6
the LED indicators. When the amber LED is blinking, go to step 3.
3. Press and hold the test button again for 6 seconds to select Range
Confirmation Test.
All three LED’s will blink on and off (for 1 second) in this test mode, then if the
sensor receives a range confirmation telegram, the sensor displays the linked
signal strength status for 2.5 seconds, see table below.
LED
Signal Strength
Green - blinking 2.5 sec
-41 to -70 dBm
Amber - blinking 2.5 sec
-70 to -80 dBm
Red - blinking 2.5 sec
-80 to -95 dBm
No LED
No linked receivers detected
The test will repeat every 10 seconds and run for a duration of 50 seconds. You
may quit the test at any time by pressing the test button for 6 seconds.
Commissioning Test Mode:
This mode accelerates the time period between
transmissions of the current light level to every 10 seconds, for a duration of
5 minutes (regardless of amount of energy stored - See “Daylight Harvesting”
above). This test requires a start assist battery to be installed for the duration of
the test.
1. To enter Commissioning Test Mode, press and hold the teach button until
the green LED begins to blink (about 6 seconds).
2. A quick press and release of the button at this point will allow you to select
between test modes. Pressing and releasing the test button scrolls through
the LED indicators. When the red LED is blinking, go to step 3.
3. Press and hold the test button again for 6 seconds to select Commissioning
Test Mode.
You may quit the test at any time by pressing the test button for 6 seconds.
Содержание TAP-21 Series