Operating instructions

W4D300-DT04-09

Translation of the original operating instructions

4.3 Connecting the cables

The device has external leads.

;

First connect the "PE" (protective earth).

Connect the cables according to your application. When doing so,
observe Chapter 4.4 Connection diagram.

4.3.1 Cable routing

Water must be prevented from reaching the cable exit along the cable.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

Fans installed lying flat

Fig. 1: Fan installed lying flat, cable routed in a U-shaped loop.

Fans installed upright

Fig. 2: Cable routing for fans installed upright. The cables must always
be routed downward.

4.3.2 Motor protection

CAUTION
Voltage

The device is a built-in component and has no disconnecting
switch.
→ Connect the device to a suitable tripping unit.
→ Only connect the device to circuits that can be switched

off with an all-pole disconnection switch.

→ When working on the device, secure the system/

machine in which the device is installed so as to prevent it
from being switched back on.

NOTE
Lack of motor protection

Without motor protection, the motor can overheat and suffer
damage.
→ Connect the thermal overload protector installed in the

winding.

The motors are equipped with thermal overload protectors to protect the
devices.
Check to make sure that the thermal overload protector is correctly
connected before each operation.
Failure to connect the thermal overload protector correctly will
invalidate your warranty claim.

Item no. 16471-5-9970 · ENU · Change 202174 · Approved 2019-01-07 · Page 7 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W4D300-DT04-09

Страница 1: ...and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the elect...

Страница 2: ...to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNIN...

Страница 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Страница 4: ...Product drawing All dimensions in mm 1 Airflow direction V 2 Cable PFA AWG20 9x crimped ferrules Item no 16471 5 9970 ENU Change 202174 Approved 2019 01 07 Page 4 10 ebm papst Mulfingen GmbH Co KG Ba...

Страница 5: ...circuit Fig 4 TN system 0 75 mA Motor protection Thermal overload protector TOP with basic insulation with cable Lateral Protection class I with customer connection of protective earth Conformity wit...

Страница 6: ...nvironment Only connect the device to circuits that can be switched off with an all pole disconnection switch 4 2 1 Requirements Check whether the information on the nameplate matches the connection d...

Страница 7: ...or fans installed upright The cables must always be routed downward 4 3 2 Motor protection CAUTION Voltage The device is a built in component and has no disconnecting switch Connect the device to a su...

Страница 8: ...phases Delta connection Y Star connection L1 black L2 blue L3 brown U1 black V1 blue W1 brown U2 green V2 white W2 yellow TOP 2x gray PE green yellow Item no 16471 5 9970 ENU Change 202174 Approved 2...

Страница 9: ...Live terminals and connections even with device switched off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION The motor restarts automati...

Страница 10: ...he applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be...

Отзывы: