Note: 

•  Range Confirmation is only available with “F series” or later Echoflex 

Controllers.

•  The MOS must be at full charge and/or have the battery installed for Range 

Confirmation Tests energy requirements.

•  Only one receiver can be linked to the sensor for proper operation of the test.

•  Disable repeaters in range for proper test operation. 

All  three  LED’s  will  blink  (for  1  second)  in  this  test  mode  when  the  sensor 

transmits or receives a Range Confirmation Telegram followed by the sensor 

displaying the linked signal strength status for 2.5 seconds, see table below.

LED

Signal Strength

Green - Solid 2.5 sec -41 to -70 dBm 
Amber - Solid 2.5 sec -70 to -80 dBm
Red - Solid 2.5 sec

-80 to -95 dBm

No LED

No linked receivers detected

The test will repeat every 10 seconds and run for a duration of 3 minutes. You 

may quit the test at any time by pressing the test button for 6 seconds.

Walk Test Mode

Walk test mode allows the installer to verify areas that are within range of the 

motion sensor.

1. To enter walk test mode, press and hold the teach button until the green 

LED begins to blink (about 6 seconds).

2. A quick press and release of the button at this point will allow you to select 

between test modes. Pressing and releasing the test button scrolls through 

the LED indicators. When the red LED is blinking, go to step 3. 

3. Press and hold the test button again for 6 seconds to select walk test. 

The red LED will blink every time a motion sensor trigger is detected. The test 

times out in 100 seconds. If a faster exit from walk test mode is required, press 

and hold the teach button for 10 seconds.

Sensitivity Adjust Mode

The sensitivity adjust mode allows the user to change the PIR sensitivity. False 

occupancy states caused by other elements can be reduced by selecting the 

minimum sensitivity level. The default setting is high sensitivity.

1. To enter sensitivity adjust mode, press and hold the teach button until the 

green LED begins to blink (about 6 seconds).

2. A quick press and release of the button at this point will allow you to select 

between test modes. Pressing and releasing the test button scrolls through 

the LED indicators. When the red and amber LEDs are blinking, go to step 3. 

3. Press and hold the test button again for 6 seconds to select sensitivity 

adjust mode. 

A press and release of the button will allow you to scroll through the settings as 

shown in the table below. 

Содержание MOS-21 Series

Страница 1: ...Motion Sensor with 868 MHz radio with high bay lens The package includes the occupancy sensor and installation guide MOS 21 Sensor Description The 21 series MOS sensor also referred to as the sensor...

Страница 2: ...nds When the sensor awakens and no motion is detected the sensor transmits a vacancy telegram after 100 seconds 200 seconds total since the previous transmission The sensor will remain active until th...

Страница 3: ...tly affect the receivers reception of the telegrams Before installing refer to the sections in the guide detailing the installation of wireless devices layout tips and test operation modes NOTE The se...

Страница 4: ...the lens pops free 4 Choose a mounting method The sensor can be mounted With the screws and anchors not provided to a wall board ceiling Use a pencil to mark the mounting base key hole locations and r...

Страница 5: ...accordance to the light level it is detecting see table below Light Level Test Indication Blinks Lux Foot candles Time to Fully Charge Discharge Time 0 0 0 below operating level n a 1 20 40 2 4 operat...

Страница 6: ...nds 2 A quick press and release of the button at this point will allow you to select between test modes Pressing and releasing the test button scrolls through the LED indicators When the red LED is bl...

Страница 7: ...me wall Avoid locating transmitters and receivers where the telegrams must penetrate walls at acute angles This increases the material the telegram must pass through reducing the signal power Avoid la...

Страница 8: ...t notice Document 8DC 5492 Revision 1 4 8188M21 5492 1 Rev C Regulatory Statements FCC Part 15 231 315 and 902 MHz models only Contains FCC ID TCM300C or TCM300U The enclosed device complies with Part...

Отзывы: