Operating instructions

W3G990-GW22-01

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Function / assignment

KL 1

1

L1

Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz

KL 1

2

L2

Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz

KL 1

3

L3

Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz

PE

PE

Earth connection, PE connection

KL 2

1

NO

Status relay, floating status contact; normally open; close with error

KL2

2

COM

Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA

KL2

3

NC

Status relay, floating status contact; break with error

KL 3

1

RSA

Bus connection RS-485, RSA, MODBUS RTU; SELV

KL 3

2

RSB

Bus connection RS-485, RSB, MODBUS RTU; SELV

KL 3

3 / 10

GND

Signal ground for control interface; SELV

KL 3

4

Ain1 U

Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain1; SELV

KL 3

5

+ 10 V

Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof, power supply for external
devices (e.g. potentiometer), SELV

KL 3

6

Ain1 I

Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only usable as alternative to input
Ain1 U; SELV

KL 3

7

Din1

Digital input 1: enabling of electronics,
enabling: open pin or applied voltage 5-50 VDC
disabling: bridge to GND or applied voltage <1 VDC
reset function: triggers software reset after a level change to <1 VDC; SELV

KL 3

8

Din2

Digital input 2: parameter set switch 1/2, according to EEPROM setting, the valid/used parameter set can be
selected via bus or via digital input DIN2.
Parameter set 1: open pin or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV

KL 3

9

Din3

Digital input 3: controller function of integrated controller, according to EEPROM setting, the controller function
of the integrated controller is normally/inversely selectable per bus or per digital input
normal: open pin or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage <1 VDC; SELV

KL 3

11

Ain2 U

Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV

KL 3

12

+ 20 V

Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for external
devices (e.g. sensors); SELV

KL 3

13

Ain2 I

Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only usable as alternative to
input Ain2 U; SELV

KL 3

14

Aout

Analogue output 0-10 VDC, max. 5 mA, output of the current motor level control coefficient / motor speed
parametrisable curve; SELV

Item no. 50262-5-9970 · ENG · Revision 82539 · Release 2014-05-08 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G990-GW22-01

Страница 1: ...y out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installe...

Страница 2: ...NGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long...

Страница 3: ...ace Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt de...

Страница 4: ...the unit mm 1 Direction of air flow V 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm Item no 50262 5 9970 ENG Revision 82539 Release 2014 05 08 Page 4 1...

Страница 5: ...n rotor Type of protection IP 54 Insulation class F Humidity class F4 1 Mounting position Shaft horizontal or rotor on bottom rotor on top on request Condensate discharge holes Rotor side Operation mo...

Страница 6: ...Bodily harm e g back injuries are possible Two people should remove the device out of its packaging together Check the device for transport damage Damaged devices must no longer be installed Install t...

Страница 7: ...ss section VDE UL VDE mm AWG 3 PE AC 380 480 VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG...

Страница 8: ...ble routing No water may penetrate along the cable in the direction of the cable gland Fans installed lying flat Make sure that the cable is routed in the form of a loop water trap Fig 3 Fan installed...

Страница 9: ...n pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set s...

Страница 10: ...fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the devi...

Страница 11: ...Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up...

Страница 12: ...ve casing against accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and...

Отзывы: