Operating instructions

W4D710-ND01-01

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All dimensions in mm.

1

Airflow direction "V"

2

Tightening torque 1.5 ± 0.2 Nm

3

Cable diameter min. 7 mm, max. 14 mm, tightening torque 4 ± 0.6 Nm

Item no. 17033-5-9970 · ENU · Change 212910 · Approved 2020-09-11 · Page 4 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W4D710-ND01-01

Страница 1: ...authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic...

Страница 2: ...the fan 1 6 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on th...

Страница 3: ...ollowing ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also in...

Страница 4: ...ons in mm 1 Airflow direction V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 7 mm max 14 mm tightening torque 4 0 6 Nm Item no 17033 5 9970 ENU Change 212910 Approved 2020 09 11 Page 4 12 ebm p...

Страница 5: ...at optimum efficiency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 42 kg Size 710 mm Motor size 138 Rotor s...

Страница 6: ...of physical injury such as back injuries Use suitable hoisting equipment to remove the device from its packaging CAUTION The blades of the impeller could be damaged Carefully set down the fan on a so...

Страница 7: ...sure that the minimum cable cross section is at least AWG 26 0 13 mm 4 2 2 Residual current circuit breaker RCCB If the use of a residual current device RCD is required in your installation only pulse...

Страница 8: ...cable is routed in a U shaped loop Fig 2 Fan installed lying flat cable routed in a U shaped loop Fans installed upright When routing the cable make sure that the cable glands are located at the bott...

Страница 9: ...tion Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2x gray PE green yellow Item no 17033 5 9970 ENU Change 212910 Approved 2020 09 11 Page 9 12 ebm papst Mulfing...

Страница 10: ...inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant frequencies...

Страница 11: ...d replace it Repair of load bearing or rotating parts is not permitted Operate the fan for 2 hours at maximum speed so that any water that has ingressed can evaporate If cleaning does not eliminate vi...

Страница 12: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...