ebm-papst W3G630-NU33-03 Скачать руководство пользователя страница 15

Operating instructions

W3G630-NU33-03

Translation of the original operating instructions

Impeller not
running smoothly

Imbalance in rotating
parts

Clean the device;
replace it if imbalance
persists after cleaning.
Make sure no
weight clips are
removed during
cleaning.

Motor not turning

Mechanical blockage

Switch off, isolate
from supply and
remove mechanical
blockage.

Line voltage faulty

Check line voltage,
restore power supply.
Attention! The error
message resets
automatically.
Device restarts
automatically without
warning.

Faulty connection

Isolate from supply,
correct connection;
see connection
diagram.

Broken motor winding Replace device
Inadequate cooling

Improve cooling.
Allow the device to
cool down.

Ambient temperature
too high

Reduce the ambient
temperature. Allow
the device to cool
down.

Impermissible
operating point (e.g.
back pressure too
high)

Correct the operating
point. Allow the
device to cool down.

In the event of further malfunctions, contact ebm-papst.

6.1 Warning/status codes

The LED on the electronics housing shows the motor status with various
colors and flash codes. The flash codes have a frequency of 2 Hz.
Each flash code is followed by a pause lasting 3 seconds. The following
colors are used: Green: no warning or fault. Orange: There is a warning.
No user intervention is required for warnings. Red: There is at least one
error. See the following table. If there are multiple simultaneous errors,
their associated flash codes are displayed in succession. If there are
simultaneous warnings and errors, only the errors are displayed.

6.1.1 Warning codes

Number of pulses

Motor status - LED
orange

Message at status
relay

1

Current limitation in
action

2

Line impedance too
high (DC-link voltage
unstable)

3

Power limiter in action

4

Output stage
temperature high

5

Motor temperature high

6

Temperature inside
electronics high

7

DC-link voltage low

8

Braking mode: set in
case of external drive
in opposite direction
at high speed for
lengthy period

Yes

9

Calibration of rotor
position sensor in
progress

Yes

10

Actual speed is lower
than run monitoring
speed limit

Yes

11

Open circuit at analog
input or PWM input
for the set value

Yes

13

DC-link voltage high

15

Line voltage high

16

Shake-loose function
activated

6.1.2 Status codes

Manual reset by "Switch off line voltage - wait briefly - switch line
voltage back on" or, if provided,
via the "Fan enable/disable" input

Number of
pulses

Motor status -
LED red

Possible cause Possible

remedy

1

Phase failure or
line undervoltage

Missing phase
Poor power
supply quality

Check line
voltage

3

Output stage
overheating

Electronics
housing
contaminated

Provide better
cooling.
Manual reset
required

4

Communication
error between
master
controller and
slave controller

External
supply applied
via Vout for
setting
parameters.
Internal error

Switch off line
voltage
- wait -
switch back on

6

Motor
overheating

Ambient
temperature too
high
Impermissible
operating point

Reduce
ambient
temperature
Correct
operating point.
Manual reset
required

7

Hall sensor error Internal error

Switch off line
voltage
- wait -
switch back on

8

Motor blocked

Mechanical
blockage

Switch off
- check safe
isolation from
supply -
check
freedom of
movement of
rotor

Item no. 57630-5-9970 · ENU · Change 230625 · Approved 2022-09-06 · Page 15 / 17

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G630-NU33-03

Страница 1: ...specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated...

Страница 2: ...be thrown out by the fan when in operation Never step on the guard grill or subject the guard grill to load Do not place any objects on the guard grill There must be sufficient space around the fan t...

Страница 3: ...ems with phase conductor grounding or in IT power systems The device is to be used in networks with network quality characteristics as per EN 50160 Using the device only in stationary systems Performi...

Страница 4: ...m tightening torque 4 0 6 Nm The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 3 Tightening torque 1 5 0 2 Nm Item no...

Страница 5: ...of the necessary recess for mounting the fan housing in the end device BG630 D 785 mm BG710 D 830 mm BG800 D 950 mm BG910 D 1050 mm Item no 57630 5 9970 ENU Change 230625 Approved 2022 09 06 Page 5 1...

Страница 6: ...side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article...

Страница 7: ...nforms to IEC 61000 3 12 provided that the short circuit power Ssc at the connection point of the customer system to the public power grid is greater than or equal to 250 times the rated output of the...

Страница 8: ...e that the minimum cable cross section is at least AWG 26 0 13 mm Protective earth contact resistance according to EN 61800 5 1 Compliance with the resistance specifications according to EN 61800 5 1...

Страница 9: ...6228 1 for flexible cable 0 25 mm 4 mm NOTE The cable and cable cross section must be selected taking into account the max starting current of the drive and the type of cable routing see Chapter 4 2 2...

Страница 10: ...e sealing surfaces are clean Screw in the four screws for tightening torque see Chapter 3 1 Product drawing 4 3 4 Cable routing Water must be prevented from reaching the cable gland along the cable NO...

Страница 11: ...eristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve param...

Страница 12: ...159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active...

Страница 13: ...operating instructions 4 7 Equivalent circuit diagrams Item no 57630 5 9970 ENU Change 230625 Approved 2022 09 06 Page 13 17 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 793...

Страница 14: ...supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the p...

Страница 15: ...LED orange Message at status relay 1 Current limitation in action 2 Line impedance too high DC link voltage unstable 3 Power limiter in action 4 Output stage temperature high 5 Motor temperature high...

Страница 16: ...ls to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test...

Страница 17: ...num Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Onl...

Отзывы: