background image

 

Startup_GTF116e

-

P_r1a   Page 1 of 2

 

STARTUP INSTRUCTIONS:  
1.  Verify that the sensor probes are located where they meet EBTRON published installation guides. 
2.  Verify that the probes are  properly spaced with the airflow arrows pointing in the direction of airflow. 

 

Improperly installed probes will compromise the installed accuracy of the device and degrade system 
performance.

 

3.  Verify that the transmitter is installed and wired in accordance with the 

GTF116e-P Wiring Guide

 

provided with the transmitter and power is provided to the transmitter. 

4.  Make sure the ductwork is clean and free of debris prior to fan startup. 
5. 

Move the power switch to the “ON” position.  Power

-up faults, if detected, are displayed on the LCD.   

If any power up faults are detected, resolve all conflicts or contact EBTRON customer service at        
1-800-232-8766 before proceeding.. 

 

If extension cables have been added, the extension cable length must be entered into the transmitter.  
Refer to the Operations and Maintenance Manual for more information.

 

Advantage IV (A4) GTF116e

-

P STARTUP GUIDE

 

SW1

TX

RX

WINK

ACT

N1

N2

A1

A2

A3

C

L2

L1

TYPE B

TYPE A

Description

Parameter Default

Optional Settings/Ranges

Units

System of Units

SYS

I-P (US customary) SI (metric)

Airflow Calculation Method

AIRFLOW

ACT (actual)

STD (standard mass flow)

Altitude (for actual flow correction) ALT

0

AUTO, 0 to 20000 [0 to 6000]

ft [m]

Low Limit Airflow Cutoff

LLIMIT

0 FPM

0 to 500 FPM [0.0 to 2.5 m/s]

Area

AREA

{Order Area}

0.00 to 9999.99 [0.000 to 999.999]

sq ft [sq m]

Humidity Sensor Config. (/H opt.) H CONFIG RH (relative humidity) ENTH (enthalpy), DPT (dew point)
Auto Pb Correct Psych. Values Pb CORR

ON (onboard sensor) OFF

AO1, AO2 and AO3 Type

AOUT

4-20mA

0-10V, 0-5 V

AO1 Assignment

AO1 ASGN AF (Airflow)

None

AO1 Unit of Measure

AO1 UM

FPM [m/s]

CFM [L/s]

AO1 Minimum Scale Reading

AO1 MS

0

None

FPM [m/s]

AO1 Full Scale Reading

AO1 FS

5000 [25.0]

100 to 15000 [0.5 to 75.0]

FPM [m/s]

AO2 Assignment

AO2 ASGN TEMP (Temperature) ALRM (Alarm) or TRBL (System Trouble)

AO2 Unit of Measure

AO2 UM

F [C]

None

°F [°C]

AO2 Minimum Scale Reading

AO2 MS

-20 [-30]

-50 to 160 [-50 to 70]

°F [°C]

AO2 Full Scale Reading

AO2 FS

160 [70]

-50 to 160 [-50 to 70]

°F [°C]

AO3 Assignment

AO3 ASGN RH

None

AO3 Unit of Measure

AO3 UM

% RH

None

AO3 Minimum Scale Reading AO3 MS

0

0 to 100

% RH

AO3 Full Scale Reading

AO3 FS

100

0 to 100

% RH

AO3 Assignment

AO3 ASGN ENTH

None

AO3 Unit of Measure

AO3 UM

Btu/lb [kJ/kg]

None

AO3 Minimum Scale Reading AO3 MS

0

-20 to 400 [-40 to 800]

Btu/lb [kJ/kg]

AO3 Full Scale Reading

AO3 FS

200 [400]

-20 to 400 [-40 to 800]

Btu/lb [kJ/kg]

AO3 Assignment

AO3 ASGN DPT

None

AO3 Unit of Measure

AO3 UM

F DPT [C DPT]

None

AO3 Minimum Scale Reading AO3 MS

0

-50 to 160 [-50 to 70]

°F [°C]

AO3 Full Scale Reading

AO3 FS

100 [50]

-50 to 160 [-50 to 70]

°F [°C]

Lon Network xif File Link

Refer to the O&M Manual for more information and/or additional parameter defaults, settings and ranges. 

GTF116e-P Parameters - Factory Defaults and Optional Settings/Ranges

H CONFIG=RH (default)

H CONFIG=ENTH

H CONFIG=DPT

https://ebtron.com/wp-content/uploads/software/EBTRON_116e.xif

Отзывы: