Firmware V1.40 - Doku 2.1   06. April 2016

Operating instruction

UA 410 D Case Controller

Controller for discounter and for thermostatic expansion valves - Version V1.40

Содержание UA 410 D

Страница 1: ...Firmware V1 40 Doku 2 1 06 April 2016 Operating instruction UA 410 D Case Controller Controller for discounter and for thermostatic expansion valves Version V1 40...

Страница 2: ...as data sheets more detailed documentation and FAQs are available for you on line in E EDP Eckelmann Electronic Documentation Platform at www eckelmann de elds You reach all relevant documents for thi...

Страница 3: ...1 Application 7 2 2 Hardware 8 2 3 New features compared to previous versions 9 3 Application of UA 410 D 11 3 1 Versions 11 3 2 Controller type 12 3 3 Version update 13 4 Function of UA 410 D 15 4 1...

Страница 4: ...UA 410 D 33 5 1 Installation 33 5 1 1 DIN rail mounting of the controller for discounter 33 5 1 1 1 Mounting on the DIN rail 34 5 1 1 2 Disassembling from the DIN rail 35 5 1 2 Handling of the spring...

Страница 5: ...0 mA analogue inputs 63 6 11 Terminal assignment of the analogue inputs of temperature sensors 64 6 11 1 Sensor identification 65 6 12 Terminal assignment of the USB interface 65 7 Operation of UA 410...

Страница 6: ...nu 0 Main menu 94 8 2 2 Menu 1 Actual Values 94 8 2 3 Menu 2 Setpoints 97 8 2 4 Menu 3 Clock 101 8 2 5 Menu 4 Messages 102 8 2 6 Menu 5 Archive 103 8 2 7 Menu 6 Configuration 104 8 3 Controller type U...

Страница 7: ...27 10 1 5 Hardware fault alarm 127 10 1 6 Alarm routes 127 10 1 7 Termination of alarm 128 10 2 Messages 128 10 3 Transient alarms and messages 128 10 4 Message log 128 11 Specifications of UA 410 D 1...

Страница 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice...

Страница 9: ...Safety instructions or hazard warnings are composed of four elements 1 The pictogram warning sign symbol at the edge of the page 2 A short concise description of the danger 3 A description of the pos...

Страница 10: ...the attention symbol can result in personal injury in extreme cases serious injuries or death and or material damage S Voltage symbol warns of hazardous electrical voltage This work safety symbol warn...

Страница 11: ...d limb If this cannot be ruled out coded plug connectors must be used S Specified ambient conditions e g humidity and temperature limits must be observed and complied with in order to avoid malfunctio...

Страница 12: ...requirements requirements on staff Special skills are required for project planning programming assembly commissioning and maintenance work This work may be performed by qualified and specially train...

Страница 13: ...must be strictly observed 1 Disconnect electric power Disconnect power at all connections of the entire installation on which work is to be carried out Warning hazardous electrical voltage Beware of p...

Страница 14: ...protective packaging provided Avoid materials that may produce electrostatic discharge for example Plastic containers and table tops Synthetic fiber clothing Plastic soled shoes Plastic file covers St...

Страница 15: ...bus through which it communicates with further control and monitoring components across the entire network Via the CAN bus an intelligent data exchange is carried out with the following system compone...

Страница 16: ...mA 4 x Analog inputs 230 V AC 1x BT 300 ESC RESET BT 30 0 4x Case Controllers 1 99 Digital inputs 2 x 4 20 mA 2 wire NTC temperature sensors 2 x Analog outputs 0 10 V USB ZNR 115 130 E1 MODE ESC PRIO...

Страница 17: ...rsions Version 1 40 S New hardware platform UA 410 D blue main board grey coded mating connector with spring terminals see chapter 5 1 2 two row CAN bus spring terminal for easier wiring Version 1 40...

Страница 18: ...A Currently reserve for future applications 2 analogue outputs 0 10 V Currently reserve for future applications Fourth digital input Currently reserve for future applications USB interface For firmwar...

Страница 19: ...the E LDS system F Replacement controller for UA 300 D F Suitable for stand alone operation F With integrated real time clock lithium cell power reserve F With integrated archive memory for data reco...

Страница 20: ...ling For definition of the basic control behaviour only one controller type can always be selected that is set using the DIP switch S3 Controller type DIP Switch S3 Coding Switch positions 1 to 8 1 2...

Страница 21: ...anger data loss In some cases a change of firmware version can lead to the loss of all the set points in the case controller As a precaution the settings must be backed up by saving them to the LDSWin...

Страница 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice...

Страница 23: ...rameter Menu 6 2 5 The following NTC sensor types are usable L243 K243 Temperature range 50 C to 50 C Type K243 sensor can be used in place of type L243 Characteristics of these two sensors are identi...

Страница 24: ...optional sensors are listed below Controller type Sensors necessary for regulation Optional sensors advanced functions Single zone operation UA 111 X UA 111 XP R2 1 R2 2 R2 3 R2 4 R2 5 R2 6 R2 7 R2 8...

Страница 25: ...A 111 X Zone 1 only With the UA 111 X controller the compressors are controlled as a function of the supply air sensors for the first temperature zone see description below Section 4 2 2 1 The cooling...

Страница 26: ...etpoint on the last supply air sensor It is started again when temperature has passed the switching differential on the majority of the supply air sensors ON delay always expires consecutively for Com...

Страница 27: ...d if none has been demanded by the pressure switch within the set interval The time is started as soon as a cooling relay is ener gized If forced actuation is active the pressure switch will not be in...

Страница 28: ...seconds After that time control of the compressors is restored to the pressure switch 4 2 2 8 On off control by all supply air sensors Controller type UA 111 X and UA 111 XP Control takes place throug...

Страница 29: ...r sensor Terminal Z01 02 Valve 1 Solenoid Valve 1 relay Terminal 25 26 28 Valve 2 Solenoid Valve 2 relay Terminal 35 36 38 Compressor 1 relay Terminal 43 44 Compressor 2 relay Terminal 53 54 Compresso...

Страница 30: ...rature reaches the setpoint switch off value on the room air sensor and is restarted with ad justable hysteresis Single zone operation LT rooms R4 1 Room air sensor Terminal Z21 22 Ventil 1 Solenoid V...

Страница 31: ...after each additional hour The following condition also applies If both compressors have been shut down continuous run monitoring is deactivated in this zone for one cycle 1 5 or 1 h When forced shut...

Страница 32: ...of ice forming from normal operation Defrosting takes place either by heating the evaporator electric heating element or off cycling the compressor During defrosting temperature control of the refrige...

Страница 33: ...rt Defrosting can be started by two methods S Internal timer The next defrost cycle cannot be started before the safe defrost time defrost parameter has expired even when defrosting is terminated by e...

Страница 34: ...when the counting rate is set to 0 A defrost counter is set to 6 at the commencement of defrosting and counts down as a function of the set counting rate as long as temperature on the pilot case evap...

Страница 35: ...t Timer Set Man Defrost parameter Menu 3 2 to OFF Termination in LDSWin Click on Terminate Defrost button Manual defrosting can then be initiated again immediately On the UR 141 parameters cannot be s...

Страница 36: ...the setpoint plus hysteresis only the fan starts at first After the fan has started cooling does not restart until the set time delay has expired This second instance will normally occur following def...

Страница 37: ...with cooling and stops with a delay when cooling is stopped Stop delay is contingent on two conditions both of which must be fulfilled The set overrun time must have expired Temperature on the evapor...

Страница 38: ...alues Toggling can be made by two methods Menu 3 3 S EXTERNAL By applying voltage to the 230 V digital input Input 2 terminal D21 D22 by switch of timer S INTERNAL By setting toggle times on the inter...

Страница 39: ...om the controller itself Lighting in the store and outside the display case is likewise not controlled by the controller In states B and C external power is continuously supplied to the display case b...

Страница 40: ...ts the data via the CAN bus to the system centre store computer for archiving 4 2 9 2 Temperature recording to EU Regulation 37 2005 For temperature recording in accordance with the EU regulation 37 2...

Страница 41: ...for the installation Similar to illustration The case controller for discounter is attached to the DIN rail 35 mm using two retaining springs The DIN rail must have a minimum height of 5 mm The case...

Страница 42: ...ase controller and the next component e g cable channel otherwise the re taining springs cannot be pulled out Step 2 Place the case controller on the top edge of the DIN rail and tilt it downwards unt...

Страница 43: ...mbling the safety instructions and work safety instructions in chapter 1 must be observed All connectors may only be connected and disconnected when power is off Step 1 Pull all mating plugs with cabl...

Страница 44: ...ly inserting into the spring terminal is also possible S The wires are disconnected using a screwdriver max 3 5 mm width via the orange push button at the termi nal connection that has no direct conta...

Страница 45: ...1 to 99 by Decade Switches S1 and S2 S Set controller type and Mster Slave mode on DIP Switch S3 S Setting of special functions via DIP switch S3 coding switch 8 10 1 2 1 3 4 5 0 2 3 1 4 6 7 8 9 2 1...

Страница 46: ...oth decade switches are at zero giving address 00 the CAN bus is inactive and the controller is not recognized as a CAN bus station A different CAN bus address must be assigned to each refrigeration p...

Страница 47: ...nged in voltage free state only Settings be come effective on the case controller until the controller is briefly switched off and back on Controller type DIP Switch S3 Coding Switch positions 1 to 8...

Страница 48: ...L N ZNG 116 030 DEF1 230 V AC 11 VA N L PE 50 60 Hz 10 1 D32 D31 D22 D21 D12 D11 73 74 43 44 63 64 53 54 2 1 3 4 CAN GND CAN LOW CAN HIGH SHIELD D42 D41 GND AO2 GND AO1 5 0 2 3 1 4 6 7 8 9 5 0 2 3 1 4...

Страница 49: ...bus Off CAN bus connection interrupted or CAN bus defect 2 Digital inputs red LED2 LED3 LED4 LED5 ON Digital input 1 is activated terminals D11 D12 On Digital input 2 is activated terminals D21 D12 On...

Страница 50: ...the corresponding CAN bus address Kn nnn 1 99 in the selec tion list to be parametrised using the cursor or direct input and recall by tapping the ENTER button so that the main menu of the controller...

Страница 51: ...ller attempts to replace the missing signal with a pressure value measured at the pack controller and transmitted via the CAN bus if available With the installation or after a first start a sensor sca...

Страница 52: ...d this time Defr 1 xxxxx hh mm Enter defrost times Defr 2 xxxxx hh mm Defr 14 xxxxx hh mm Manual Defrost XXX Manual defrosting ON OFF 8 Press the ESC key to exit Menu 2 Defrost Timer 9 Choose Menu 3 S...

Страница 53: ...ain menu of the Store Computer Operator Terminal choose menu 7 Monitoring 3 Configuration and enter amongst other things the case controller node names in plain text 7 Monitoring 3 Configuration CONFI...

Страница 54: ...irst start reset controller to factory settings Caution data loss A first start causes all parameters to be reset to the factory settings All parameters are reset to the factory settings during a firs...

Страница 55: ...tors may only be connected and dis connected when power is off Circuit boards may only be exchanged when power is off Always take hold of circuit boards at the edges ESD regulations must be observed s...

Страница 56: ...attery holder and dispose of it in a proper manner 6 Check that the lid is in the correct position and push it down until it clicks into place 7 Put device on the DIN rail and attach all connectors ag...

Страница 57: ...to the loss of all the setpoints in the case controller As a precaution the settings should be backed up by sav ing them to the LDSWin PC software prior to the update After the firmware update the bac...

Страница 58: ...cting the controller to the PC the installation program Firmware_Up loader_Setup_vxx exe must be executed once Please follow the instructions given by the installation assistant In the following windo...

Страница 59: ...e coding switches 1 8 of the DIP switch S3 must be returned to their original position see chapter 5 10 2 2 Connect the controller while off load to the PC via a USB A B cable Z11 Z12 Z21 Z22 Z31 Z32...

Страница 60: ...e firmware update In order to carry out a successful firmware update the steps described in chapter 5 10 1 must be car ried out once for each PC Step 1 Under Start Programs ECKELMANN Firmware Uploader...

Страница 61: ...ware update the program can be closed The USB A B cable can now be disconnected from the controller Step 6 DIP switch S3 returned to original position Danger of failure of controller After the firmwar...

Страница 62: ...ager select Connections COM and LPT and with the right hand mouse button select the incorrectly installed COM port UA 400 COM Port oder WR 300 COM Port Then press Update Driver and follow the instruct...

Страница 63: ...24 V DC AIN1 GND AIN2 D42 D41 GND AO2 GND AO1 24 V DC OUT GND 24 V DC OUT SHIELD 82 81 83 92 91 93 OFF 1 2 3 4 5 6 7 8 BATTERY 5 0 2 3 1 4 6 7 8 9 5 0 2 3 1 4 6 7 8 9 N L PE RELAY 4 RELAY 5 RELAY 6 RE...

Страница 64: ...60 Hz 10 1 D32 D31 D22 D21 D12 D11 73 74 43 44 63 64 53 54 2 1 3 4 CAN GND CAN LOW CAN HIGH SHIELD D42 D41 GND AO2 GND AO1 5 0 2 3 1 4 6 7 8 9 5 0 2 3 1 4 6 7 8 9 N L PE CAN BUS ADDRESS 1 99 31 32 30...

Страница 65: ...99 TEV2 ALARM L TEV1 1 2 31 32 30 29 RELAY 1 RELAY 2 RELAY 3 15 16 18 25 26 28 35 36 38 LEDs Relay 7 Relay 6 Relay 5 Relay 4 Relay 3 Relay 2 Relay 1 Controller type 73 74 63 64 53 54 43 44 35 36 38 2...

Страница 66: ...16 18 N L invertiert INVERTED invers Alarm ALARM Alarme K hlung COOLING R frig ration Mode of operation positive means that operation of the relay is not inverted The relay is energized when the cont...

Страница 67: ...53 54 2 1 3 4 CAN GND CAN LOW CAN HIGH SHIELD D42 D41 GND AO2 GND AO1 5 0 2 3 1 4 6 7 8 9 5 0 2 3 1 4 6 7 8 9 CAN BUS ADDRESS 1 99 ZNG 112 730 DEF3 31 32 30 29 LEDs Controller type D42 D41 D32 D31 D2...

Страница 68: ...de the refrigerated display case and when external interference for example from parallel power wires is not to be expected see operating instruction Basics and General Safety and Connection Instructi...

Страница 69: ...WITCH S3 ON 1 2 3 4 5 6 7 8 ZNG 112 930 DEF4 CAN HIGH CAN LOW CAN GND CAN BUS wei white blanc braun brown brun gr n green vert SHLD LiYCY 2 x 2 x 0 75 mm 10 1 D32 D31 D22 D21 D12 D11 73 74 43 44 63 64...

Страница 70: ...Z31 Z32 Z41 Z42 Z51 Z52 Z61 Z62 Z71 Z72 Z81 Z82 Z91 Z92 Z01 Z02 DISPLAY 2 1 3 5 4 6 12 11 13 14 82 81 83 92 91 93 24 V DC AIN1 GND AIN2 24 V DC OUT GND 24 V DC OUT SHIELD 82 81 83 92 91 93 24 V DC max...

Страница 71: ...ller must be shielded cable type LiYCY No shielding is required on sensor leads when installed exclusively inside the refrigerated display case and when external interference for example from parallel...

Страница 72: ...nd leads carrying a supply voltage are routed through separate cable channels The case controller analogue inputs are only approved for the connection of temperature sensors as named in chapter 3 1 Co...

Страница 73: ...troller via a PC equipped with LDSWin Z11 Z12 Z21 Z22 Z31 Z32 Z41 Z42 Z51 Z52 Z61 Z62 Z71 Z72 Z81 Z82 Z91 Z92 Z01 Z02 DISPLAY 2 1 3 5 4 6 12 11 13 14 82 81 83 92 91 93 24 V DC AIN1 GND AIN2 24 V DC OU...

Страница 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice...

Страница 75: ...ntre a store computer or an operator terminal The communication with the controller is per formed via the CAN bus MODE ESC PRIO 1 PRIO 2 9 WXYZ 7 PQRS 8 TUV 6 MNO 4 GHI 5 JKL 3 DEF 2 ABC 1 0 ALARM RES...

Страница 76: ...rs and fewer buttons as compared with the system centre the store computer and operator terminal Operation with a system centre store computer operator terminal or the PC software LDSWin pro vides mor...

Страница 77: ...and CI 3x00 AL 300 MODE ESC PRIO 1 PRIO 2 9 WXYZ 7 PQRS 8 TUV 6 MNO 4 GHI 5 JKL 3 DEF 2 ABC 1 0 ALARM RESET 1 8 10 9 7 3 6 ZNR 21003 DEF 01 CI 4000 TOUCH 4 2 5 A B 1 2 8 7 5 6 4 3 1 CI 4x00 Alarms and...

Страница 78: ...for details If any letter is appended e g Menu 3 1 2 a this means that another submenu operating screen or selection list can be reached using the cursor right button The letters indicate their seque...

Страница 79: ...viewed one at a time Arrows appear on the right of the display to indicate whether you can scroll or page through a menu or screen Scrolling Using the cursor buttons and scrolling can be line by line...

Страница 80: ...nu All menus and screens are closed automatically if no key is pressed for 10 minutes The display then jumps to the Main Menu or to the Alarm menu if any fault report is currently active only CI 3x00...

Страница 81: ...m priority of the controller can be input as required Step 3 The main menu of the controller is then displayed by tapping the Remote control button 7 3 2 2 Store computer CI 3x00 operator terminal AL...

Страница 82: ...melden 7 3 3 2 Store computer CI 3x00 operator terminal AL 300 Before entering values the input lock must be removed from the store computer or operator terminal as follows Step 1 Select menu item 9 P...

Страница 83: ...1 System centre CI 4x00 Activating deactivating service mode Service Mode Verz gerung Min Fernalarmierung f r 1 255 Minuten unterdr cken 255 Service Mode wieder aufheben Button dr cken und 0 Minuten...

Страница 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice...

Страница 85: ...ERATUR Cooling Zone 1 1 2 COOLING 1 Defrost Zone 1 1 3 DEFROST 1 Not used with this controller type Alarm 1 5 ALARM Compressor 1 6 COMPRESSOR Cooling Zone 2 1 7 COOLING 2 Defrost Zone 2 1 8 DEFROST 2...

Страница 86: ...1 COMPRESSOR Setpoint toggle 2 5 2 Compr alt Clock 3 CLOCK Current Time 3 1 CLOCK Defrost timer 3 2 DEFROST TIMER Sollwerte toggle 3 3 TOGGLE Messages 4 MESSAGES View 4 1 MESSAGES Acknowledge 4 2 MESS...

Страница 87: ...figuration Move to menu 6 8 1 2 Menu 1 Actual Values Actual Values POS XXXXX 1 Temp Sensor Move to menu 1 1 2 Cooling Zone 1 Move to menu 1 2 3 Defrost Zone 1 Move to menu 1 3 4 Not used with this con...

Страница 88: ...air temperature Input Z91 Z92 Temp R4 8 XXX C Current return air temperature Input Z01 Z02 S Menu 1 2 Cooling Zone 1 COOLING 1 POS XXXXX Cooling XXX Current ON OFF status of cooling Zone 1 Terminals 2...

Страница 89: ...essor 1 XXX Current ON OFF status of Compressor 1 output Terminals 43 44 Compressor 2 XXX Current ON OFF status of Compressor 2 output Terminals 53 54 S Menu 1 7 Cooling Zone 2 COOLING 2 POS XXXXX Coo...

Страница 90: ...e to menu 2 1 1 2 Zone 2 Move to menu 2 1 2 shown only when two zone operation is set Menu 6 1 3 Zone 1A Altern Move to menu 2 1 3 shown only when setpoint toggle is enabled Menu 3 3 4 Zone 2A Altern...

Страница 91: ...3 COOLING 2A POS XXXXX Entry Default Setpoint R2 8 XXX C Supply air temperature setpoint 10 20 1 C Hystersis R2 8 X K Supply air temperature hysteresis setpoint 1 8 2 K S Menu 2 2 Defrost DEFROST POS...

Страница 92: ...etpoint toggle is enabled Menu 3 3 S Menu 2 4 1 Zone 1 ALARM 1 POS XXXXX Entry Default High Temp Setp XX C High temperature setpoint at which High Temperature alarm is generated 30 30 8 C Low Temp Set...

Страница 93: ...ve to menu 2 5 2 Setpoint Toggle S Menu 2 5 1 Setpoints Compressor COMPRESSOR POS XXXXX Entry Default Enable C1 XXX Enable Compressor 1 ON OFF ON Enable C2 xxx Enable Compressor 2 ON OFF ON Delay C1 O...

Страница 94: ...imer XXX Defrost initiation via input D11 12 EXT or internal INT EXT INT INT Safe Defr Time XXX m Safe defrost time for maximum allowed duration of defro sting used only for internal defrosting 0 120...

Страница 95: ...from to TT TT time hh mm shown only when internal set point toggle is activated Menu 3 3 Mo Su etc or numbers hh mm A total of 7 different ON and OFF toggle times can be defi ned A toggle time will on...

Страница 96: ...2 see Note shown only when two zone operation is set Menu 6 1 dd mm yy hh mm Time of archiving Record n Zone 1 abcdef x C Status and temperature of Zone 1 see Note Zone 2 abcdef x C Status and temper...

Страница 97: ...X Associated compressor pack Parameter only required when linked to a VS 3000 BS having several zones If a different type of pack controller is used set this parameter blank or numbers Z1 Z2 No Sensor...

Страница 98: ...ult XX m Sensor break alarm delay 0 30 15 min High Low Temp XX m High low temperature alarm delay 0 120 60 min No Defrost XX h No defrost alarm delay 2 168 24 h Selfholding X Alarm self hold with manu...

Страница 99: ...e L243 is identical with K243 K277 Temperature range 50 to 50 C 5K3A1 Temperature range 50 100 C S Menu 6 3 Cooling COOLING POS XXXXX Entry Default Cont Cool Mon XX m Duration of forced interruption o...

Страница 100: ...r 1 6 COMPRESSOR Cooling Zone 2 1 7 COOLING 2 Defrost Zone 2 1 8 DEFROST 2 Setpoints 2 SETPOINTS Cooling 2 1 COOLING Zone 1 2 1 1 COOLING 1 Zone 2 2 1 2 COOLING 2 Zone 1A Altern 2 1 3 COOLING 1A Zone...

Страница 101: ...R Setpoints toggle 3 3 TOGGLE Messages 4 MESSAGES View 4 1 MESSAGES Acknowledge 4 2 MESSAGES Delete 4 3 MESSAGES Archive 5 ARCHIVE Configuration 6 CONFIGURAT Refrger Point 6 1 REFR PT Controller 6 2 C...

Страница 102: ...figuration Move to menu 6 8 2 2 Menu 1 Actual Values Actual Values POS XXXXX 1 Temp Sensor Move to menu 1 1 2 Cooling Zone 1 Move to menu 1 2 3 Defrost Zone 1 Move to menu 1 3 4 Not used with this con...

Страница 103: ...air temperature Input Z91 Z92 Temp R4 8 XXX C Current return air temperature Input Z01 Z02 S Menu 1 2 Cooling Zone 1 COOLING 1 POS XXXXX Cooling XXX Current ON OFF status of cooling Zone 1 Terminals...

Страница 104: ...mpressor 1 output Terminals 43 44 Compressor 2 XXX Current ON OFF status of Compressor 2 output Terminals 53 54 Compressor 3 XXX Current ON OFF status of Compressor 3 output Terminals 63 64 S Menu 1 7...

Страница 105: ...Move to menu 2 1 1 2 Zone 2 Move to menu 2 1 2 shown only when two zone operation is set Menu 6 1 3 Zone 1A Altern Move to menu 2 1 3 shown only when setpoint toggle is enabled Menu 3 3 4 Zone 2A Alt...

Страница 106: ...air temperature setpoint 10 20 1 C Hystersis R2 8 X K Supply air temperature hysteresis setpoint 1 8 2 K S Menu 2 2 Defrost DEFROST POS XXXXX 1 Zone 1 Move to menu 2 2 1 2 Zone 2 Move to menu 2 2 2 s...

Страница 107: ...XXX Entry Default High Temp Setp XX C High temperature setpoint at which High Temperature alarm is generated 30 30 8 C Low Temp Setp XX K Low temperature setpoint difference below temperature control...

Страница 108: ...r 3 ON OFF OFF Delay C1 ON xxx s Start delay Compressor 1 0 250 60s Delay C2 ON xxx s Start delay Compressor 2 0 250 180s Delay C3 ON xxx s Start delay Compressors 3 0 250 10s Delay C1 OFF xxx s Stop...

Страница 109: ...timer XXX Defrost initiation via input D11 12 EXT or internal INT EXT INT INT Safe Defr Time XXX m Safe defrost time for maximum allowed duration of defro sting used only for internal defrosting 0 120...

Страница 110: ...TT time hh mm shown only when internal set point toggle is activated Menu 3 3 Mo Su etc or numbers hh mm A total of 7 different ON and OFF toggle times can be defi ned A toggle time will only be obeye...

Страница 111: ...e 2 see Note shown only when two zone operation is set Menu 6 1 dd mm yy hh mm Time of archiving Record n Zone 1 abcdef x C Status and temperature of Zone 1 see Note Zone 2 abcdef x C Status and tempe...

Страница 112: ...e XXX Associated compressor pack Parameter only required when linked to a VS 3000 BS having several zones If a different type of pack controller is used set this parameter blank or numbers Z1 Z2 No Se...

Страница 113: ...No Defrost XX h No defrost alarm delay 2 168 24 h Selfholding X Alarm self hold with manual alarm cancellation YES or automatic cancellation on send NO Y N N S Menu 6 2 4 230V Inputs Only trained pers...

Страница 114: ...XXX Entry Default Cont Cool Mon XX m Duration of forced interruption of cooling in continuous running 0 15 0 min Emergency Op XX In failure of required sensors the solenoid is actuated to adjust to th...

Страница 115: ...roller type Cooling Zone 2 1 7 COOLING 2 Defrost Zone 2 1 8 DEFROST 2 Fans Zone 2 1 9 FANS 2 Setpoints 2 SETPOINTS Cooling 2 1 COOLING Zone 1 2 1 1 COOLING 1 Zone 2 2 1 2 COOLING 2 Zone 1A Altern 2 1...

Страница 116: ...MER Setpoints toggle 3 3 TOGGLE Messages 4 MESSAGES View 4 1 MESSAGES Acknowledge 4 2 MESSAGES Delete 4 3 MESSAGES Archive 5 ARCHIVE Configuration 6 CONFIGURAT Refrger Point 6 1 REFR PT Controller 6 2...

Страница 117: ...zone operation is set Menu 6 1 8 Defrost Zone 2 Move to menu 1 8 Menu item is shown only when two zone operation is set Menu 6 1 9 Fans Zone 2 Move to menu 1 9 Menu item is shown only when two zone op...

Страница 118: ...S Menu 1 3 Defrost Zone 1 DEFROST 1 POS XXXXX Counting Rate X Counting rate Defrost Counter X Defrost counter Defrost 1 XXX Current ON OFF status of defrosting Zone 1 Terminals 43 44 Temp R1 1 XXX C...

Страница 119: ...POS XXXXX Cooling XXX Current ON OFF status of cooling Zone 2 Terminals 35 36 38 Run Time XX Cooling relay on time during last day 00 00 24 00 hours Starts X Cooling relay actuations during last day...

Страница 120: ...e is disabled Menu 3 3 Move to menu 2 3 1 4 Alarm Move to menu 2 4 Special case when single zone operation is set Menu 6 1 and setpo int toggle is disabled Menu 3 3 Move to menu 2 4 1 S Menu 2 1 Cooli...

Страница 121: ...2 Move to menu 2 2 2 shown only when two zone operation is set Menu 6 1 3 Zone 1A Altern Move to menu 2 2 3 shown only when setpoint toggle is enabled Menu 3 3 4 Zone 2A Altern Move to menu 2 2 4 sho...

Страница 122: ...oint 10 30 12 C Wait Time Xm Waiting time setpoint 0 15 0m Drip Time Xm Drip time setpoint 0 15 0m S Menu 2 3 Fans FANS POS XXXXX 1 Zone 1 Move to menu 2 3 1 2 Zone 2 Move to menu 2 3 2 shown only whe...

Страница 123: ...o menu 2 4 3 shown only when setpoint toggle is enabled Menu 3 3 3 4 Zone 2A Altern Move to menu 2 4 4 shown only when two zone operation is set Menu 6 1 and only when setpoint toggle is enabled Menu...

Страница 124: ...alarm is generated 30 30 10 C Low Temp Setp XX K Low temperature setpoint difference below temperature control setpoint at which Low Temperature alarm is gene rated 0 6 2 K 8 3 4 Menu 3 Clock CLOCK PO...

Страница 125: ...frosting ON OFF OFF Parameter automatically set to ON for safe defrost time at first start S Menu 3 3 Toggle Setpoints TOGGLE POS XXXXX Entry Default Toggle Setp XXX Setpoint toggle via EXT external d...

Страница 126: ...ssages MESSAGES POS XXXXX Error Message 1 Fault 1 message text dd mm yy hh mm ON Start of Fault 1 dd mm yy hh mm OFF End of Fault 1 only when Fault 1 terminated Error Message n Fault n message text dd...

Страница 127: ...one 2 abcdef x C Status and temperature of Zone 2 see Note shown only when two zone operation is set Menu 6 1 Status abcdef covers following states of the refrigeration point Display will be if state...

Страница 128: ...nsors XX Number of temperature sensors connected After entering sensor scan is performed to redetermine the number of sensors Temp Zones X Number of temperature zones Single zone operation Two zone op...

Страница 129: ...to change inputs as changes may affect other functions 230V INPUT POS XXXXX Entry Default Input1 Door1 Function of Digital Input 1 D11 D12 Coldroom door 1 closed open Door1 Input2 SETP TOG Function o...

Страница 130: ...Menu structure UA 410 D Controller type UR 141 122 Firmware V1 40 Doku 2 1 06 April 2016 S Menu 6 4 Language LANGUAGE POS XXXXX Entry Default Deutsch D English GB Francais F Cesky CZ...

Страница 131: ...ed as a component exclusively for further processing As a consequence of this fact Eckelmann AG does not undertake any measures for the taking back or munici pal recycling of this product as it is not...

Страница 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice...

Страница 133: ...Check parameter setting sensors sy stem 122 High Temp Zone 1 Temperature above upper limit on monitored control sensors of Zone 1 Check parameter setting sensors sy stem 123 High Temp Zone 2 Temperat...

Страница 134: ...ed if the coldroom door remains open beyond a definable time Menu 6 2 3 see chapter 4 2 6 10 1 2 High or low temperature alarm High or low temperature is alarmed when temperature rises or falls to the...

Страница 135: ...n a sensor Sensor break alarm is always generated for sensors vital to control functions In the case of optional sensors alarm is only generated when the sensors have not been removed from monitoring...

Страница 136: ...conditions but not constituting an alarm state are reported via the interfaces and entered in the message log Examples of messages Electric power failure Change of setpoint Manual shutdown Defrosting...

Страница 137: ...e current over PE Max 1 mA Rated surge voltage 2 5 kV Overvoltage category II 4 0 kV Overvoltage category III Relay outputs Relay 4 N O x 230 V AC floating min 10 mA load type ohmic max 6 A inductivel...

Страница 138: ...range Transport 20 C 80 C Operation 0 C 50 C Temperature change Transport max 20 K h Operation max 10 K h Relative humidity non condensing Transport 8 80 Operation 20 80 Shock to DIN EN 60068 2 27 Tr...

Страница 139: ...Gegenstecker mit Kabel Repr sentation sans set de connecteurs View without connector set Darstellung ohne Gegenstecker 257 42 134 128 127 All dimensions in mm 11 3 Mechanical data of the temperature...

Страница 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice...

Страница 141: ...mperature sensor Combined humidity sensor 4 20 mA and temperature sensor Pt1000 4 wire for wall mounting KGLZPTHYGR BT 300 x Operator Interface and Temperature display BT 300 M Operator Interface hand...

Страница 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice...