8.3.3.2 CI 3x00 store computer / AL 300 operator terminal
Before entering values, the input lock must be removed from the store computer or operator terminal as
follows:
Step 1: Select menu item 9 "Parametrisation" in the main menu.
Step 2: Select menu item 3 "Lock-down" in this menu.
Step 3:
A. Unlocking store computer (standard)
Tap the
button (
) to set the marker (
) The lock-down has now been deactivated and it is
ENTER
possible to make settings.
or
B. Unlocking store computer and activating Superuser mode (Superuser permissions)
Input current date backwards (nothing is shown on the display).
The current date is April 17, 2016, i.e. 17/04/16; the required input for enabling Superuser
Example:
permissions is then 614071.
Confirm the input with the
button (
); an " " is shown on the display.
ENTER
S
Step 4: Exit the operating screen and return to the main menu by tapping the
button twice.
ESC
Tip: If you are already in the user interface of a CAN bus node but have forgotten to deactivate the
input lock-down, you can unlock the input lock-down for this controller using the button combination
and . The input lock-down is active again as soon as you exit the user interface of the
MODE
,
controller.
8.3.4 Activating service mode
For repair and maintenance work, service personnel can deactivate the remote alarm function of the system
centre and of the store computer for a limited period using the service mode.
The service mode is exclusively reserved for service personnel!
If there are still pending alarms (with the priority 1..2) after the time for the service mode has elapsed,
the audible warning devices and the alarm relays are activated and the alarms are forwarded using
the automatic transmission of alarms.
8.3.4.1 CI 4x00 System Centre
Activating/deactivating service mode