KGL Operating Manual – UA 412 S
2019-01-14
/
45 122
S1 (10 position)
S2 (1 position)
Set CAN bus address
Function
0
0
00
CAN bus interface inactive (disabled):
0
1..9
01..09
Case controller: CAN bus address assigned
1..9
0..9
10..99
Example:
S1 = 3 = 3 x 10 = 30 and
= 4 = 4 x 1 = 4
S2
CAN bus address = S1 + S2 = 30 + 4 = 34
The case controller does not accept the settings on the decade switches
and
until after the
S1
S2
controller has been briefly disconnected from the power supply!
6.4 Setting of the controller type and master/slave mode
Caution: data loss! All parameters are reset to their factory settings if the controller type is changed
or due to a first start (see chapter
)!
First start / reset controller to factory settings, page 19
Setting of the controller type
The required controller type can be set via the
by adjusting the coding switches 1..9 with a thin
DIP switch S3
screwdriver (D = 2 mm) through a hole in the case cover: