background image

Operating instructions

W3G800-GV01-01

Translation of the original operating instructions

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
In the event of a fault, the rotor and the impeller will be
energized

The rotor and the impeller have basic insulation.
→ Do not touch the rotor and impeller once installed.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.

Risk of injury
→ Keep out of the device’s danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ After working on the device, remove any tools or other

objects from the device.

1.5 Safety and protective features

DANGER
Guard missing and guard not functioning

Without a guard, hands may become caught up in the device
during operation for example, resulting in serious injury. Loose
parts or items of clothing could be drawn in.
→ The device is a built-in component. As the owner, you are

responsible for ensuring that the device is adequately
safeguarded.# Operate the device only with a fixed
protective device and guard grill.

→ Stop the device immediately if a protective device is

found to be missing or ineffective.

WARNING
Damage to guard grill, parts flying out

The guard grill is not suitable for heavy loads. Parts lying on the
guard grill or falling through the guard grill may be thrown out by
the fan when in operation.
→ Never step on the guard grill or subject the guard grill to load.
→ Do not place any objects on the guard grill.
→ There must be sufficient space around the fan to be able

to get past the fan.

1.6 Electromagnetic radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction
with open- and closed-loop control devices.
If impermissible radiation levels occur following installation, appropriate
shielding measures have to be taken by the user.

NOTE
Electrical or electromagnetic interference after installing
the device in customer equipment.

→ Verify that the entire setup is EMC-compliant.

1.7 Mechanical movement

DANGER
Rotating device

Risk of injury to body parts coming into contact with the rotor or
the impeller.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

DANGER
Ejected parts

Missing protective devices may cause balancing weights or
broken fan blades to be ejected and cause injuries.
→ Take appropriate safety measures.

WARNING
Rotating device

Long hair and dangling items of clothing, jewelry and the like
can become entangled and be pulled into the device. Injuries
can result.
→ Do not wear any loose-fitting or dangling clothing or jewelry

while working on rotating parts.

→ Protect long hair with a cap.

1.8 Emissions

WARNING
Depending on the installation and operating conditions,
the sound pressure level may exceed 70 dB(A).

Risk of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment such as hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature on electronics housing

Risk of burns
→ Ensure sufficient protection against accidental contact.

1.10 Transport

WARNING
Transporting the fan

Injuries from tipping or slipping
→ Wear safety shoes and cut-resistant safety gloves.
→ The fan is only to be transported in its original packaging.
→ The fan is to be transported lying flat, i.e. the motor axis

must be vertical.

→ Secure the fan(s) e.g. with a lashing strip to stop

anything slipping or tipping.

Item no. 50274-5-9970 · ENU · Change 204653 · Approved 2020-08-28 · Page 2 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G800-GV01-01

Страница 1: ...ecialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated w...

Страница 2: ...g in conjunction with open and closed loop control devices If impermissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOTE Electrical or...

Страница 3: ...tenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions an...

Страница 4: ...tion of air flow V 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Mounting holes for FlowGrid Item no 50274 5 9970 ENU Change 204653 Approved 2020 08 2...

Страница 5: ...g a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 50 7 kg Size 800 mm Motor size 150 Rotor surface Painted black Electronics housing material Die cast...

Страница 6: ...the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection p...

Страница 7: ...ss section equal to or greater than that of the phase conductor We recommend the use of 105 C cables Ensure that the minimum cable cross section is at least AWG 26 0 13 mm 4 2 2 Supply connection and...

Страница 8: ...y into the terminal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no wire ends fan out Fig 2 Connect...

Страница 9: ...de for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value requirement Analog l...

Страница 10: ...contact changeover contact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS485 RSA MODBUS RTU...

Страница 11: ...EEPROM setting the integrated controller s direction of action can be selected via bus or digital input Din3 normal pin open or applied voltage 5 50 VDC inverse bridge to GND or applied voltage 1 VDC...

Страница 12: ...supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the p...

Страница 13: ...ly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Only clean when not in motion Do n...

Страница 14: ...rve the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also t...

Отзывы: