background image

Operating instructions

W3G800-KU21-D1

Translation of the original operating instructions

Impeller not
running smoothly

Imbalance in rotating
parts

Clean the device;
replace it if imbalance
persists after cleaning.
Make sure no
weight clips are
removed during
cleaning.

Motor not turning

Mechanical blockage

Switch off, isolate
from supply and
remove mechanical
blockage.

Line voltage faulty

Check line voltage,
restore power supply.
Attention! The error
message resets
automatically.
Device restarts
automatically without
warning.

Faulty connection

Isolate from supply,
correct connection;
see connection
diagram.

Broken motor winding Replace device
Inadequate cooling

Improve cooling.
Allow the device to
cool down.

Ambient temperature
too high

Reduce the ambient
temperature. Allow
the device to cool
down.

Impermissible
operating point (e.g.
back pressure too
high)

Correct the operating
point. Allow the
device to cool down.

In the event of further malfunctions, contact ebm-papst.

6.1 Warning/status codes

The LED on the electronics housing shows the motor status with various
colors and flash codes. The flash codes have a frequency of 2 Hz.
Each flash code is followed by a pause lasting 3 seconds. The following
colors are used: Green: no warning or fault. Orange: There is a warning.
No user intervention is required for warnings. Red: There is at least one
error. See the following table. If there are multiple simultaneous errors,
their associated flash codes are displayed in succession. If there are
simultaneous warnings and errors, only the errors are displayed.

6.1.1 Warning codes

Number of pulses

Motor status - LED
orange

Message at status
relay

1

Current limitation in
action

2

Line impedance too
high (DC-link voltage
unstable)

3

Power limiter in action

4

Output stage
temperature high

5

Motor temperature high

6

Temperature inside
electronics high

7

DC-link voltage low

8

Braking mode: set in
case of external drive
in opposite direction
at high speed for
lengthy period

Yes

9

Calibration of rotor
position sensor in
progress

10

Actual speed is lower
than run monitoring
speed limit

Yes

11

Open circuit at analog
input or PWM input
for the set value

Yes

13

DC-link voltage high

15

Line voltage high

16

Shake-loose function
activated

6.1.2 Status codes

Manual reset by "Switch off line voltage - wait briefly - switch line
voltage back on" or, if provided,
via the "Fan enable/disable" input

Number of
pulses

Motor status -
LED red

Possible cause Possible

remedy

1

Phase failure or
line undervoltage

Missing phase
Poor power
supply quality

Check line
voltage

3

Output stage
overheating

Electronics
housing
contaminated

Provide better
cooling.
Manual reset
required

4

Communication
error between
master
controller and
slave controller

External
supply applied
via Vout for
setting
parameters.
Internal error

Switch off line
voltage
- wait -
switch back on

6

Motor
overheating

Ambient
temperature too
high
Impermissible
operating point

Reduce
ambient
temperature
Correct
operating point.
Manual reset
required

7

Hall sensor error Internal error

Switch off line
voltage
- wait -
switch back on

8

Motor blocked

Mechanical
blockage

Switch off
- check safe
isolation from
supply -
check
freedom of
movement of
rotor

Item no. 56589-5-9970 · ENU · Change 209539 · Approved 2021-02-01 · Page 14 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G800-KU21-D1

Страница 1: ...o carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following...

Страница 2: ...g in conjunction with open and closed loop control devices If impermissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOTE Electrical or...

Страница 3: ...stationary systems Performing all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter...

Страница 4: ...flow direction V 2 Cable diameter min 6 mm max 12 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Mounting holes for FlowGrid Item no 56589 5 9970 ENU Change 209539 Approved 2021 02 01...

Страница 5: ...100 000 Pa Data obtained at optimum efficiency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 50 kg Size 800...

Страница 6: ...t of the customer system to the public power grid is greater than or equal to 250 times the rated output of the arrangement It is the responsibility of the installation engineer or operator owner of t...

Страница 7: ...with the resistance specifications according to EN 61800 5 1 for the protective earth connection circuit must be verified in the end application Depending on the installation situation it may be neces...

Страница 8: ...ysical separation of these cables in the terminal box may be mandatory Use the partitions inside the terminal box as an aid to routing for this purpose First connect the protective earth PE Connect th...

Страница 9: ...Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value requirement Analog linear Direction of action parameter set 1 Positive heating Direction of action parameter set 2 Po...

Страница 10: ...eristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve param...

Страница 11: ...159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active...

Страница 12: ...operating instructions 4 7 Equivalent circuit diagrams Item no 56589 5 9970 ENU Change 209539 Approved 2021 02 01 Page 12 16 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 793...

Страница 13: ...supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the p...

Страница 14: ...us LED orange Message at status relay 1 Current limitation in action 2 Line impedance too high DC link voltage unstable 3 Power limiter in action 4 Output stage temperature high 5 Motor temperature hi...

Страница 15: ...ls to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test...

Страница 16: ...num Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Onl...

Отзывы: