Echoflex Solutions Installation Guide

SmartSpace Controller–Gen 2

Connect Power Input and Relay Output

The power input and relay output wiring exits the SmartSpace Controller–Gen
2 through the knockout mount on the enclosure.

1.

Connect the power input wiring.

a.

Connect the white wire (14 AWG) to the incoming neutral wire
from the breaker panel and the neutral wire of the lighting load.

b.

Connect the black power input wire (12 AWG) to the line input
feed wire (hot) from the breaker panel.

2.

Connect the relay output wiring. A Single Zone controller has one (red)
relay output wire (12 AWG). A Dual Zone controller has two relay
output wires (12 AWG): Zone 1 is red and Zone 2 is red/white.

a.

Connect the Zone 1 relay output wire (red) to the hot input of the
load.

b.

For the Dual Zone controller, connect the Zone 2 relay output
wire (red/white) to the hot input of the second load.

SmartSpace Controller–Gen 2

Page 7 of 12

Echoflex Solutions

Содержание EDSSC-G2

Страница 1: ...2019 12 Overview The Elaho SmartSpace Controller Gen 2 provides fully rated 20 A relays for direct control of individual fixtures or zone power and offers fully isolated 0 10 V dimming control for com...

Страница 2: ...onnect EchoConnect is a two wire topology free system that provides the SmartSpace Controller Gen 2 with the flexibility to connect in a system with up to 16 Elaho control products and up to 15 other...

Страница 3: ...el supports Power input 120 277 VAC 60 Hz Load rating 20 A general purpose tungsten or resistive 16 A electronic ballast Dual Zone model supports Power input 120 277 VAC 60 Hz Load rating 20 A general...

Страница 4: ...nect is a bidirectional protocol that uses one pair of wires data and data for both data and power Echoflex Solutions recommends using Belden 8471 or approved equal Class 2 wire The total combined len...

Страница 5: ...osition d arr t et suivez les proc dures de Consignation D consignation prescrites par la norme NFPA 70E WARNING For indoor use only Must install to an electrical junction box or wireway AVERTISSEMENT...

Страница 6: ...ire is pulled appropriately Terminate Cat5 wiring using the EchoConnect Cat5 Station Termination Kit and install it using a bus topology See the installation guide that is provided with the Cat5 Stati...

Страница 7: ...re of the lighting load b Connect the black power input wire 12 AWG to the line input feed wire hot from the breaker panel 2 Connect the relay output wiring A Single Zone controller has one red relay...

Страница 8: ...lack Green Yellow EchoConnect Ground Red Load 1 Red White Load 2 Occupancy Sensor 24 VDC 24 VDC Red Common Black Sensor Input Yellow Dual Zone SmartSpace Occupancy Sensor 24 VDC 24 VDC Red Common Blac...

Страница 9: ...erre avant de raccorder tout c blage de commande 0 10V l appareil The 0 10V dimming output wiring exits the SmartSpace Controller Gen 2 through the top nipple of the enclosure with the power wiring 1...

Страница 10: ...Zone model only do not set the Zone switch setting to a number higher than 15 If set to 16 both circuits in the controller will be assigned to and controlled on Zone 16 2 Set the Space rotary switch...

Страница 11: ...ux Input Mode button to cycle through the available sensor types Troubleshooting Restore Defaults To return the SmartSpace Controller Gen 2 to factory defaults set both rotary switches to 16 and then...

Страница 12: ...ert the microSD card in the SD slot on the side of the SmartSpace Controller Gen 2 enclosure The Dim Mode LED will illuminate amber in a triple blink pattern while the firmware is updating and then wi...

Отзывы: