Parameter description
10
08:06
Maximum
temperature heat
supplier
Setting range:
OFF (----), 30 … 110 °C
Factory setting:
90°C
Function:
Irrespective of switching differentials, the pump performs a
forced switch on after the sensor of heat supplier F3 has
exceeded the set value.
08:07
Final switch-off
temperature of heat
supplier
Setting range:
OFF (----), 70 … 210 °C
Factory setting:
OFF
Function:
Irrespective of switching differentials, the pump performs a
forced switch off after the sensor of heat supplier F3 has
exceeded the set value.
08:08
Maximum
temperature heat
storage tank
Setting range:
OFF (----), 50 … 110 °C
Factory setting:
75°C
Function:
Irrespective of switching differentials, the pump performs a
forced switch off after the sensor of heat storage tank F1 has
exceeded the set value. This switch-off takes priority over
functions 08:07 and 08:06.
08:09
Burner block
Heat generator
Setting range:
0 ... 2
X2
Factory setting:
1
Function:
0 = OFF
1 = Burner block when pump is active
2 = Burner block only for DHW when pump
is active
08:10
Temporary
interruption of heat
generator
Setting range:
OFF (----) ... 24h
X2
Factory setting:
OFF
Function:
After burner block is active, the heat generator is also blocked for
the duration of the set time.
08:11
Activation of heat
balance
Setting range:
OFF (----)
X3
1 = Heat balancing via sensor on F2
Factory setting:
1
Function:
The settings of parameters 08:12 to 08:14 are only active if the
heat balance function has been switched on via this parameter.
08:12
Volume flow HT-
medium
Setting range:
0.0 … 30 l/min
Factory setting:
0.0 l/min
Function:
Here the volume flow is set in litre/minute when calculating flow
rate, according to respective pump capacity.
Display
Designation
Description
0450021014_1308-22_BA_CETA100_EbV_EN.book Seite 10 Donnerstag, 21. Februar 2013 11:46 11