Operating instructions

W3G800-GT21-01

Translation of the original operating instructions

No.

Conn.

Designation

Function/assignment

KL 3

6

Ain1 I

Analog input 1, set value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input Ain1U;
SELV

KL 3

7

Din1

Digital input 1: enable electronics,
enable: pin open or applied voltage 5-50 VDC
disable: bridge to GND or applied voltage < 1 VDC
reset function: triggers software reset after a level change to < 1 VDC; SELV

KL 3

8

Din2

Digital input 2: Switching parameter sets 1/2, according to EEPROM setting, the valid or used parameter set
can be selected via bus or via digital input DIN2.
Parameter set 1: pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage < 1 VDC; SELV

KL 3

9

Din3

Digital input 3: according to EEPROM setting, the integrated controller's direction of action can be selected via
bus or digital input Din3;
normal: pin open or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage < 1 VDC; SELV

KL 3

11

Ain2 U

Analog input 2, measured value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input
Ain2I; SELV

KL 3

12

+ 20 V

Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof power supply for external
devices (e.g. sensors); SELV
or: +24 VDC input for parameter setting without line voltage

KL 3

13

Ain2 I

Analog input 2, measured value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input
Ain2U; SELV

KL 3

14

Aout

Analog output 0-10 VDC, max. 5 mA, output of current motor modulation level / motor speed
adjustable curve; SELV

Item no. 50260-5-9970 · ENU · Change 209539 · Approved 2021-02-09 · Page 11 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G800-GT21-01

Страница 1: ...pecialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when working on the device Keep the wo...

Страница 2: ... g in conjunction with open and closed loop control devices If impermissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body par...

Страница 3: ...ntenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited an...

Страница 4: ...ction of air flow V 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Mounting holes for FlowGrid Item no 50260 5 9970 ENU Change 209539 Approved 2021 02 09 Page 4 14 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...ined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 42 8 kg Size 800 mm Motor size 150 Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade material Sheet aluminum insert sprayed with PP plastic Fan housing material Sheet steel galvanized and coated with black plastic RAL 9005 Guard grille material S...

Страница 6: ...is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal to 120 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1 Mechanical connection CAUTION Cutting and crushing hazard when remo...

Страница 7: ...e with the resistance specifications according to EN 61800 5 1 for the protective earth connection circuit must be verified in the end application Depending on the installation situation it may be necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided wit...

Страница 8: ...with the seals provided in the terminal box Route the wire s not included in scope of delivery into the terminal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no wire ends fan out Fig 2 Connecting wires to terminals Seal the terminal box 4 3 3 Cable routing Water must be prevented from reaching the ...

Страница 9: ...ade for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 1 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value requirement Analog linear Direction of action parameter set 1 Positive heating Direction of action parameter set 2 Positive heating Item no 50260 5 9970 ENU Change 209539 Approved 2021 02 09 Page 9 14 ebm papst Mulfingen...

Страница 10: ... contact changeover contact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS485 RSA MODBUS RTU SELV KL 3 2 RSB Bus connection RS485 RSB MODBUS RTU SELV KL 3 3 10 GND Reference ground for control interface SELV KL 3 4 Ain1 U Analog input 1 set value 0 10 V Ri 100 kΩ adjustable curve only usabl...

Страница 11: ...o EEPROM setting the integrated controller s direction of action can be selected via bus or digital input Din3 normal pin open or applied voltage 5 50 VDC inverse bridge to GND or applied voltage 1 VDC SELV KL 3 11 Ain2 U Analog input 2 measured value 0 10 V Ri 100 kΩ adjustable curve only usable as alternative to input Ain2I SELV KL 3 12 20 V Fixed voltage output 20 VDC 20 V 25 10 max 50 mA short...

Страница 12: ... supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the...

Страница 13: ...rly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Only clean when not in motion Do not disconnect the fan from the power supply just switch it off via the control input This will prevent start up of the fan Dirt deposits on the motor housing can cause overheating of the motor Soilin...

Страница 14: ...erve the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 6 3 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into suitabl...

Отзывы: