As a general rule, care should be taken to ensure that signal cables and cables carrying mains
voltage are routed in separate cable channels!
supply lines must be shielded (cable type: LiYCY)!
CAN bus:
supply lines must be shielded (cable type: J-Y(ST)Y)!
Modbus:
Terminal No.
Function
Base module
SIOX
1
2
3
4
-
CAN bus
SHIELD
GND
CAN-L
CAN-H
5, 6, 7, 8
-
RS232
9, 10, 11, 12
-
TTY
13
14
15
16
-
Modbus RS485* - currently not supported
(-)
(+)
GND
SHIELD
Terminals 13 /14 with integrated 120 ohms terminating resistor
Note: a 120 ohms terminating resistor must be connected at the end of the Modbus!
* For details for the setting, see chapter
Setting of the interface RS485/TTY using jumper J1, page 90
-
SIOX IN
SIOX data cable - input
SIOX OUT
SIOX OUT
SIOX data cable - output
91
92
93
94
95
91
92
93
94
95
SIOX SUPPLY - power supply cable
GROUND of 9 V
+9 V DC
GROUND of 24 V
+24 V DC
SHIELD
6.2.7 D2D – SIOX extension module for discharge gas defrosting
Complete design of the controller – with the SIOX-D2D extension module for discharge gas defrosting in the
last position.
6.2.7.1 D2D - Terminal assignment of the 230 V AC digital inputs
Connection: Only on SIOX-D2D