RAHMEN POS: XXXXX
Input
Default
Fixed ED
Fixed run time of the frame heater
Enthalpy regulation
Enthalpy regulation according to room temperature and room humidity
Menu 2-5-2 Frame heater setpoints
SOLLWERTE POS: XXXXX
Input
Default
Mod: xxxxxxxxxxxx
Display of the set frame heater mode (menu 2-5-1)
Fixed ED
Einschaltdauer xxx %
Fixed run time
only displayed for mode = Feste ED (menu 2-5-1)
--, 0..100
100%
Selection list 2-5-3 Toggle mode
The value is selected in accordance with the entry. The check mark indicates the current setting.
RAHMEN UM. POS: XXXXX
Input
Default
Fixed ED
Fixed run time of the frame heater
Enthalpy regulation
Enthalpy regulation according to room temperature and room humidity
Menu 2-5-4 Sollwerte Umsch.
SOLLW. UM POS: XXXXX
Input
Default
Mod: xxxxxxxxxxxx
Display of the set frame heater mode (menu 2-5-3)
Fixed ED
Einschaltdauer xxx %
Fixed run time
only displayed for mode = Feste ED (menu 2-5-3)
--, 0..100
100%
9.1.4 Menu 3 Clock
UHR POS: XXXXX
1 current time
Continue to menu 3-1
2 Defrost timer
Continue to menu 3-2
3. Toggle setpoint
Continue to menu 3-3
Menu 3-1 current time
When connected to the CAN bus, the default time is provided via the time master (system centre
/store computer/operator terminal). In this case, entries are overwritten by the default value.
UHR POS: XXXXX
Input
Default
Date: XX dd/mm/yy
Display and input of current weekday, date
dd/mm/yy
Time: hh.mm
Display and input of current time
hh:mm
So-Wi automat.X
Display and input of automatic summer / winter time changeover (Y/N)
,
, (Y/N)
Y
Menu 3-2 Defrost timer