background image

IG

_G

PI

G

_P_

IN

T_

R

1

 
 

EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569  •  Toll Free: 800.2EBTRON (232.8766)  •  Fax: 843.756.1838  •  

www.EBTRON.com

 

 

                GP1/HP1/SP1 D

UCT

 & P

LENEM 

P

ROBES 

- I

NTERNAL 

M

OUNT 

Q

UICK 

I

NSTALLATION 

G

UIDE 

a measurable difference! 

EBTRON 

®

 

2

 

INTERNAL MOUNT MARKING AND PREPARATION 

 

1. 

 Each probe package is factory labeled for the specific location and duct size for which it is designed.  

Orders for locations requiring multiple probes at a specific location are typically banded and packaged together. 
Determine the specific duct location for the probe(s) as indicated on the engineer's plans showing where the 
airflow measuring station is to be located.  Refer to Figure 3 for probe spacing and orientation. 
2.  



Carefully open the probe packaging and inspect for damage. Proceed to the specific additional installation 

instructions for rectangular ducts (at step 3), round ducts (at step 6) or flat oval duct applications (at step 9). 

 

For Rectangular Ducts 
3.  



 The first dimension of the probe size indicates the length of the probe. The second dimension indicates 

the specific duct internal mounting inside dimension 'X' (including internal insulation). On ducts with internal 
insulation that cannot be removed, adjust ‘X’ to equal the internal mounting inside dimension, minus two times 
the thickness of the insulation.  Refer to Figure 2 and verify that the probe is the correct size for the application 
duct size. Mark a point on the center of the inside of the duct at ‘X’. Draw a line on the inside of the duct at this 
point that is perpendicular to the edge of the duct. This line will be used to locate the position of the probe 
mounting brackets. The probe quantity for the measurement site determines the probe installation 
configuration/orientation as shown in Figure 3. 
4. 



Using the applicable Rectangular Duct Probe mechanical and spacing details of Figures 2 and 3, mark 

the location for the cable exit end of each probe bracket at the location line(s) drawn in step 3. 

 

5.  



Mark the other corresponding end bracket (without cable) installation locations for each probe at the 

opposite side of the inside duct wall.  
Proceed to step 12, Final Assembly. 
 
For Round Ducts 
6.  

 

Mark and draw a line around the inside circumference of the duct at the point where the probe brackets 

are to be installed. The number of probes for this specific measurement site determines the probe installation 
configuration and orientation as shown in Figure 3. Applications with multiple probes must be staggered 1.5 to 
2 in (38.1 to 50.8 mm) from each other as shown in Round Duct Probe Spacing detail of Figure 4 to prevent 
probes from intersecting at the center of the duct. 
7. 



Using the Round Duct Probe Spacing detail of Figure 3, locate and mark the individual probe 

mounting location(s) on the circumference line drawn in step 6. 
8. 



Mark the non cable end bracket installation locations for each probe on the opposite side of the inside 

duct wall. 
Proceed to step 12, Final Assembly. 

 

For Flat Oval Ducts 
9.  

 

Mark and draw a line around the inside circumference of the duct at the point where the probes are to 

be installed. For oval duct applications, orientation is as shown in the Oval Duct Probe Spacing table and detail 
application illustrations of Figure 3. Configuration ‘2b’, ‘3b’ and ‘4b’ probes must be staggered 1.5 to 2 in (38.1 
to 50.8 mm) from each other in order to prevent probes from intersecting at the center of the duct. 
10.

 

Using the Round Duct Probe Spacing detail of Figure 3, locate and mark the individual probe installation 

location(s) for the cable exit end of each probe bracket on the circumference line drawn in step 6. 
11.

 

Mark the non cable end bracket installation locations for each probe on the opposite side of the inside duct 

wall. 
Proceed to step 12, Final Assembly. 

Отзывы: