6.8 Battery replacement
Only UA 412 S AC
The case controller has a buffer battery of the
. In order to change the battery, it is
type CR 2450 N, 3 V Lithium
necessary to remove the case controller from the system. In this case, the refrigeration point is
regulated
not
and monitored!
Warning about dangerous electrical voltage! Danger of electric shock! The safety regulations
and work safety instructions in chapter
must be observed for the
battery replacement.
A battery replacement may
be performed by trained personnel or at the factory by the
only
manufacturer!
All plug connectors may only be inserted and removed when the power supply is disconnected
. Label connector if necessary before the removal and then detach.
Circuit boards may only be replaced when the
. Always hold
power supply is disconnected
circuit boards at the edge.
Observe ESD (Electrostatic Discharge) regulations (see manual
ESD - guidelines for handling,
)!
Disconnect case controller and refrigeration point from the power supply. Acknowledge alarm in the
higher level controller if necessary.
Risk of false alarm! The removal of the controller from the CAN bus generates an error message in
the higher level controller (
system centre / store computer / operator terminal
to the precautionary measures that directly affect the control, consequences on the higher level
controllers connected to the CAN bus must also be considered. It must be ensured that
is activated on the higher level controller and that the service centre has previously been
informed accordingly.
Performing the battery replacement
Disconnect case controller and refrigeration point from the power supply. Acknowledge alarm in the
higher level controller if necessary.
Disconnect all plug connectors, remove the device from the DIN rail.
Warning about dangerous electrical voltage! Danger of electric shock! A voltage of 230 V AC
can be present on some connectors.