![Ebyte MA02-XXCX0080 Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/ebyte/ma02-xxcx0080/ma02-xxcx0080_user-manual_530424029.webp)
Chengdu Ebyte Electronic Technology Co.,Ltd.
【
8DO
】
MA02-XXCX0080 User Manual
Copyright ©2012–2021
,Chengdu Ebyte Electronic Technology Co.,Ltd.
第
29
页
7
、
The Modbus is used in the
7.1 List of registers
Form7-1-1 List of registers
Register
address
numb
er
Content of the register
State
scope of data
Applicable
function code
(00000)0x0000
4
DO state
RW
0x00-0xFF,Write changes the
current DO state,Read then gets
the current DO status.
0x01
、
0x05
、
0x0F
(00100)0x0064
4
Status when power on
DO
RW
0x00-0xFF,Set the upper power
state of the DO,After writing,
after the next restart, the DO
state is the set state
.
0x01
、
0x05
、
0x0F
(10000)0x0000
4
DI values
RW
0x00-0xFF,Represents ote the
current level signal of DI.
0x02
(41204)0x04B4
4
DI count values
RW
0x0001-0x0008,Write indicates
the initial value of the set
count,Read out indicates that the
readout has been counted.
0x03
、
0x06
、
0x10
(41400)0x0578
4
DO working mode
RW
0x0000-0x0002,0x0000Level
mode (default mode
)
,Level
mode(default
mode,0x0002Follow mode.
0x03
、
0x06
、
0x10
(41500)0x05DC
4
DO pulse width
RW
0x32-0xFFF(50-65535),Duratio
n of the pulse,/ms.
0x03
、
0x06
、
0x10
(41318)0x0526
4
DI count method
RW
0x0000-0x0002,0x0000 Rising
along the count,0x0001 Decline
along the count,0x0002Level
count.
0x03
、
0x06
、
0x10
(41304)0x0518
4
DI count value reset
method
RW
0x0000-0x0001,0x0000Automat
ic
clearing
method,0x0001Manual
clearance.
0x03
、
0x06
、
0x10
(41311)0x051F
4
Set the clearance method
RW
0x0001-0x00FF.
0x03
、
0x06
、
0x10
(41600)0x0640
4
Set up the DO to follow the
channel
RW
0x0001-0x0008,0x0001
Represents the first input.
0x03
、
0x06
、
0x10
(42000)0x07D0
7
Module model
R
See Model Definition Table.
0x03
(42012)0x07DC
2
The firmware version
R
The firmware version number.
0x03
(42014)0x07DE
10
Module name
RW
The name is 20 bytes including
"\ 0".
0x03
、
0x06
、
0x10
(42027)0X07E8
1
Module software address
RW
0x01-0xE0.
0x03
、
0x06
、
0x10
(42025)0X07E9
1
Restore the default parameter
RW
The parameters written to the
5BB5, settings recover to the
default parameters.
0x03
、
0x06
、
0x10
(42026)0x07EA
1
Equipment restart
RW
The Write to the 5BB5, device
restarts immediately
0x03
、
0x06
、
0x10
(42100)0x0834
1
Potter rate code
RW
The
default
value
is
0x0003,exactly 9600.
0x0000,is 1200
;
0x0001,is 2400
;
0x0002,is 4800
;
0x03
、
0x06
、
0x10