alarm. 

 

Assemble alarm unit onto the mounting plate by turning 

the alarm unit counter-clockwise. See Figure 4 

 

Restore  the  AC supply  by  pluging  the  AC  QUICK 

CONNECTOR into the back of the alarm (see Figure 4). 

Make sure that the locks on the connector snap into place.

 

 

Test  the  correct  operation  of  the smoke  alarm  by 

depressing the test button on the front of the detector. 

The unit should emit a loud pulsating alarm. 

 

Should use 2.1mm wire for connection. 

 

OPERATING YOUR SMOKE ALARM 

Once the smoke alarm has been installed a small GREEN indicator light 

(LED) should be visible through the alarm grill indicating that AC supply 

is healthy. A RED indicator light (LED) should also flash approximately 

once a minute to indicate the battery is healthy and the unit is operating 

properly.   

If smoke is detected, the unit will emit a load pulsating alarm and a RED 

indicator light (LED) will be flashing quickly at the same time until the 

air is clear. 

 

TESTING YOUR SMOKE ALARM 

It is recommended that you test your smoke alarm once a week to 

ensure the detector is working correctly. 

Push and hold the test button for approximately 3 seconds. A loud 

pulsating alarm should sound and a RED indicator light (LED) will 

flash at the same time. 

NOTE – for multiple interconnected smoke alarms, only the RED 

indicator light (LED) of the originating unit will flash rapidly. All other 

units in the interconnect system will sound an alarm but their RED 

indicator light (LED) will NOT flash. Test each alarm checking that the 

alarm is triggered on all other alarms installed.   

HUSH OR SILENCE FEATURE 

This Smoke Alarm has a built-in Hush or Silence feature incorporated 

into  the  Test  button.    If  cooking  or  other  non-hazardous  sources 

cause the unwanted alarm, it can be temporarily silenced by depressing 

the test button and holding for approximately 3 seconds.    The alarm 

will enter a dormant period for 10 minutes.    The red LED will flash 

every 10 seconds to indicate the sensitivity is reduced.    At the end of 

the hush period the alarm will reset to normal sensitivity. 

NOTE – If the smoke density increase during this period (i.e. from a fire) 

the unit will go into alarm mode.   

 

LOW BATTERY WARNING 

If the smoke alarm emits a short ‘beep’ once a minute the battery is at 

the end of its life and should be replaced immediately. This low voltage 

warning  will  be  given  for  at  least  30  days.  In  this  case,  the  other 

interconnected units in the system which are not in low battery condition 

will chirps for a few seconds once an hour as long as the detector with 

the “dead” battery beeps. 

 

If the red indicator light (LED) does not flash every minute then replace 

the battery. 

 

 

MAINTAINING YOUR SMOKE ALARM

 

Clean your smoke alarm at least once every six months to prevent dust 

build up. This can be done using a vacuum cleaner with the brush 

attachment. Clean gently around the front grilled section and sides. 

The apparatus shall not be exposed to dripping or splashing and 

no objects filled with liquids, such as vases, shall be placed on 

the app

aratus. 

 

BATTERY REPLACEMENT 

Always TURN OFF  the  A.C. supply to  the Smoke Alarm before 

replacing the battery. Replace the battery at least once annually, or 

immediately when the low battery signal sounds once a minute, 

even though the Smoke Alarm is receiving A.C. power. 

 

Test  the  alarm  for  correct  operation  using  the  test  facility 

whenever the battery is replaced. 

 

WARNING:  DANGER  OF  EXPLOSION  IF  BATTERY 

IS INCORRECTLY REPLACED.  THE USE OF BATTERIES 

OTHER THAN THOSE RECOMMENDED ON THE BACK OF 

THE SMOKE ALARM MAY BE DETRIMENTAL TO ITS 

OPERATION 

 

The battery should only be replaced by a qualified electrician 

or similarly qualified person. 

 

Turn off the A C power supply to the Smoke Alarm. 

 

Gently unlock  the detector unit from the  base by push 

back the snap lock with a screw driver and turn the alarm 

unit clockwise to release it.   See Figure 5 and Figure 6 

 

Remove the battery from the compartment. 

 

Insert  a  new,  healthy  9V  battery.  NOTE  POLARITY  OF 

CONNECTIONS.  Ensure  the  metal  tab  is  fully 

depressed when the battery has been fitted 

 

Using the Push-to-Test button, test the smoke alarm to verify 

9V  DC  battery  back-up.  See  “TESTING  YOUR  SMOKE 

ALARM” 

 

Reattached  the  Smoke  alarm  to  the  mounting  plate  by 

rotating the alarm unit counter-clockwise until the  it  snaps 

into place. (see Figure 4) 

 

Turn on the AC power and test the Smoke Alarm using the 

Push-to-Test button. See “TESTING YOUR SMOKE ALARM” 

 

IMPORTANT SAFEGUARDS 

Installation of your smoke alarm is only one step in your safety plan. 

Other important steps should be taken to further improve your safety:- 

 

Install  the  smoke  alarm properly,  following  this  instruction 

leaflet 

 

Test your smoke alarm weekly 

 

Replace the battery immediately once depleted 

 

Do not smoke in bed 

 

Keep matches & lighters away from children 

 

Store flammable materials in a proper manner and never use 

them near naked flames or sparks 

 

Maintain emergency equipment such as Fire Extinguishers, 

escape ladders etc and ensure all occupants know how to 

use them correctly. 

 

Plan an escape route/s from your building in advance and 

ensure  all  occupants  are  aware  of  them.  Re-enforce  this 

awareness periodically through-out the year. 

 

Make sure escape routes remain free of any obstructions. 

IS  DUE  TO  AN  ACTUAL  FIRE  AND  THE  DWELLING  SHOULD  BE 

EVACUATED IMMEDIATELY. 

THIS PRODUCT IS A SEALED UNIT AND CANNOT BE REPAIRED – IF 

THE UNIT IS TAMPERED WITH IT WILL INVALIDATE THE WARRANTY. 

IF THE UNIT IS FAULTY PLEASE RETURN IT TO YOUR ORIGINAL 

SUPPLIER WITH YOUR PROOF OF PURCHASE. 

 

YOUR SMOKE ALARM WARRANTY 

These smoke alarms are warranty to be free from defects in materials and 

workmanships under normal use and service for a period of five years 

from date of purchase.    The company will not be obligated to repair or 

replace parts which are found to be in need of repair because of misuse, 

damage  or  alterations  occur  after  the  date  of  purchase.    Send  the 

Smoke Alarm with proof of purchase, postage and return postage prepaid, 

to local distributor.    The liability of the company arising from the sale of 

this smoke alarm shall not in any case exceed the cost of replacement of 

smoke alarm and in no case shall the company be liable for consequential 

loss or damages resulting from the failure of the smoke alarm. 

 

SOLAS GEAL DISTRIBUTION LTD. SHALL HAVE NO LIABILITY FOR 

ANY PERSONAL INJURY OR PROPERTY DAMAGE, OR ANY SPECIAL 

INCIDENTAL, CONTINGENT OR CONSEQUENTIAL DAMAGE OF ANY 

KIND  RESULTING  FROM  A  FIRE.  THE  EXCLUSIVE  REMEDY  FOR 

BREACH OF THE LIMITED WARRANTY CONTAINED HEREIN IS THE 

REPAIR  OR  REPLACEMENT  OF  THE  DETECTIVE  PRODUCT  AT 

SOLAS  GEAL  DISTRIBUTION  LTD.  OPTION.  IN  NO  CASE  SHALL 

SOLAS GEAL DISTRIBUTION LTD.’S LIABILITY UNDER ANY OTHER 

REMEDY PRESCRIBED BY LAW EXCEED THE PURCHASE PRICE. 

YOUR  SMOKE  ALARMS  IS  NOT  A  SUBSTITUTE  FOR  PROPERTY, 

DISABILITY,  LIFE  OR  OTHER  INSURANCE  OF  ANY  KIND. 

APPROPRIATE  COVERAGE  IS  YOUR  RESPONSIBILITY.  CONSULT 

YOUR INSURANCE AGENT. 

 

This does not affect your statutory rights. 

 

This alarm is only suitable for single occupancy private dwellings only and 

not  intended  for  multi  occupancy  private  dwellings  or  commercial  or 

industrial dwellings. 

 

Waste  electrical  products  should  not  be  disposed  of  with  normal 

household waste. Please recycle where facilities exist. Check with your 

Local  Authority  or  retailer  for  recycling  advice.  New  regulation  will 

encourage  the  recycling  of  Waste  from  Electrical  and  Electronic 

Equipment (European "WEEE Directive" effective August 2005). 

 

Importer:          Solas Geal Distribution Ltd. 

 

Unit 8 Ashbourne Business Centre, 

 

Ballybin Road, Ashbourne, Co. Meath, 

Ireland

 

 

Ver: 13-MAY-2017 

 

 

Figure 5 

Turn the alarm units clockwise until the snap lock   

engages. 

 

 

 

 

Figure 6 – Push Back the snap lock and turn the 

Alarm anti-clockwise

 

 

 

Figure 4 

Plug the AC QUICK 

CONNECTOR into the 

back of the alarm.

 

 

WARNING: IF THERE IS ANY QUESTION AS TO THE CAUSE 

OF AN ALARM IT SHOULD BE ASSUMED THAT THE ALARM 

unlock

 

220~240V   
AC OPERATED   
INTERCONNECTABLE 
PHOTOELECTRIC SMOKE 
ALARM 

 

MODEL: SGD1236
(With 9V Battery Back-up)  

Main Features :

 

 This instruction leaflet contains important information on 

the correct installation and operation of your smoke alarm. 

Read  this  leaflet  fully  before  attempting  installation  and 

retain for future reference. 

SPECIFICATION 

Power Source 

   

: 220-240Vac~ 50-60Hz with 9V 

battery back-up (battery included) 

Battery Back-up

Battery Back-up Life : In the event of a break in the mains supply   

the battery will give detector operation for 

1 month minimum

Operation Current   

: <40mA operation (In Alarm) 

Sensitivity to smoke

: 0.08-0.18db/m 

Operation Temperature  : 0

o

C - 40

o

C

Ambient Humidity 

: 10%-90% 

Alarm Sound Level 

: 85 Decibels at 3 metres   

Interconnect facility 

: 20 smoke detector over 150 

metres maximum  

Approved to 

: BS EN14604:2005

 

PRODUCT DESCRIPTION 

 

 

LOCATING THE SMOKE ALARM 

If  your  dwelling  is  multi-storey,  for  minimum  protection  one  alarm 

should be fitted at the bottom of the staircase with further alarms fitted 

on each upstairs landing. This includes basements but excludes crawl 

spaces and unfinished attics. See Figure 2 for examples. 

 

NOTE: For maximum protection an alarm should be fitted in every 

room (except kitchen, bathroom and garage).   

 

DO  NOT  FIT  AN  ALARM  IN  THE  KITCHEN  OR  BATHROOM,  as 

cooking fumes or steam may trigger the alarm. 

DO NOT FIT ALARM IN GARAGE, as exhaust fumes are likely to set 

it off. 

 

POSITIONING THE SMOKE ALARM 

Ceiling Mounting   

As hot smoke rises and spread out, it is advisable to mount on a 

ceiling  in  a  central  position.  Avoid  areas  where  there  is no air 

circulation.  E.g.  Corners  of  rooms  and  keep  away  from  items 

which may prevent the free flow of air. Place the unit at least 300 

mm from and light fitting or decorative object which might obstruct 

smoke entering the alarm. Keep at least 300 mm away from walls. 

See Figure 3i. 

 

Wall Mounting 

Do  not  mount  tight  into  the  corners.  Put  the  top  edge  of  your 

smoke alarm between 150 and 300mm below the ceiling. Keep at 

least 300mm from room corners. See Figure 3i 

 

On a Sloping Ceiling 

In areas with sloping or peaked ceilings install your Smoke Alarm 

900mm  from  the  highest  point  measured  horizontally  because 

“dead air” at the apex may prevent smoke from reaching the unit. 

See Figure 3ii. 

 

 

Areas to be avoided include the following :- 

 

Situations  where  the  temperature  may  fall  below  0

℃ 

or 

 

rise above 40

   

 

Humid areas such as bathrooms, kitchens, shower rooms 

 

where the relative humidity may exceed 90% 

 

Near a decorative object, door, light fitting, window molding 

etc., that may prevent smoke from entering the alarm. 

 

Fume filled environments such as garages. Exhaust gases 

may cause false alarms. 

 

Adjacent  to  or  directly  above  hot  components  such  as 

radiators  or  wall  vents  that  can  affect  the  direction  of  air 

currents. 

 

In very dusty or dirty environments such as workshops. 

 

Locate unit at least 1.5m and route wiring at least 1m away 

for  fluorescent  light  fittings  as  electrical  “noise”  and/or 

flickering may affect the unit. Do not wire into the same circuit 

as fluorescent lights or dimmers. 

 

Do not locate in insect infested areas. Insects and contamination on 

the alarm sensor can increase its response time. 

 

INSTALLING THE SMOKE ALARM

 

WARNING  –  This  smoke  alarm  is  mains  powered  and  requires 

wiring  by  a  qualified  electrician  in  accordance  with  the  current 

IEE Regulations for Electrical Installations (BS7671). 

 

The  circuit  used  to  power  the  smoke  alarm  must  be  a  dedicated 

permanent  supply  that  cannot  be switched  off accidentally by the 

normal user. Before installing ensure the electrical supply is isolated. 

 

WARNING :  To prevent injury,  this  smoke alarm must be securely 

attached  to  the  ceiling/wall  in  accordance  with  the  installation 

instructions. 

 

Figure A 

 

! Important ! A correct AC Quick Connector Plug should have a 

Brown, Blue, White wire on it as the configura�on on Figure A 

above. If the 

AC Quick Connector Plug does not have the correct 

color order, please STOP USING IT and contact your retailer 

store immediately to replace for a new AC Quick Connector.

 

 

The Smoke Alarm will function correctly either as a stand-alone 

alarm or inter-connected. 

All  interconnected  Smoke  Alarms  must  be  supplied  from  a 

single power circuit. 

A common neutral must be used for the interconnect to function. 

 

Do not connect the Inter-connect wire to Live or Neutral. 

 

Disconnect the  AC main  power from  the  circuit that is  going  to  be 

used. 

 

Having  established  the  mounting  location  install  a  junction box 

suitable  for locating  the  termination point. Ensure  that there is no 

other  electrical  wiring  or  pipe  work  in  the  area adjacent  to the 

mounting surface. 

 

Unlock the detector unit from the base by push back the snap lock 

with a screw driver and turn the alarm unit anti-clockwise to release 

it. See Figure 5 and Figure 6 

 

Fix mounting plate in position. 

 

Strip the Live / Neutral and Inter-connect (if used) wires. 

 

Connect  the  wires  correctly.  If  the  smoke  alarms  are  to  be 

interconnected, connect the white wire. For Alarm that are used as

single station, DO NOT CONNECT THE WHITE WIRE TO ANYTHING.

Ensure the screws are fully tightened.  See Figure 6. 

 

The alarm must be wired in accordance with National wiring codes. 

LIVE -  connect  to  house  wires  coloured  Brown,  Red  or marked 

with L. 

 

LIVING

ROOM

BATHROOM

KITCHEN

BEDROOM

BEDROOM

BEDROOM

BEDROOM

HALL

LANDING

HALL

BATHROOM

BEDROOM

LIVING

ROOM

KITCHEN

BASEMENT

MAXIMUM PROTECTION
MINIMUM PROTECTION

KEY

FIGURE 1 - SINGLE STOREY DWELLING

FIGURE 2 - 2/3  STOREY DWELLING

eclipse

2797-CPR-638573

KM 638574

BS 

EN14604:2005

NEUTRAL - 

connect to house wires coloured Blue, Black or marked with N.

Figure 3i - Positioning the smoke / heat detector Figure 3ii

CEILING

30 cm

BEST IN CENTRE OF ROOM

15 cm Min.

Do not mount lower 

than 30 cm

DEAD AIR SPACE,

Do not mount

within this area

WALL

900 mm

(3 ft)

CLASS II

APPARATUS

• Photoelectric Sensor For Slow 
    Smoldering Fires
• Power / Alarm Test Button 
• HUSH FEATURE
• Battery Back-Up  
• Low Battery Warning 
• INTERCONNECTABLE (UP TO 20 HEAT 
    AND/OR SMOKE ALARMS)
• Kitemark Approved –  BS EN14604: 
    2005
• Supplied with Fixing Kit
• Loud 85dB Alarm Signal
• Fault signal 

: 9V DC Carbon Zinc Battery (Peak 

Power 1604E Golden Power 1604D, 

Gold Peak 1604P), 

Alkaline Battery (Gold Peak 1604A, 

Energizer 522, Duracell MN1604) or 

Lithium Battery (EVE CR9V/P) 

All the Smoke Alarms should be interconnected to ensure the 

early warning will be heard, particularly by somebody sleeping. A 

properly designed early warning fire system ensures the alarm is 

given before the escape routes become blocked with smoke.   

If your dwelling is on a single storey, for minimum protection you 

should fit an alarm in a corridor or hallway between the sleeping 

and living areas (incl. Kitchens). Place it as near to the living 

areas as possible and ensure the audible alarm can be heard 

when the bedrooms are occupied. See Figure 1 for examples. 

SGD1236 is a multiple station photoelectric smoke alarm and can 

be connected to other alarms of the same make and type. This 

interconnect feature allow up to 20 units to be connected together 

over 150 metres maximum, using the single white wire, and thus 

allowing all alarms to sound when any one is activated.
Note: This smoke alarm cannot be connected to any other 

device such as a fire alarm panel. 

INTERCONNECT - connect to the third wire. If you are 

not interconnecting to other units, do not connect this wire.

 

Insert a 9V battery firmly into battery compartment on 

the  rear  of  the  alarm.  NOTE  POLARITY  OF 

CONNECTIONS.  Ensure the metal  tab is fully depressed 

when the battery has been 

fitted. 

NOTE –  For the safety of the 

end user, the smoke alarm 

cannot  be fitted without  its 

battery. 

 

Before  assembly  to  base 

plate  test  the  correct 

operation  of  the  smoke 

alarm  (operating  from  the 

battery  only)  by  depressing 

the test button on the front of 

the alarm. The unit  should emit  a loud pulsating alarm. 

 

Assemble alarm unit onto the mounting plate by turning 

the alarm unit counter-clockwise. See Figure 4 

 

Restore  the  AC supply  by  pluging  the  AC  QUICK 

CONNECTOR into the back of the alarm (see Figure 4). 

Make sure that the locks on the connector snap into place.

 

 

Test  the  correct  operation  of  the smoke  alarm  by 

depressing the test button on the front of the detector. 

The unit should emit a loud pulsating alarm. 

 

Should use 2.1mm wire for connection. 

 

OPERATING YOUR SMOKE ALARM 

Once the smoke alarm has been installed a small GREEN indicator light 

(LED) should be visible through the alarm grill indicating that AC supply 

is healthy. A RED indicator light (LED) should also flash approximately 

once a minute to indicate the battery is healthy and the unit is operating 

properly.   

If smoke is detected, the unit will emit a load pulsating alarm and a RED 

indicator light (LED) will be flashing quickly at the same time until the 

air is clear. 

 

TESTING YOUR SMOKE ALARM 

It is recommended that you test your smoke alarm once a week to 

ensure the detector is working correctly. 

Push and hold the test button for approximately 3 seconds. A loud 

pulsating alarm should sound and a RED indicator light (LED) will 

flash at the same time. 

NOTE – for multiple interconnected smoke alarms, only the RED 

indicator light (LED) of the originating unit will flash rapidly. All other 

units in the interconnect system will sound an alarm but their RED 

indicator light (LED) will NOT flash. Test each alarm checking that the 

alarm is triggered on all other alarms installed.   

HUSH OR SILENCE FEATURE 

This Smoke Alarm has a built-in Hush or Silence feature incorporated 

into  the  Test  button.    If  cooking  or  other  non-hazardous  sources 

cause the unwanted alarm, it can be temporarily silenced by depressing 

the test button and holding for approximately 3 seconds.    The alarm 

will enter a dormant period for 10 minutes.    The red LED will flash 

every 10 seconds to indicate the sensitivity is reduced.    At the end of 

the hush period the alarm will reset to normal sensitivity. 

NOTE – If the smoke density increase during this period (i.e. from a fire) 

the unit will go into alarm mode.   

 

LOW BATTERY WARNING 

If the smoke alarm emits a short ‘beep’ once a minute the battery is at 

the end of its life and should be replaced immediately. This low voltage 

warning  will  be  given  for  at  least  30  days.  In  this  case,  the  other 

interconnected units in the system which are not in low battery condition 

will chirps for a few seconds once an hour as long as the detector with 

the “dead” battery beeps. 

 

If the red indicator light (LED) does not flash every minute then replace 

the battery. 

 

 

MAINTAINING YOUR SMOKE ALARM

 

Clean your smoke alarm at least once every six months to prevent dust 

build up. This can be done using a vacuum cleaner with the brush 

attachment. Clean gently around the front grilled section and sides. 

The apparatus shall not be exposed to dripping or splashing and 

no objects filled with liquids, such as vases, shall be placed on 

the app

aratus. 

 

BATTERY REPLACEMENT 

Always TURN OFF  the  A.C. supply to  the Smoke Alarm before 

replacing the battery. Replace the battery at least once annually, or 

immediately when the low battery signal sounds once a minute, 

even though the Smoke Alarm is receiving A.C. power. 

 

Test  the  alarm  for  correct  operation  using  the  test  facility 

whenever the battery is replaced. 

 

WARNING:  DANGER  OF  EXPLOSION  IF  BATTERY 

IS INCORRECTLY REPLACED.  THE USE OF BATTERIES 

OTHER THAN THOSE RECOMMENDED ON THE BACK OF 

THE SMOKE ALARM MAY BE DETRIMENTAL TO ITS 

OPERATION 

 

The battery should only be replaced by a qualified electrician 

or similarly qualified person. 

 

Turn off the A C power supply to the Smoke Alarm. 

 

Gently unlock  the detector unit from the  base by push 

back the snap lock with a screw driver and turn the alarm 

unit clockwise to release it.   See Figure 5 and Figure 6 

 

Remove the battery from the compartment. 

 

Insert  a  new,  healthy  9V  battery.  NOTE  POLARITY  OF 

CONNECTIONS.  Ensure  the  metal  tab  is  fully 

depressed when the battery has been fitted 

 

Using the Push-to-Test button, test the smoke alarm to verify 

9V  DC  battery  back-up.  See  “TESTING  YOUR  SMOKE 

ALARM” 

 

Reattached  the  Smoke  alarm  to  the  mounting  plate  by 

rotating the alarm unit counter-clockwise until the  it  snaps 

into place. (see Figure 4) 

 

Turn on the AC power and test the Smoke Alarm using the 

Push-to-Test button. See “TESTING YOUR SMOKE ALARM” 

 

IMPORTANT SAFEGUARDS 

Installation of your smoke alarm is only one step in your safety plan. 

Other important steps should be taken to further improve your safety:- 

 

Install  the  smoke  alarm properly,  following  this  instruction 

leaflet 

 

Test your smoke alarm weekly 

 

Replace the battery immediately once depleted 

 

Do not smoke in bed 

 

Keep matches & lighters away from children 

 

Store flammable materials in a proper manner and never use 

them near naked flames or sparks 

 

Maintain emergency equipment such as Fire Extinguishers, 

escape ladders etc and ensure all occupants know how to 

use them correctly. 

 

Plan an escape route/s from your building in advance and 

ensure  all  occupants  are  aware  of  them.  Re-enforce  this 

awareness periodically through-out the year. 

 

Make sure escape routes remain free of any obstructions. 

IS  DUE  TO  AN  ACTUAL  FIRE  AND  THE  DWELLING  SHOULD  BE 

EVACUATED IMMEDIATELY. 

THIS PRODUCT IS A SEALED UNIT AND CANNOT BE REPAIRED – IF 

THE UNIT IS TAMPERED WITH IT WILL INVALIDATE THE WARRANTY. 

IF THE UNIT IS FAULTY PLEASE RETURN IT TO YOUR ORIGINAL 

SUPPLIER WITH YOUR PROOF OF PURCHASE. 

 

YOUR SMOKE ALARM WARRANTY 

These smoke alarms are warranty to be free from defects in materials and 

workmanships under normal use and service for a period of five years 

from date of purchase.    The company will not be obligated to repair or 

replace parts which are found to be in need of repair because of misuse, 

damage  or  alterations  occur  after  the  date  of  purchase.    Send  the 

Smoke Alarm with proof of purchase, postage and return postage prepaid, 

to local distributor.    The liability of the company arising from the sale of 

this smoke alarm shall not in any case exceed the cost of replacement of 

smoke alarm and in no case shall the company be liable for consequential 

loss or damages resulting from the failure of the smoke alarm. 

 

SOLAS GEAL DISTRIBUTION LTD. SHALL HAVE NO LIABILITY FOR 

ANY PERSONAL INJURY OR PROPERTY DAMAGE, OR ANY SPECIAL 

INCIDENTAL, CONTINGENT OR CONSEQUENTIAL DAMAGE OF ANY 

KIND  RESULTING  FROM  A  FIRE.  THE  EXCLUSIVE  REMEDY  FOR 

BREACH OF THE LIMITED WARRANTY CONTAINED HEREIN IS THE 

REPAIR  OR  REPLACEMENT  OF  THE  DETECTIVE  PRODUCT  AT 

SOLAS  GEAL  DISTRIBUTION  LTD.  OPTION.  IN  NO  CASE  SHALL 

SOLAS GEAL DISTRIBUTION LTD.’S LIABILITY UNDER ANY OTHER 

REMEDY PRESCRIBED BY LAW EXCEED THE PURCHASE PRICE. 

YOUR  SMOKE  ALARMS  IS  NOT  A  SUBSTITUTE  FOR  PROPERTY, 

DISABILITY,  LIFE  OR  OTHER  INSURANCE  OF  ANY  KIND. 

APPROPRIATE  COVERAGE  IS  YOUR  RESPONSIBILITY.  CONSULT 

YOUR INSURANCE AGENT. 

 

This does not affect your statutory rights. 

 

This alarm is only suitable for single occupancy private dwellings only and 

not  intended  for  multi  occupancy  private  dwellings  or  commercial  or 

industrial dwellings. 

 

Waste  electrical  products  should  not  be  disposed  of  with  normal 

household waste. Please recycle where facilities exist. Check with your 

Local  Authority  or  retailer  for  recycling  advice.  New  regulation  will 

encourage  the  recycling  of  Waste  from  Electrical  and  Electronic 

Equipment (European "WEEE Directive" effective August 2005). 

 

Importer:          Solas Geal Distribution Ltd. 

 

Unit 8 Ashbourne Business Centre, 

 

Ballybin Road, Ashbourne, Co. Meath, 

Ireland

 

 

Ver: 13-MAY-2017 

 

 

Figure 5 

Turn the alarm units clockwise until the snap lock   

engages. 

 

 

 

 

Figure 6 – Push Back the snap lock and turn the 

Alarm anti-clockwise

 

 

 

Figure 4 

Plug the AC QUICK 

CONNECTOR into the 

back of the alarm.

 

 

WARNING: IF THERE IS ANY QUESTION AS TO THE CAUSE 

OF AN ALARM IT SHOULD BE ASSUMED THAT THE ALARM 

unlock

 

Insert a 9V battery firmly into battery compartment on 

the  rear  of  the  alarm.  NOTE  POLARITY  OF 

CONNECTIONS.  Ensure the metal  tab is fully depressed 

when the battery has been 

fitted. 

NOTE –  For the safety of the 

end user, the smoke alarm 

cannot  be fitted without  its 

battery. 

 

Before  assembly  to  base 

plate  test  the  correct 

operation  of  the  smoke 

alarm  (operating  from  the 

battery  only)  by  depressing 

the test button on the front of 

the alarm. The unit  should emit  a loud pulsating alarm. 

 

Assemble alarm unit onto the mounting plate by turning 

the alarm unit counter-clockwise. See Figure 4 

 

Restore  the  AC supply  by  pluging  the  AC  QUICK 

CONNECTOR into the back of the alarm (see Figure 4). 

Make sure that the locks on the connector snap into place.

 

 

Test  the  correct  operation  of  the smoke  alarm  by 

depressing the test button on the front of the detector. 

The unit should emit a loud pulsating alarm. 

 

Should use 2.1mm wire for connection. 

 

OPERATING YOUR SMOKE ALARM 

Once the smoke alarm has been installed a small GREEN indicator light 

(LED) should be visible through the alarm grill indicating that AC supply 

is healthy. A RED indicator light (LED) should also flash approximately 

once a minute to indicate the battery is healthy and the unit is operating 

properly.   

If smoke is detected, the unit will emit a load pulsating alarm and a RED 

indicator light (LED) will be flashing quickly at the same time until the 

air is clear. 

 

TESTING YOUR SMOKE ALARM 

It is recommended that you test your smoke alarm once a week to 

ensure the detector is working correctly. 

Push and hold the test button for approximately 3 seconds. A loud 

pulsating alarm should sound and a RED indicator light (LED) will 

flash at the same time. 

NOTE – for multiple interconnected smoke alarms, only the RED 

indicator light (LED) of the originating unit will flash rapidly. All other 

units in the interconnect system will sound an alarm but their RED 

indicator light (LED) will NOT flash. Test each alarm checking that the 

alarm is triggered on all other alarms installed.   

HUSH OR SILENCE FEATURE 

This Smoke Alarm has a built-in Hush or Silence feature incorporated 

into  the  Test  button.    If  cooking  or  other  non-hazardous  sources 

cause the unwanted alarm, it can be temporarily silenced by depressing 

the test button and holding for approximately 3 seconds.    The alarm 

will enter a dormant period for 10 minutes.    The red LED will flash 

every 10 seconds to indicate the sensitivity is reduced.    At the end of 

the hush period the alarm will reset to normal sensitivity. 

NOTE – If the smoke density increase during this period (i.e. from a fire) 

the unit will go into alarm mode.   

 

LOW BATTERY WARNING 

If the smoke alarm emits a short ‘beep’ once a minute the battery is at 

the end of its life and should be replaced immediately. This low voltage 

warning  will  be  given  for  at  least  30  days.  In  this  case,  the  other 

interconnected units in the system which are not in low battery condition 

will chirps for a few seconds once an hour as long as the detector with 

the “dead” battery beeps. 

 

If the red indicator light (LED) does not flash every minute then replace 

the battery. 

 

 

MAINTAINING YOUR SMOKE ALARM

 

Clean your smoke alarm at least once every six months to prevent dust 

build up. This can be done using a vacuum cleaner with the brush 

attachment. Clean gently around the front grilled section and sides. 

The apparatus shall not be exposed to dripping or splashing and 

no objects filled with liquids, such as vases, shall be placed on 

the app

aratus. 

 

BATTERY REPLACEMENT 

Always TURN OFF  the  A.C. supply to  the Smoke Alarm before 

replacing the battery. Replace the battery at least once annually, or 

immediately when the low battery signal sounds once a minute, 

even though the Smoke Alarm is receiving A.C. power. 

 

Test  the  alarm  for  correct  operation  using  the  test  facility 

whenever the battery is replaced. 

 

WARNING:  DANGER  OF  EXPLOSION  IF  BATTERY 

IS INCORRECTLY REPLACED.  THE USE OF BATTERIES 

OTHER THAN THOSE RECOMMENDED ON THE BACK OF 

THE SMOKE ALARM MAY BE DETRIMENTAL TO ITS 

OPERATION 

 

The battery should only be replaced by a qualified electrician 

or similarly qualified person. 

 

Turn off the A C power supply to the Smoke Alarm. 

 

Gently unlock  the detector unit from the  base by push 

back the snap lock with a screw driver and turn the alarm 

unit clockwise to release it.   See Figure 5 and Figure 6 

 

Remove the battery from the compartment. 

 

Insert  a  new,  healthy  9V  battery.  NOTE  POLARITY  OF 

CONNECTIONS.  Ensure  the  metal  tab  is  fully 

depressed when the battery has been fitted 

 

Using the Push-to-Test button, test the smoke alarm to verify 

9V  DC  battery  back-up.  See  “TESTING  YOUR  SMOKE 

ALARM” 

 

Reattached  the  Smoke  alarm  to  the  mounting  plate  by 

rotating the alarm unit counter-clockwise until the  it  snaps 

into place. (see Figure 4) 

 

Turn on the AC power and test the Smoke Alarm using the 

Push-to-Test button. See “TESTING YOUR SMOKE ALARM” 

 

IMPORTANT SAFEGUARDS 

Installation of your smoke alarm is only one step in your safety plan. 

Other important steps should be taken to further improve your safety:- 

 

Install  the  smoke  alarm properly,  following  this  instruction 

leaflet 

 

Test your smoke alarm weekly 

 

Replace the battery immediately once depleted 

 

Do not smoke in bed 

 

Keep matches & lighters away from children 

 

Store flammable materials in a proper manner and never use 

them near naked flames or sparks 

 

Maintain emergency equipment such as Fire Extinguishers, 

escape ladders etc and ensure all occupants know how to 

use them correctly. 

 

Plan an escape route/s from your building in advance and 

ensure  all  occupants  are  aware  of  them.  Re-enforce  this 

awareness periodically through-out the year. 

 

Make sure escape routes remain free of any obstructions. 

IS  DUE  TO  AN  ACTUAL  FIRE  AND  THE  DWELLING  SHOULD  BE 

EVACUATED IMMEDIATELY. 

THIS PRODUCT IS A SEALED UNIT AND CANNOT BE REPAIRED – IF 

THE UNIT IS TAMPERED WITH IT WILL INVALIDATE THE WARRANTY. 

IF THE UNIT IS FAULTY PLEASE RETURN IT TO YOUR ORIGINAL 

SUPPLIER WITH YOUR PROOF OF PURCHASE. 

 

YOUR SMOKE ALARM WARRANTY 

These smoke alarms are warranty to be free from defects in materials and 

workmanships under normal use and service for a period of five years 

from date of purchase.    The company will not be obligated to repair or 

replace parts which are found to be in need of repair because of misuse, 

damage  or  alterations  occur  after  the  date  of  purchase.    Send  the 

Smoke Alarm with proof of purchase, postage and return postage prepaid, 

to local distributor.    The liability of the company arising from the sale of 

this smoke alarm shall not in any case exceed the cost of replacement of 

smoke alarm and in no case shall the company be liable for consequential 

loss or damages resulting from the failure of the smoke alarm. 

 

SOLAS GEAL DISTRIBUTION LTD. SHALL HAVE NO LIABILITY FOR 

ANY PERSONAL INJURY OR PROPERTY DAMAGE, OR ANY SPECIAL 

INCIDENTAL, CONTINGENT OR CONSEQUENTIAL DAMAGE OF ANY 

KIND  RESULTING  FROM  A  FIRE.  THE  EXCLUSIVE  REMEDY  FOR 

BREACH OF THE LIMITED WARRANTY CONTAINED HEREIN IS THE 

REPAIR  OR  REPLACEMENT  OF  THE  DETECTIVE  PRODUCT  AT 

SOLAS  GEAL  DISTRIBUTION  LTD.  OPTION.  IN  NO  CASE  SHALL 

SOLAS GEAL DISTRIBUTION LTD.’S LIABILITY UNDER ANY OTHER 

REMEDY PRESCRIBED BY LAW EXCEED THE PURCHASE PRICE. 

YOUR  SMOKE  ALARMS  IS  NOT  A  SUBSTITUTE  FOR  PROPERTY, 

DISABILITY,  LIFE  OR  OTHER  INSURANCE  OF  ANY  KIND. 

APPROPRIATE  COVERAGE  IS  YOUR  RESPONSIBILITY.  CONSULT 

YOUR INSURANCE AGENT. 

 

This does not affect your statutory rights. 

 

This alarm is only suitable for single occupancy private dwellings only and 

not  intended  for  multi  occupancy  private  dwellings  or  commercial  or 

industrial dwellings. 

 

Waste  electrical  products  should  not  be  disposed  of  with  normal 

household waste. Please recycle where facilities exist. Check with your 

Local  Authority  or  retailer  for  recycling  advice.  New  regulation  will 

encourage  the  recycling  of  Waste  from  Electrical  and  Electronic 

Equipment (European "WEEE Directive" effective August 2005). 

 

Importer:          Solas Geal Distribution Ltd. 

 

Unit 8 Ashbourne Business Centre, 

 

Ballybin Road, Ashbourne, Co. Meath, 

Ireland

 

 

Ver: 13-MAY-2017 

 

 

Figure 5 

Turn the alarm units clockwise until the snap lock   

engages. 

 

 

 

 

Figure 6 – Push Back the snap lock and turn the 

Alarm anti-clockwise

 

 

 

Figure 4 

Plug the AC QUICK 

CONNECTOR into the 

back of the alarm.

 

 

WARNING: IF THERE IS ANY QUESTION AS TO THE CAUSE 

OF AN ALARM IT SHOULD BE ASSUMED THAT THE ALARM 

unlock

 

Insert a 9V battery firmly into battery compartment on 

the  rear  of  the  alarm.  NOTE  POLARITY  OF 

CONNECTIONS.  Ensure the metal  tab is fully depressed 

when the battery has been 

fitted. 

NOTE –  For the safety of the 

end user, the smoke alarm 

cannot  be fitted without  its 

battery. 

 

Before  assembly  to  base 

plate  test  the  correct 

operation  of  the  smoke 

alarm  (operating  from  the 

battery  only)  by  depressing 

the test button on the front of 

the alarm. The unit  should emit  a loud pulsating alarm. 

 

Assemble alarm unit onto the mounting plate by turning 

the alarm unit counter-clockwise. See Figure 4 

 

Restore  the  AC supply  by  pluging  the  AC  QUICK 

CONNECTOR into the back of the alarm (see Figure 4). 

Make sure that the locks on the connector snap into place.

 

 

Test  the  correct  operation  of  the smoke  alarm  by 

depressing the test button on the front of the detector. 

The unit should emit a loud pulsating alarm. 

 

Should use 2.1mm wire for connection. 

 

OPERATING YOUR SMOKE ALARM 

Once the smoke alarm has been installed a small GREEN indicator light 

(LED) should be visible through the alarm grill indicating that AC supply 

is healthy. A RED indicator light (LED) should also flash approximately 

once a minute to indicate the battery is healthy and the unit is operating 

properly.   

If smoke is detected, the unit will emit a load pulsating alarm and a RED 

indicator light (LED) will be flashing quickly at the same time until the 

air is clear. 

 

TESTING YOUR SMOKE ALARM 

It is recommended that you test your smoke alarm once a week to 

ensure the detector is working correctly. 

Push and hold the test button for approximately 3 seconds. A loud 

pulsating alarm should sound and a RED indicator light (LED) will 

flash at the same time. 

NOTE – for multiple interconnected smoke alarms, only the RED 

indicator light (LED) of the originating unit will flash rapidly. All other 

units in the interconnect system will sound an alarm but their RED 

indicator light (LED) will NOT flash. Test each alarm checking that the 

alarm is triggered on all other alarms installed.   

HUSH OR SILENCE FEATURE 

This Smoke Alarm has a built-in Hush or Silence feature incorporated 

into  the  Test  button.    If  cooking  or  other  non-hazardous  sources 

cause the unwanted alarm, it can be temporarily silenced by depressing 

the test button and holding for approximately 3 seconds.    The alarm 

will enter a dormant period for 10 minutes.    The red LED will flash 

every 10 seconds to indicate the sensitivity is reduced.    At the end of 

the hush period the alarm will reset to normal sensitivity. 

NOTE – If the smoke density increase during this period (i.e. from a fire) 

the unit will go into alarm mode.   

 

LOW BATTERY WARNING 

If the smoke alarm emits a short ‘beep’ once a minute the battery is at 

the end of its life and should be replaced immediately. This low voltage 

warning  will  be  given  for  at  least  30  days.  In  this  case,  the  other 

interconnected units in the system which are not in low battery condition 

will chirps for a few seconds once an hour as long as the detector with 

the “dead” battery beeps. 

 

If the red indicator light (LED) does not flash every minute then replace 

the battery. 

 

 

MAINTAINING YOUR SMOKE ALARM

 

Clean your smoke alarm at least once every six months to prevent dust 

build up. This can be done using a vacuum cleaner with the brush 

attachment. Clean gently around the front grilled section and sides. 

The apparatus shall not be exposed to dripping or splashing and 

no objects filled with liquids, such as vases, shall be placed on 

the app

aratus. 

 

BATTERY REPLACEMENT 

Always TURN OFF  the  A.C. supply to  the Smoke Alarm before 

replacing the battery. Replace the battery at least once annually, or 

immediately when the low battery signal sounds once a minute, 

even though the Smoke Alarm is receiving A.C. power. 

 

Test  the  alarm  for  correct  operation  using  the  test  facility 

whenever the battery is replaced. 

 

WARNING:  DANGER  OF  EXPLOSION  IF  BATTERY 

IS INCORRECTLY REPLACED.  THE USE OF BATTERIES 

OTHER THAN THOSE RECOMMENDED ON THE BACK OF 

THE SMOKE ALARM MAY BE DETRIMENTAL TO ITS 

OPERATION 

 

The battery should only be replaced by a qualified electrician 

or similarly qualified person. 

 

Turn off the A C power supply to the Smoke Alarm. 

 

Gently unlock  the detector unit from the  base by push 

back the snap lock with a screw driver and turn the alarm 

unit clockwise to release it.   See Figure 5 and Figure 6 

 

Remove the battery from the compartment. 

 

Insert  a  new,  healthy  9V  battery.  NOTE  POLARITY  OF 

CONNECTIONS.  Ensure  the  metal  tab  is  fully 

depressed when the battery has been fitted 

 

Using the Push-to-Test button, test the smoke alarm to verify 

9V  DC  battery  back-up.  See  “TESTING  YOUR  SMOKE 

ALARM” 

 

Reattached  the  Smoke  alarm  to  the  mounting  plate  by 

rotating the alarm unit counter-clockwise until the  it  snaps 

into place. (see Figure 4) 

 

Turn on the AC power and test the Smoke Alarm using the 

Push-to-Test button. See “TESTING YOUR SMOKE ALARM” 

 

IMPORTANT SAFEGUARDS 

Installation of your smoke alarm is only one step in your safety plan. 

Other important steps should be taken to further improve your safety:- 

 

Install  the  smoke  alarm properly,  following  this  instruction 

leaflet 

 

Test your smoke alarm weekly 

 

Replace the battery immediately once depleted 

 

Do not smoke in bed 

 

Keep matches & lighters away from children 

 

Store flammable materials in a proper manner and never use 

them near naked flames or sparks 

 

Maintain emergency equipment such as Fire Extinguishers, 

escape ladders etc and ensure all occupants know how to 

use them correctly. 

 

Plan an escape route/s from your building in advance and 

ensure  all  occupants  are  aware  of  them.  Re-enforce  this 

awareness periodically through-out the year. 

 

Make sure escape routes remain free of any obstructions. 

IS  DUE  TO  AN  ACTUAL  FIRE  AND  THE  DWELLING  SHOULD  BE 

EVACUATED IMMEDIATELY. 

THIS PRODUCT IS A SEALED UNIT AND CANNOT BE REPAIRED – IF 

THE UNIT IS TAMPERED WITH IT WILL INVALIDATE THE WARRANTY. 

IF THE UNIT IS FAULTY PLEASE RETURN IT TO YOUR ORIGINAL 

SUPPLIER WITH YOUR PROOF OF PURCHASE. 

 

YOUR SMOKE ALARM WARRANTY 

These smoke alarms are warranty to be free from defects in materials and 

workmanships under normal use and service for a period of five years 

from date of purchase.    The company will not be obligated to repair or 

replace parts which are found to be in need of repair because of misuse, 

damage  or  alterations  occur  after  the  date  of  purchase.    Send  the 

Smoke Alarm with proof of purchase, postage and return postage prepaid, 

to local distributor.    The liability of the company arising from the sale of 

this smoke alarm shall not in any case exceed the cost of replacement of 

smoke alarm and in no case shall the company be liable for consequential 

loss or damages resulting from the failure of the smoke alarm. 

 

SOLAS GEAL DISTRIBUTION LTD. SHALL HAVE NO LIABILITY FOR 

ANY PERSONAL INJURY OR PROPERTY DAMAGE, OR ANY SPECIAL 

INCIDENTAL, CONTINGENT OR CONSEQUENTIAL DAMAGE OF ANY 

KIND  RESULTING  FROM  A  FIRE.  THE  EXCLUSIVE  REMEDY  FOR 

BREACH OF THE LIMITED WARRANTY CONTAINED HEREIN IS THE 

REPAIR  OR  REPLACEMENT  OF  THE  DETECTIVE  PRODUCT  AT 

SOLAS  GEAL  DISTRIBUTION  LTD.  OPTION.  IN  NO  CASE  SHALL 

SOLAS GEAL DISTRIBUTION LTD.’S LIABILITY UNDER ANY OTHER 

REMEDY PRESCRIBED BY LAW EXCEED THE PURCHASE PRICE. 

YOUR  SMOKE  ALARMS  IS  NOT  A  SUBSTITUTE  FOR  PROPERTY, 

DISABILITY,  LIFE  OR  OTHER  INSURANCE  OF  ANY  KIND. 

APPROPRIATE  COVERAGE  IS  YOUR  RESPONSIBILITY.  CONSULT 

YOUR INSURANCE AGENT. 

 

This does not affect your statutory rights. 

 

This alarm is only suitable for single occupancy private dwellings only and 

not  intended  for  multi  occupancy  private  dwellings  or  commercial  or 

industrial dwellings. 

 

Waste  electrical  products  should  not  be  disposed  of  with  normal 

household waste. Please recycle where facilities exist. Check with your 

Local  Authority  or  retailer  for  recycling  advice.  New  regulation  will 

encourage  the  recycling  of  Waste  from  Electrical  and  Electronic 

Equipment (European "WEEE Directive" effective August 2005). 

 

Importer:          Solas Geal Distribution Ltd. 

 

Unit 8 Ashbourne Business Centre, 

 

Ballybin Road, Ashbourne, Co. Meath, 

Ireland

 

 

Ver: 13-MAY-2017 

 

 

Figure 5 

Turn the alarm units clockwise until the snap lock   

engages. 

 

 

 

 

Figure 6 – Push Back the snap lock and turn the 

Alarm anti-clockwise

 

 

 

Figure 4 

Plug the AC QUICK 

CONNECTOR into the 

back of the alarm.

 

 

WARNING: IF THERE IS ANY QUESTION AS TO THE CAUSE 

OF AN ALARM IT SHOULD BE ASSUMED THAT THE ALARM 

unlock

Figure 4

Plug the AC Quick Connector 

into the back of the alarm

Figure 5

Turn the alarm units clockwise until the snap 

lock engages

Figure 6

Push back the snap lock and turn 

the alarm anti-clockwise

Figure 7

Wiring and interconnect facility

Figure 3i    

 

 

Figure 3ii 

Positioning the smoke / heat detector

Отзывы: