Eclipse Linnox SP CCS-LS Скачать руководство пользователя страница 4

Eclipse Linnox Model CCS-LS, Installation Guide 159, 2/20/04

4

There are several special symbols in this document.  You must
know  their meaning and importance.
Following is an explanation of the symbols.  Please read
thoroughly.

Danger:

Indicates hazards or unsafe practices which
WILL result in severe personal injury or even
death.  Only qualified and well trained personnel
are allowed to carry out these instructions or
procedures.
Act with great care and follow the instructions.

Warning:

Indicates hazards or unsafe practices which
could result in severe personal injury or damage.
Act with great care and follow the instructions.

Caution:

Indicates hazards or unsafe practices which could
result in damage to the machine or minor personal
injury.
Act carefully.

Note:
Indicates an important part of the text.
Read thoroughly.

If you need help, contact Eclipse Combustion or your local Eclipse
representative.

D

OCUMENT

 C

ONVENTIONS

H

OW

 

TO

 G

ET

 H

ELP

Содержание Linnox SP CCS-LS

Страница 1: ...No 159 2 20 04 Installation Guide Model CCS LS Version 1 Linnox SP Burners...

Страница 2: ...ates patents No further warranty is expressed or implied We have made every effort to make this manual as accurate and complete as possible Should you find errors or omissions please bring them to our...

Страница 3: ...document covers the basic standard Linnox burner configurations Normally this document is part of the over all project documentation covering the complete burner system Data Sheets 159 1 and 159 2 App...

Страница 4: ...l are allowed to carry out these instructions or procedures Act with great care and follow the instructions Warning Indicates hazards or unsafe practices which could result in severe personal injury o...

Страница 5: ...dling and storage 8 Pre installation Checklist 8 Burner Mounting 9 Gas Supply 9 Electrical Supply 10 Checklist after installation 10 Description of Burner Operation 11 Description of Start up Sequence...

Страница 6: ...tors result in both very low NOx and CO emissions at a high turn down rate while maintaining extremely stable combustion The Linnoxe burner is designed for applications where a linear heat distributio...

Страница 7: ...Never try to light a burner if it shows signs of damage or malfunction Note Personal safety and the Safety of others is a direct result of how equipment is installed operated and maintained Read and...

Страница 8: ...propriate support and handling equipment when lifting the burner Protect the burner from weather damage dirt and moisture Protect the burner package from excessive temperatures and humidity Storage Wh...

Страница 9: ...p for measuring process pressure with or without insulation box refer to assembly drawing with or without gasket between mounting plate and installation refer to assembly drawing Caution The burner fl...

Страница 10: ...ction Wiring diagrams are provided with this Guide GAS PIPEWORK MUST NOT BE USED FOR EARTHING PURPOSES If burner control signals are supplied via a flame safeguard control panel provided by others Ecl...

Страница 11: ...gh a by pass gas valve 13 To prevent condensation both flame rod or UV Cell and igniter are purged with combustion air branched after the first shut off valve To limit the purge air flow a pressure re...

Страница 12: ...ller supplies a gas flow corresponding to the amount of combustion air The high fire gas flow is limited by an adjusting valve that has to be adjusted for the specified gas type at the location of ope...

Страница 13: ...d The mixer gas nozzles are sized for the correct gas type Adjustment steps 1 Preparation 2 Dry run 3 Combustion air check 4 Start up and low fire adjustment 5 Operating checks 1 Ensure all installati...

Страница 14: ...lures do not shut down the fuel system within the required response time immediately correct the problem before proceeding Note On multiple burner systems with a central combustion air blower one shou...

Страница 15: ...rt flame appearance also depends on the start position of the combustion air valve After the pre ignition time 2 sec according EN 746 2 the 2nd shut off valve will open and the Linnox burner will be i...

Страница 16: ...the flame is important to ensure the correct burner adjustment If the recirculating process air is cold 212 F 100 C the burner elements will not glow or just partly start to glow If the recirculating...

Страница 17: ...int until it trips The burner must be at high fire Re set to the original setting and run the ignition cycle again 3 Check the combustion air pressure switch for correct operation by increasing the se...

Страница 18: ...x x x x Burner mixture duct Check burner and mixer unit for leakage damage or deterioration Especially those parts in contact with the process environment must be inspected thoroughly Check the flame...

Страница 19: ...ms before re starting the burner Replace the UV sensor within the time frame as specified by the supplier x x Igniter flame rod Check and clean or replace the igniter flame rod x Thermal overlaod Chec...

Страница 20: ...uence starts but locks out before ignition Combustion air fault Blower failure Blocked blower inlet or filter Pressure switch failure 3 way solenoid valve failure Check blower and remedy fault Clean i...

Страница 21: ...s pressure too high High fire adjusting valve too far open Gas ratio regulator failure Check burner data for correct pressures Replace gas ratio regulator The low fire flame is orange or yellow Burner...

Страница 22: ...Offered By Power Equipment Company 2011 Williamsburg Road Richmond Virginia 23231 Phone 804 236 3800 Fax 804 236 3882 www peconet com...

Отзывы: