Startup_GTF116e
-
P_r1a Page 1 of 2
STARTUP INSTRUCTIONS:
1. Verify that the sensor probes are located where they meet EBTRON published installation guides.
2. Verify that the probes are properly spaced with the airflow arrows pointing in the direction of airflow.
Improperly installed probes will compromise the installed accuracy of the device and degrade system
performance.
3. Verify that the transmitter is installed and wired in accordance with the
GTF116e-P Wiring Guide
provided with the transmitter and power is provided to the transmitter.
4. Make sure the ductwork is clean and free of debris prior to fan startup.
5.
Move the power switch to the “ON” position. Power
-up faults, if detected, are displayed on the LCD.
If any power up faults are detected, resolve all conflicts or contact EBTRON customer service at
1-800-232-8766 before proceeding..
If extension cables have been added, the extension cable length must be entered into the transmitter.
Refer to the Operations and Maintenance Manual for more information.
Advantage IV (A4) GTF116e
-
P STARTUP GUIDE
SW1
TX
RX
WINK
ACT
N1
N2
A1
A2
A3
C
L2
L1
TYPE B
TYPE A
Description
Parameter Default
Optional Settings/Ranges
Units
System of Units
SYS
I-P (US customary) SI (metric)
Airflow Calculation Method
AIRFLOW
ACT (actual)
STD (standard mass flow)
Altitude (for actual flow correction) ALT
0
AUTO, 0 to 20000 [0 to 6000]
ft [m]
Low Limit Airflow Cutoff
LLIMIT
0 FPM
0 to 500 FPM [0.0 to 2.5 m/s]
Area
AREA
{Order Area}
0.00 to 9999.99 [0.000 to 999.999]
sq ft [sq m]
Humidity Sensor Config. (/H opt.) H CONFIG RH (relative humidity) ENTH (enthalpy), DPT (dew point)
Auto Pb Correct Psych. Values Pb CORR
ON (onboard sensor) OFF
AO1, AO2 and AO3 Type
AOUT
4-20mA
0-10V, 0-5 V
AO1 Assignment
AO1 ASGN AF (Airflow)
None
AO1 Unit of Measure
AO1 UM
FPM [m/s]
CFM [L/s]
AO1 Minimum Scale Reading
AO1 MS
0
None
FPM [m/s]
AO1 Full Scale Reading
AO1 FS
5000 [25.0]
100 to 15000 [0.5 to 75.0]
FPM [m/s]
AO2 Assignment
AO2 ASGN TEMP (Temperature) ALRM (Alarm) or TRBL (System Trouble)
AO2 Unit of Measure
AO2 UM
F [C]
None
°F [°C]
AO2 Minimum Scale Reading
AO2 MS
-20 [-30]
-50 to 160 [-50 to 70]
°F [°C]
AO2 Full Scale Reading
AO2 FS
160 [70]
-50 to 160 [-50 to 70]
°F [°C]
AO3 Assignment
AO3 ASGN RH
None
AO3 Unit of Measure
AO3 UM
% RH
None
AO3 Minimum Scale Reading AO3 MS
0
0 to 100
% RH
AO3 Full Scale Reading
AO3 FS
100
0 to 100
% RH
AO3 Assignment
AO3 ASGN ENTH
None
AO3 Unit of Measure
AO3 UM
Btu/lb [kJ/kg]
None
AO3 Minimum Scale Reading AO3 MS
0
-20 to 400 [-40 to 800]
Btu/lb [kJ/kg]
AO3 Full Scale Reading
AO3 FS
200 [400]
-20 to 400 [-40 to 800]
Btu/lb [kJ/kg]
AO3 Assignment
AO3 ASGN DPT
None
AO3 Unit of Measure
AO3 UM
F DPT [C DPT]
None
AO3 Minimum Scale Reading AO3 MS
0
-50 to 160 [-50 to 70]
°F [°C]
AO3 Full Scale Reading
AO3 FS
100 [50]
-50 to 160 [-50 to 70]
°F [°C]
Lon Network xif File Link
Refer to the O&M Manual for more information and/or additional parameter defaults, settings and ranges.
GTF116e-P Parameters - Factory Defaults and Optional Settings/Ranges
H CONFIG=RH (default)
H CONFIG=ENTH
H CONFIG=DPT
https://ebtron.com/wp-content/uploads/software/EBTRON_116e.xif