2.0 Burner Operating Parameters & Requirements

Performance Data

Note:  Pressures listed below are for sizing purposes only and must NOT be

used for set-up. Use separate metering orifices for burner adjustment.

Gas Inlet Pressure

Burner

Tube

Flame

Nat. Gas

Propane

Size

I.D.

Max. Input

 Length

0.6 s.g.

1.5 s.g.

124

6"

1,000,000 Btu/hr.

22 ft.

7.0" w.c.

6.0" w.c.

English

132

8"

1,750,000 Btu/hr.

23 ft.

7.0" w.c.

6.0" w.c.

Units

140

10"

2,750,000 Btu/hr.

29 ft.

10.0" w.c.

7.5" w.c.

148

12"

4,000,000 Btu/hr.

35 ft.

12.0" w.c.

8.0" w.c.

124

152 mm

293 kW

6.7 m

17.4 mbar

15 mbar

Metric

132

203 mm

513 kW

7.0 m

17.4 mbar

15 mbar

Units

140

254 mm

806 kW

8.9 m

24.9 mbar

18.7 mbar

148

305 mm

1172 kW

10.7 m

29.9 mbar

19.9 mbar

Firing Chamber Limits

Operates best with neutral pressure at exhaust end of immersion tube.

Ambient Temperature Limits

-40

°

 to +104

°

F (-40

°

 to +40

°

C)

3.0 Immersion Tube Design

Bends and Elbows

Immersion tubes may have standard, sweep or miter bends without affecting burner
operation. However, the first elbow must be a minimum of ten tube diameters from the
burner face. Figure 1 details the tube layout and a double mitered bend.

Tube Length

The tube must be long enough to permit complete combustion before fluing to the
stack. If less than maximum rated input is required for the process, maximum tube
length can be reduced in direct proportion to the input reduction from catalog rating.

Draft Hood

Do not seal the discharge of the immersion tube to a stack—use a draft breaking
hood, as detailed in Figure 2. Be sure that the manifold and stack are large enough for
the total flow of exhaust gases.

All draft hood and stack designs must conform to applicable codes.

4.0 Installation

Burner Inspection

Make a thorough inspection of the burner when uncrating and before installing it. If any
parts appear broken, bent, or damaged, contact your Eclipse representative or the
Eclipse factory before installing the burner.

Companion Flange

A companion flange must be welded to the immersion tube. This flange may be pur-
chased from Eclipse or supplied by others; see Figure 3.

Burner Mounting

The main burner casting has an integral mounting flange. With the supplied gasket be-
tween them, bolt the burner mounting flange to the companion flange for an airtight
seal, as shown in Figure 3.

(Section 4.0 is continued on page 4)

If improperly adjusted or operated, burners can produce toxic concentra-
tions of gases, including carbon monoxide.

 Venting these gases into confined,

poorly ventilated areas is dangerous. To avoid this situation:

• Vent the appliance to the outdoors wherever feasible. Refer to the appliance

manufacturer’s instructions for flue and stack design guidelines.

• If outside venting is not possible, be certain that the building has enough vol-

ume and fresh air makeup to keep potentially harmful combustion products
within the safe levels defined by OSHA or other authorities having jurisdiction.

WARNING

Содержание Immerso-Pak 100 IP Series

Страница 1: ...merso Pak burners are packaged nozzle mixing burners de signed to fire long single or multi pass immersion tubes Applications include large industrial immersion heating equipment such as cleaning tank...

Страница 2: ...eduction from catalog rating Draft Hood Do not seal the discharge of the immersion tube to a stack use a draft breaking hood as detailed in Figure 2 Be sure that the manifold and stack are large enoug...

Страница 3: ...nifolded together into a common stack alway use draft hoods and size the stack to handle the total exhaust flow from all the burners plus dilution air This prevents cross feeding of pressure be tween...

Страница 4: ...xces sive pressure losses which can prevent the system from performing properly Use flexible nipples on burner air and gas inlets Solid piping may restrain the burner from thermal expansion and damage...

Страница 5: ...urner in low fire position then starts to control after main gas valve reaches fully open position Connect R to B and motor drives to high fire Disconnect R and B and motor returns to low fire LS 2 Sw...

Страница 6: ...Gas Flow Using Tag Settings Each burner is test fired at Eclipse before shipment and supplied with a tag Figure 6 showing the differential gas pressure that corresponds to maxi mum rated input Attach...

Страница 7: ...stment Gasket Cover Plate Handle shown fully open Cap Adjusting Screw To Adjust Pilot Flame 1 Remove the cap 2 Turn the adjusting pin clockwise for less gas and counterclock wise for more gas Do not r...

Страница 8: ...y valve is open too far 1 Gas flow is rich Proportionator spring is screwed out too far 2 Insuffiicient air flow due to dirty blower filter or impeller 3 Air butterfly valve is closed too far 4 Insuff...

Страница 9: ...ipment out of service and correct the problem Leak test automatic and manual reset fuel valves per insurance procedures Check Bolts Screws Check all bolts and screws for tightness Check for Overheatin...

Отзывы: