Operating instructions

W8D630-KN01-01

Translation of the original operating instructions

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

Recommendation for fastening AxiCool fan with screws: (based on VDI
2230)

;

Use screws of strength class 8.8.

;

For sizes 500 and 630, screws M8 with a tightening torque of max.
20 Nm.

;

For size 800, screws M10 with a tightening torque of max. 40 Nm.

The tightening torques specified above are based on the following values
are only valid for them:

The contact surfaces must be flat.

The fan must not be strained on fastening.

As every application is different, the tightening torque recommended
by ebm-papst must be checked in the application concerned.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

NOTE
Water ingress into wires or cables

Water ingresses at the customer cable end and can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment and that the connection point is lower than the
motor if possible.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

Protective earth contact resistance according to EN 61800-5-1

Compliance with the resistance specifications according to EN 61800-5-
1 for the protective earth connection circuit must be verified in the end
application. Depending on the installation situation, it may be necessary
to connect an additional protective earth conductor by way of the extra
protective earth terminal provided on the device. The protective earth
terminal is located on the housing and provided with a protective earth
symbol and a hole.

4.2.2 Residual current circuit breaker (RCCB)

If the use of a residual current device (RCD) is required in your
installation, only pulse-current sensitive and/or AC/DC-
sensitive residual current devices (type A or B) are
permissible. As with variable frequency drives, residual current
devices cannot provide personal safety while operating the
device.

4.2.3 Voltage control

NOTE

Current overshoots may occur if speed control is implemented
by transformers or electronic voltage regulators (e.g. phase
control). Depending on the type of installation of the device,
noise and vibration may also occur in the case of phase
control. Vibration can lead to bearing damage and thus
premature failure.

4.2.4 Variable frequency drive

Please use a variable frequency drive only after consultation with ebm-
papst.
When a variable frequency drive is used for speed adjustment, the
maximum safe operating speed (see 3.2 Nominal data) may not be
exceeded.

For operation with variable frequency drives, install sinusoidal
filters that work on all poles (phase-phase and phase-ground)
between the drive and the motor.
During operation with variable frequency drives, an all-pole
sine filter protects the motor against high-voltage transients that
can destroy the coil insulation system, and against harmful
bearing currents.

Heating-up of the motor when using a variable frequency drive must be
checked by the customer following installation in the end device.

Item no. 15829-5-9970 · ENU · Change 99214 · Approved 2018-05-15 · Page 8 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W8D630-KN01-01

Страница 1: ...ized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed ...

Страница 2: ...d grill to load Do not place any objects on the guard grill There must be sufficient space around the fan to be able to get past the fan 1 6 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING...

Страница 3: ...ing the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flo...

Страница 4: ...ll dimensions in mm 1 Airflow direction V 2 Cable silicone 6G 0 5 mm 6x crimped ferrules 3 Mounting holes for FlowGrid Item no 15829 5 9970 ENU Change 99214 Approved 2018 05 15 Page 4 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...pport struts only in X position as illustrated or rotor on bottom 2 For horizontal shaft installation position the cable exit must be at the bottom right Item no 15829 5 9970 ENU Change 99214 Approved 2018 05 15 Page 5 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 6: ...mum efficiency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 18 84 kg Size 630 mm Motor size 110 Rotor surface Painted black Terminal box material PP plastic Blade material Press fitted sheet steel blank sprayed with PP plastic Fan housing material PP plastic Material guide vanes PP plastic Guard grille mate...

Страница 7: ...r the AxiCool fans ebm papst recommends the use of a drip pan in conjunction with the AxiCool heating tape The drip pan designed for the AxiCool fan housing is available from ebm papst under the following item number Size Item no 630 mm 41201 1 4050 Installation instructions are included with every ebm papst drip pan and must be heeded on assembly 3 7 3 AxiCool terminal box A terminal box kit for ...

Страница 8: ...wer supply matches the device voltage Only use cables designed for the current level indicated on the nameplate For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth must have a cross section equal to or greater than that of the phase conductor We recommend the use of 105 C cables Ensure that the minimum cable cross section is at least AWG 26 0 1...

Страница 9: ...When working on the device secure the system machine in which the device is installed so as to prevent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect the thermal overload protector installed in the winding The motors are equipped with thermal overload protectors to protect the devices Check to make sure that th...

Страница 10: ...ange of rotation direction by reversing two phases Δ Delta connection L1 blue L2 black L3 brown TW Thermal overload protector gray 2x PE green yellow Item no 15829 5 9970 ENU Change 99214 Approved 2018 05 15 Page 10 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 11: ...determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure 4 8 Switching off the device Disconnect the device from the power supply at the supply line s main switch When disconnecting be sure to disconnect the ground connection las...

Страница 12: ...otection are fixed criteria The following section contains recommendations for ecological disposal of the product and its components 5 3 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding di...

Страница 13: ...employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 15829 5 9970 ENU Change 99214 Approved 2018 05 15 Page 13 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Отзывы: