Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connecting and
disconnecting, it must be checked that
is present at all connections of the controller.
no voltage
For operation, all of the SIOX module’s digital inputs must be set to 230 V
Wiring of the digital inputs:
AC! Operation with inputs configured to 24 V AC is not permissible as this will result in the
destruction of the control component.
Terminal No.
SIOX D2D
Function
50, 51
Manual defrost Z2 cases
52, 53
Manual defrost Z2 cold rooms
54, 55
Manual defrost Z1 cases
56, 57
Disable defrost Z2 cases
58, 59
Disable defrost Z2 cold rooms
60, 61
Disable defrost Z1 cases
62, 63
HP cutout Z2 cases
64, 65
HP cutout Z2 cold rooms
66, 67
HP cutout Z1 cases
68, 69
70, 71
72, 73
Reserve
Reserve
Reserve
If any of the two digital inputs for
of the D2D module (terminals 56/57 and
disabling Z2/ Z2R defrost
58/59) is used for a safety-critical application, additional measures for monitoring must be taken.
6.2.7.2 D2D - Terminal assignment of the 230 V AC relay outputs
Connection: Only on SIOX-D2D