Chengdu Ebyte Electronic Technology Co.,Ltd.
ME31-AAAX2240_UserManul_EN
Copyright ©2012–2022,Chengdu Ebyte Electronic Technology Co.,Ltd
9
To test other function according to below table
Function
(
function code
)
Command
Pull in the first coil
(
0x05
)
01 00 00 00 00 06 01 05 00 00 FF 00
All open
(
0x0F
)
02 00 00 00 00 08 01 0F 00 00 00 04 01 0F
All close
(
0x0F
)
02 00 00 00 00 08 01 0F 00 00 00 04 01 00
Read all DI state
(
0x02
)
01 00 00 00 00 06 01 02 00 00 00 02
Read all DO state
(
0x01
)
01 00 00 00 00 06 01 01 00 00 00 04
2.4.2 Modbus RTU control
Use serial port assistant to control ME31-AAAX2240, first channel DO output.
To test other function according to below table
Function
(
function code
)
Command
Pull in the first coil
(
0x05
)
01 05 00 00 FF 00 8C 3A
All open
(
0x0F
)
01 0F 00 00 00 04 01 0F 74 92
All close
(
0x0F
)
01 0F 00 00 00 04 01 00 3E 96
Read all DI state
(
0x02
)
01 02 00 00 00 02 F9 CB
Read all DO state
(
0x01
)