Function of UA 410 L
14
Firmware V1.50 - Doku 2.0 06. April 2016
4.2
Required and optional sensors
On the standard UA 400 controllers the Sensor Scan function determines the number of sensors connected.
This enables sensors that are not connected to be removed from sensor break monitoring.
However, the following procedure is required with the UA 410 L Temperature Data Logging Controller:
If specific sensors are deactivated for the alarm signalling, the sensor priority must be configured accordingly.
The priority of each sensor can be set separately to ”0” (message) or ”-” (alarm suppressed) when no alarm is to
be signalled on the Temperature Data Logging Controller.
In addition to the sensors that should be monitored, the respective alarm priorities in the UA 410 L should also
be set to the values 0 (message) or 1..2 (alarm signal).
A sensor is recognised as connected in LDSWin (PC software) when its priority is set to 0 .. 2. It is
considered unused within LDSWin (no message/alarm/recording), when its priority is set to --.
Required and optional sensors are listed below:
Controller type
Sensors necessary
Optional sensors
(advanced functions e.g. for control, see
chapter 4.3.1)
UA 410 L
None
Rx.1 Rx.2 Rx.3 Rx.4 Rx.5
Rx.6 Rx.7 Rx.8 Rx.9 Rx.0
Sensor break alarm
Alarm only takes place for sensors set to a sensor alarm priority of 1 or higher. An alert is generated when sen
sor alarm priority is set to 0 and no alarm or message is generated when sensor alarm priority is set to ”-”.
This approach is different from that used with other case/coldroom controllers, on which sensor
break alarm can be set by sensor scan.
4.3
Controller function
The sections following describe the various functions of the UA 410 L for control and temperature recording of
refrigeration points.
4.3.1
Cooling (solenoid valve)
On-off control
Control is made by one temperature sensor (the first five temperature sensors Rx.1 .. Rx.5 only). The cooling
relay de-energizes when temperature reaches the setpoint (switch-off value, Menu 2) on the respective temper
ature sensor. The cooling relay re-energizes with the set hysteresis.
Содержание UA 410 L Case Controller
Страница 30: ...Function of UA 410 L 24 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 52: ...Installation and Startup of UA 410 L 46 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 72: ...Operation of UA 410 L 66 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 80: ...Menu Structure of UA 410 L 74 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 82: ...Decommissioning and disposal 76 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 92: ...Order numbers and accessories of UA 410 L 86 Firmware V1 50 Doku 2 0 06 April 2016 Notice...