Installation and Startup of Combi Gateway
21
Version 1.6 04. November 2016
Step 4:
The connection to the LAN is made using a CAT5 patch cable.
Step 5:
The Combi Gateway must be connected to the functional earth and supplied with 24 V DC.
Falls benötigt, muss ein 230 V AC/24 V DC Netzteil verwendet werden (Artikel-Nummer KGLNT23024).
6.2.3
DIP switch to terminate the CAN bus (terminating resistor)
After wiring, the following must be observed for the connection of the Combi Gateway to the CAN bus:
S
CAN bus connection to the LDS system:
C_GD C_H
C_L C_PE
24V 24V
0V
0V
2
1
3
4
6
5
7
8
ZNG: 114 530 E1
2
1
3
4
CAN1
0 V
24 V DC
6
5
7
8
CAN GND
CAN High
CAN Low
SHLD
GN
WS
BR
WS
BR
GN
CAN bus
ATTENTION:
Check CAN bus
wiring!
E LDS
*
standard
wiring
2
1
CAN
Term
ON
OFF
Only if the Combi Gateway is installed at the end of the CAN bus segment, the terminating resistor
of the CAN1 interface
must
be set to
ON
using the DIP switch CAN Term1.
S
CAN bus connection directly at the store computer CI 3000 / CI 3100 via connection cable
(order number KABHICAN2M):
ZNG: 1
16 930 E0
2
1
C_GD C_H
C_L C_PE
CAN
Term
CAN2
24V 24V
0V
0V
2
1
3
4
6
5
7
8
CAN bus
This setting must only be taken into account for high speed connection (CI 3000 / CI 3100 only).
The terminating resistor of the CAN2 interface of the Combi Gateway
must
be set to
ON
using the
DIP switch
CAN Term2
.
Содержание Combi
Страница 1: ...Version 1 6 04 November 2016 Operating instruction Combi Gateway Version V1 57 ...
Страница 6: ...iv Version 1 6 04 November 2016 Notice ...
Страница 18: ...Application Combi Gateway 12 Version 1 6 04 November 2016 Notice ...
Страница 54: ...Decommissioning and disposal 48 Version 1 6 04 November 2016 Notice ...
Страница 58: ...Order No s and accessories 52 Version 1 6 04 November 2016 Notice ...