Quick Guide - SBU IO-Link
Page 8 of 10
B04
Commissioning
Once the SBU IO-Link has been connected to the controller on the user side in accordance with section B03, no
further actions are necessary. The operating states of the SBU IO-Link can be determined and parametrised with the
aid of the EBRO Connect App.
Make sure that the SBU IO-Link is firmly mounted as intended on the quarter turn actuator and is electrically
connected.
Switch the SBU IO-Link on only when the switch box is closed.
The input and output states are additionally signalled by LEDs on the PCB.
Two light elements on the housing cover serve as visual feedback of the valve's position status
(CLOSED/OPEN)
B05
Errors in general
If the SBU IO-Link does not work after connecting the power supply, make sure that the power supply is taken
through to the terminal point and has been connected properly. If the red LED lights up, the power supply polarity is
reversed. Correct polarity of the power supply is signalled by the green LED.
B06
Collective error
Errors are signalled by the flashing of the red Error LED and the switching of the Collective Error output X1.6.
No error messages have any effect on the current program sequence.
The error is reset once the cause of the error has been rectified.
B07
Errors
– Cause – Remedial action
Errors that can be signalled by the SBU IO-Link are:
Error
Cause
Remedial action
Collective
error
Runtime monitoring:
The set running time is exceeded.
Default value: 0 s (deactivated)
Check the following components:
-
Valve switched
-
Actuator function
Check compressed air supply
Check the position of the cam plate.
Check for jamming in the pipeline.
The fault is automatically reset as soon
as the repeated ride is within the time
tolerance.
Max. switching cycles:
Max. set switching cycles reached.
Default value: 0 n (deactivated)
Check the number of switching cycles
performed.
Reset or increase the counter.