Operating instructions

W3G630-NP04-H1

Translation of the original operating instructions

4.5 Connection diagram

No.

Conn.

Designation

Function/assignment

1

PE

Protective earth

2

PE

Protective earth

3

N

Power supply, neutral conductor

4

-

not used

5

L

Power supply, phase

6

NC

Status relay, floating status contact, break for failure, contact rating 250 VAC / 2 A (AC1) / min. 10 mA; basic
insulation on supply side and reinforced insulation on control interface side

7

COM

Status relay, floating status contact, common connection, contact rating 250 VAC / 2 A (AC1) / min. 10 mA;
basic insulation on supply side and reinforced insulation on control interface side

8

GND

Reference ground for control interface, SELV

9

RSA

RS485 interface for MODBUS, RSA; SELV

10

RSB

RS485 interface for MODBUS, RSB; SELV

11

0-10 V

Analog input (set value) SELV, 0-10 V, Ri = 100 kΩ, adjustable curve

12

+10 V

Fixed voltage output 10 VDC, SELV, +10 V ±3%, max. 10 mA, short-circuit-proof, power supply for external
devices (e.g. pot)

Item no. 57391-5-9970 · ENU · Change 212910 · Approved 2021-03-30 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G630-NP04-H1

Страница 1: ...ecialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated w...

Страница 2: ...ion appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC co...

Страница 3: ...n particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation op...

Страница 4: ...Cable diameter min 4 mm max 10 mm tightening torque 1 8 0 3 Nm 3 Cable diameter min 6 mm max 10 mm tightening torque 1 8 0 3 Nm use must be made of seal provided Cable diameter min 4 mm max 7 mm tigh...

Страница 5: ...motor impeller combination in a standardized measurement setup 3 4 Technical description Size 630 mm Motor size 84 Rotor surface Painted black Terminal box material PP plastic Electronics housing mat...

Страница 6: ...hazard when removing device from packaging Blades can bend Carefully remove the device from its packaging by the fan housing Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CA...

Страница 7: ...rovided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole 4 2 2 Reactive currents Because of the EMC filter integrated for co...

Страница 8: ...er is constantly present at the cable glands To prevent the constant accumulation of water at the cable glands the cable should be routed in a U shaped loop wherever possible If this is not possible a...

Страница 9: ...ontact common connection contact rating 250 VAC 2 A AC1 min 10 mA basic insulation on supply side and reinforced insulation on control interface side 8 GND Reference ground for control interface SELV...

Страница 10: ...witching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power sup...

Страница 11: ...ning agents used If severe corrosion is visible on load bearing or rotating parts switch off the device immediately and replace it Repair of load bearing or rotating parts is not permitted Operate the...

Страница 12: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 Component disposal The products are...

Отзывы: