Chengdu Ebyte Electronic Technology Co.,Ltd.
ME31-XXXA0006_UserManual_EN
Copyright ©2012
–
2023, Chengdu Ebyte Electronic Technology Co.,Ltd.
8
2.4 Control Testing
2.4.1 Modbus TCP control
Use the network assistant to control the first AO output of ME31-XXXA0006 to 10mA.
Other functions can be tested through the commands in the table below.
Function (function code)
Command
Control AO1 output 10mA (0x10)
01 00 00 00 00 0B 01 10 00 00 00 02 04 41 20 00 00
Read AO1 output (0x03)
01 00 00 00 00 06 01 03 00 00 00 02
The device is in server mode, and the
computer connects to the device as a client.
Enter the IP address of the device.
Enter the port number of the device.
Select HEX display to facilitate observation
of data.
Select HEX to send