Operating instructions

W6D800-NG13-01

Translation of the original operating instructions

4.4 Connection diagram

Three-phase motor with externally wired TOP
Change of rotation direction by reversing two phases

Δ

Delta connection

L1

black

L2

blue

L3

brown

TW

Thermal overload protector gray (2x)

PE

green/yellow

Item no. 16111-5-9970 · ENU · Change 98149 · Approved 2020-10-01 · Page 10 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W6D800-NG13-01

Страница 1: ...ized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed ...

Страница 2: ...the fan to be able to get past the fan 1 6 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangle...

Страница 3: ...ing the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flo...

Страница 4: ... dimensions in mm 1 Airflow direction V 2 Cable halogen free 6G 0 75 mm 6x crimped splices 3 Mounting holes for FlowGrid Item no 16111 5 9970 ENU Change 98149 Approved 2020 10 01 Page 4 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...pport struts only in X position as illustrated or rotor on bottom 2 For horizontal shaft installation position the cable exit must be at the bottom right Item no 16111 5 9970 ENU Change 98149 Approved 2020 10 01 Page 5 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 6: ...s PP plastic Guard grille material Steel coated with black plastic RAL 9005 Number of blades 5 Blade pitch 0 Airflow direction V Direction of rotation Clockwise viewed toward rotor Degree of protection IP54 Insulation class F Moisture F Environmental H protection class H2 Ambient temperature note If there is a risk of ice formation the fan is only to be operated with a heating tape in the fan hous...

Страница 7: ...rovides an ideal means of connecting the electrical connections of the motor heating tape and drip pan The terminal box kit to suit the AxiCool fan housing and motor is available from ebm papst under the following item number Motor connection Item no M__110 M__138 AC 50015 1 7612 Installation instructions are included with every ebm papst terminal box kit and must be heeded on assembly 4 CONNECTIO...

Страница 8: ...device voltage Only use cables designed for the current level indicated on the nameplate For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth must have a cross section equal to or greater than that of the phase conductor We recommend the use of 105 C cables Ensure that the minimum cable cross section is at least AWG 26 0 13 mm 4 2 2 Residual cur...

Страница 9: ...witched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect the thermal overload protector installed in the winding The motors are equipped with thermal overload protectors to protect the devices Check to make sure that the thermal overload protector is correctly connected before each operation Failure to connect the thermal overload prot...

Страница 10: ...ange of rotation direction by reversing two phases Δ Delta connection L1 black L2 blue L3 brown TW Thermal overload protector gray 2x PE green yellow Item no 16111 5 9970 ENU Change 98149 Approved 2020 10 01 Page 10 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 11: ...n switch When disconnecting be sure to disconnect the ground connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm papst for repair or replacement WARNING Live terminals and connections even with device switched off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the devi...

Страница 12: ...ure 5 2 Safety inspection What to check How to check How often What action Contact protection cover for intactness or damage Visual inspection At least every 6 months Repair or replacement of device Device for damage to blades and housing Visual inspection At least every 6 months Replacement of device Fastening the cables Visual inspection At least every 6 months Fasten Fastening the protective ea...

Страница 13: ... external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires are made of similar materials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for inte...

Отзывы: