10
Technicaldata
6
TECHNICAL DATA
6.1
Conformity
The positioner Type EP 501 B conforms to the EC directives
according to the EC Declaration of Conformity.
6.2
Standards
The applied standards which are used to demonstrate compliance
with the EC Directives are listed in the EC-Type Examination
Certificate and/or the EC Declaration of Conformity.
6.3
Operating conditions
NOTE!
If used outside, the device may be exposed to direct sunlight
and temperature fluctuations which may cause malfunctions
or leaks!
• If the device is used outdoors, do not expose it unprotected to
the weather conditions.
• Ensure that the permitted ambient temperature does not exceed
the maximum value or drop below the minimum value.
Ambient temperature
0 ... +60 °C
Degree of protection
IP65 / IP67
1)
according to EN 60529
(only if cables, plugs and sockets have
been connected correctly)
1)
When using the positioner under IP67 conditions, the air
exhaust filter (see “Fig. 1”) must be removed and the exhaust air
conveyed to the dry area.
6.4
Mechanical data
Dimension
see data sheet
Material
Housing material
plastic-coated aluminum
Other external parts
stainless steel (V4A), PC, PE, POM, PTFE
Sealing material
EPDM, NBR, FKM
Weight
approx. 1.0 kg
6.5
Electrical data
Connections
2 cable glands (M20 x 1.5) with screw ter-
minals 0.14 ... 1.5 mm
2
or circular plug-in
connector
(M12, 8-pole)
Interfaces
communication interface USB:
Direct connection to PC via USB adapter.
Communication with communications
software based on FTD/DTM technology.
An external adapter with integrated
interface driver is required.
Supply voltage
24 V DC ± 10 %
max. residual ripple 10 %
Power consumption
< 3.5 W
Input resistance for
set-point value signal
180
Ω
at 0/4 - 20 mA / 12 bit resolution