Echoflex Installation Guide
Tri-Zone Dimming Controller
Tri-Zone Dimming Controller
Page 4 of 8
Echoflex
Wiring Diagram
Wiring Diagrams for Emergency Fixtures
Diagram 1 of 2
Tri-Zone Dimming Controller
Power
LED
Clear
Button
Learn
Button
Learn
LED
Black - Line,
120-277 VAC or 240-347 VAC
@ 50/60 Hz 500 mW max
White - Neutral
Red - Load, switched Hot
Channel 2 - Violet with Green stripe
Gray - Dimming COM
Max. Switching Load
(ELED3) 20 A @ 120-277 VAC, Electronic Ballast or LED Driver
(ELED3H) 20 A @ 240-277 VAC, Electronic Ballast or LED Driver
(ELED3H) 16 A @ 347 VAC, Electronic Ballast or LED Driver
Neutral, Hot to LED
Driver #2 and #3
Channel 1 - Violet with Red stripe
Channel 3 - Violet with Blue stripe
Antenna (orange)
Do not cut or cap
Max. Dimming Load: 100 mA sinking
Max. Impulse Voltage: 4000 V
Internal Relay: Type 1.C
Dimming output is Class 1 circuit Independently Mounted Control
for Panel Mount/Surface Mount
Common to LED Driver #2 and #3
0-10 V Dimming to LED Driver #2
0-10 V Dimming to LED Driver #3
Violet - Dimming 0 - 10 V
LED Driver #1
Tri-Zone Dimming Controller
Power
LED
Clear
Button
Learn
Button
Learn
LED
Normal Hot
Normal Neutral
Emergency Hot
Emergency Neutral
Normal
Emergency Load
LED Driver Neutral
LED
Driver
Hot
To LED Driver #2 and #3
Dimming Common to LED Driver #2 and #3
Normal Control Sense
LED Driver
#3
LED Driver
#2
LED Driver
#1
UL924 Emergency
Bypass Relay
(Echoflex Soluons
EREB-AP)
Ch 1 D
Violet with Red stripe
Ch 3 D Violet with Blue stripe
To LED Driver #2 and #3
Ch 2 D
Violet with Green stripe